S-PT-1X2-24DC-1/2"
-
Surge protection device
2882569
Surge protection in the IP67 screw-on module for measuring sensors, direct mounting with 1/2" NPT outer thread, cable gland for the signal line, two-stage protective circuit. HART-compatible. Can be used in safety-related circuits up to SIL 3.
Tuotetiedot
Notes on operation | When the bridge is disconnected, the shield connection is indirectly connected to the housing or reference potential. |
Product type | Surge protection for MCR technology |
Product family | SURGETRAB |
IEC test classification | C1 |
C2 | |
C3 | |
D1 | |
Type | Screw-in module |
Number of positions | 3 |
Surge protection fault message | none |
Wire pairs per module | 1 |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Nominal voltage UN | 24 V DC |
Connection method | Screw connection |
Screw thread | M3 |
Tightening torque | 0.6 Nm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 26 ... 16 |
Dimensional drawing |
|
Width | 33.5 mm |
Height | 33.5 mm |
Depth | 148 mm |
Color | Steel/stainless steel color |
black (RAL 9005) | |
Housing material | Zinc die-cast, surface bronzed and nickel-plated |
Mechanical data | |
Open side panel | No |
Direction of action | Line-Line & Line-Earth Ground |
Maximum continuous operating voltage UC | 40 V DC |
28 V AC | |
Rated current | 450 mA (55 °C) |
Operating effective current IC at UC | ≤ 10 µA |
Protective conductor current IPE | ≤ 2 µA |
Nominal discharge current In (8/20) µs (line-line) | 10 kA |
Nominal discharge current In (8/20) µs (line-ground) | 10 kA (per path) |
Nominal discharge current In (8/20) µs (shield-ground) | 10 kA (optional) |
Pulse discharge current Iimp (10/350) µs | 1 kA |
Total discharge current ITotal (8/20) µs | 20 kA |
Total discharge current ITotal (10/350) µs | 2 kA |
Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA (per path) |
Discharge surge current Imax (8/20) µs maximum (shield-ground) | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 23 A |
Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
Nominal pulse current Ian (10/1000) µs (shield-ground) | 100 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (Direct grounding) |
Output voltage limitation at 1 kV/µs (shield-ground) spike | ≤ 600 V (optional) |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 55 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V (Direct grounding) |
Residual voltage at In (conductor-conductor) | ≤ 55 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
Voltage protection level Up (line-line) | ≤ 80 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (shield-ground) | ≤ 600 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up static (line-line) | ≤ 50 V (C2 - 10 kV / 5 kA) |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-earth) | ≤ 100 ns |
Response time tA (shield-ground) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
typ. 0.2 dB (≤ 300 kHz / 150 Ω) | |
Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 6 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 2 MHz |
Resistance per path | 2.2 Ω ±10 % |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C2 - 10 kV / 5 kA |
D1 - 1 kA | |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
D1 - 1 kA | |
Impulse durability (shield-ground) | C2 - 10 kV/5 kA |
D1 - 1 kA |
Ambient conditions | |
Degree of protection | IP67 |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Air clearances and creepage distances | |
Standards/regulations | IEC 60664-1 / VDE 0110-1 |
Standards/specifications | IEC 61643-21 |
Note | 2002 |
Mounting type | direct screw connection |
Tuotenumero | 2882569 |
Pakkausyksikkö | 1 Kappaletta |
Vähimmäistilausmäärä | 1 Kappaletta |
Tuoteavain | CL2231 |
Tuotekoodi | CL2231 |
GTIN | 4046356091657 |
Paino kappaletta kohti (sis. pakkauksen) | 424,9 g |
Paino kappaletta kohti (ilman pakkausta) | 363,84 g |
Tullitariffinumero | 85369010 |
Alkuperämaa | DE |
ECLASS
ECLASS-13.0 | 27171501 |
ECLASS-15.0 | 27171501 |
ETIM
ETIM 9.0 | EC000943 |
UNSPSC
UNSPSC 21.0 | 39121600 |
EU RoHS | |
Täyttää RoHS-direktiivin vaatimukset | Kyllä |
poikkeussäännökset siltä osin kuin ne ovat tiedossa | 6(c), 7(a) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia.
|
EU REACH SVHC | |
Huomautus REACH-kandidaattiaineesta (CAS-nro) | Lead (CAS-nro: 7439-92-1) |
SCIP | 022417fa-7a8a-42c1-b9e4-1ad34b5262a7 |
Yhteensopivat tuotteet
Edut
Easiest field mounting with standardized thread
Versatile in use with universal protective circuit
Use under extreme ambient conditions with robust design
PHOENIX CONTACT OY