  Tuotetiedot
| Product type | Temperature transmitter | 
| Product family | MINI Analog | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Rated insulation voltage | 50 V AC/DC | 
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Maximum power dissipation for nominal condition | 235.5 mW | 
| Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) | 
| Protective circuit | Transient protection | 
| Step response (0–99%) | < 200 ms | 
| Maximum temperature coefficient | < 0.02 %/K | 
| Transmission error in the set measuring range | ((50 K / Δ Temp)+ 0.05)% | 
| Transmission error in the full measuring range | ≤ 0.25 % | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) | 
| Max. current consumption | < 21 mA (at 24 V DC) | 
| Power consumption | < 500 mW | 
| Signal | |
| Number of inputs | 1 | 
| Input signal | Temperature | 
| Measurement | |
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) | 
| Temperature measuring range | -50 °C ... 200 °C | 
| Temperature measuring range | min. 50 K | 
| Temperature measuring range: PT100 | -50 °C ... 200 °C (configurable) | 
| Sensor input current | 1 mA (constant) | 
| Max. permissible overall conductor resistance | 10 Ω (Per cable) | 
| Connection technology | 2-, 3-, 4-conductor | 
| Signal | |
| Number of outputs | 1 | 
| Configurable/programmable | Yes | 
| Voltage output signal | 0 V ... 10 V | 
| 10 V ... 0 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| Max. voltage output signal | approx. 12.5 V | 
| Open-circuit voltage | approx. 12.5 V | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Max. current output signal | 23 mA | 
| Short-circuit current | approx. 10 mA | 
| Load/output load voltage output | > 10 kΩ | 
| Load/output load current output | < 500 Ω (at 20 mA) | 
| Ripple | < 20 mVPP (at 500 Ω) | 
| < 20 mVPP (at 10 kΩ) | |
| Connection method | Spring-cage connection | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Dimensional drawing |  | 
| Width | 6.2 mm | 
| Height | 93.1 mm | 
| Depth | 102.5 mm | 
| Color | green (RAL 6021) | 
| Housing material | PBT | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 65 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| ATEX | |
| Identification |  II 3 G Ex nA IIC T4 Gc X | 
| UL, USA/Canada | |
| Identification | UL 508 Recognized | 
| Class I, Div. 2, Groups A, B, C, D T5 | |
| GL | |
| Identification | GL EMC 2 D | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 10 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 10 % | 
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge current load (surge) | |
| Comments | Criterion B | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 10 % | 
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Mounting type | DIN rail mounting | 
| Mounting position | any | 
| Tuotenumero | 2864202 | 
| Pakkausyksikkö | 1 Kappaletta | 
| Vähimmäistilausmäärä | 1 Kappaletta | 
| Tuoteavain | DK1135 | 
| Tuotekoodi | DK1135 | 
| GTIN | 4046356046466 | 
| Paino kappaletta kohti (sis. pakkauksen) | 91,7 g | 
| Paino kappaletta kohti (ilman pakkausta) | 59,9 g | 
| Tullitariffinumero | 85437090 | 
| Alkuperämaa | DE | 
| EU RoHS | |
| Täyttää RoHS-direktiivin vaatimukset | Kyllä | 
| poikkeussäännökset siltä osin kuin ne ovat tiedossa | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia. | 
| EU REACH SVHC | |
| Huomautus REACH-kandidaattiaineesta (CAS-nro) | Lead (CAS-nro: 7439-92-1) | 
Edut
Power supply possible via the foot element (TBUS)
        Optimized temperature measuring range of -50°C to +200°C for increased accuracy
        For 2-, 3-, 4-conductor Pt 100 sensors in accordance with IEC 60751
        Error indication via diagnostic LED and analog signal
        Input and output signals can be configured via DIP switches
        Highly-compact temperature transducer for electrical isolation, conversion, amplification, and filtering of
        Pt 100 signals to create standard signals
        3-way isolation
        PHOENIX CONTACT OY
        
        Niittytie 11, 01300 Vantaa