F-MS 1100 ST
-
Type 2 surge protection plug
2909844
Surge protection plug type 2, spark gap with high insulation voltage strength, used only as replacement plug for the corresponding complete item.
Detalii despre produs
| General | |
| Note | The F-MS 1100 ST protective plug is only to be used with a VAL-MS 400 ST in series connection. It is not designed for direct use on mains voltage. |
| Uagn > 1100 V | |
| At altitudes > 2000 m (amsl), a lateral distance of 2 mm must be maintained between live and grounded parts. | |
| Product family | VALVETRAB MS |
| IEC test classification | II |
| T2 | |
| EN type | T2 |
| IEC power supply system | IT |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Surge protection fault message | optical |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal frequency fN | 50 Hz |
| 60 Hz |
| Connection method | pluggable |
| Dimensional drawing |
|
| Width | 17.5 mm |
| Height | 52.4 mm |
| Depth | 55.3 mm |
| Horizontal pitch | 1 Div. |
| Color | black (RAL 9005) |
| gray (RAL 7042) | |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PA 6.6 |
| Material group | I |
| Housing material | PA 6.6 |
| Mode of protection | L-PE (for IT systems without N in series with a VAL-MS plug) |
| Direction of action | N-PE |
| Nominal frequency fN | 50 Hz |
| 60 Hz | |
| Maximum continuous operating voltage UC | 260 V AC |
| Protective conductor current IPE | ≤ 3 µA |
| Nominal discharge current In (8/20) µs | 20 kA |
| Maximum discharge current Imax (8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA (in series with a VAL-MS plug) |
| Voltage protection level Up | ≤ 3 kV |
| Front-of-wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 3 kV |
| Response time tA | ≤ 100 ns |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 5000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g |
| Vibration (operation) | 5g |
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
| Mounting type | on base element |
| Număr articol | 2909844 |
| Unitate de ambalare | 1 Bucată |
| Cantitate minimă pentru comandă | 10 Bucată |
| Indicație | Produs la comandă (nereturnabil) |
| Cod produs | CL1321 |
| GTIN | 4055626394589 |
| Greutate pe bucată (inclusiv ambalajul) | 54,9 g |
| Greutate pe bucată (fără ambalaj) | 32,61 g |
| Cod tarifar vamal | 85363010 |
| Țara de origine | DE |
ECLASS
| ECLASS-13.0 | 27171292 |
| ECLASS-15.0 | 27171292 |
ETIM
| ETIM 10.0 | EC002496 |
UNSPSC
| UNSPSC 21.0 | 39121600 |
| EU RoHS | |
| Îndeplineşte cerinţele conform directivei RoHS | Da (Nicio reglementare privind excepţiile) |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-E
Nu există substanțe periculoase peste valorile limită
|
| EU REACH SVHC | |
| Trimitere la substanţa candidată REACH (nr. CAS) | Nicio substanţă cu un procentaj masic mai mare de 0,1 % |