ECM-UC-10A-UI-REL
-
Current measuring transducer
1698164
Current measuring transducers for measuring AC, DC, and distorted currents. Configuration via USB-C interface via the web server (without 24 V DC). Four current measuring ranges: 0 A ... 0.1 A to 0 A ... 12.5 A. Relay output, Standard configuration, Push-in connection
Descărcare gratuită disponibilă.
Descărcări
Detalii despre produs
| Note on application | |
| Note on application | As things stand now, we are preparing the product so that, as of December 11, 2027, it will comply with the requirements of the EU Cyber Resilience Act (CRA) based on the information currently available regarding the CRA. |
| Product type | Current measuring transducer |
| Insulation characteristics | |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
| Overvoltage category | III (300 V) |
| Pollution degree | 2 |
| Step response (10-90%) | 200 ms (AC/DC) |
| 20 ms (DC) | |
| Maximum temperature coefficient | < 0.02 %/K |
| Maximum transmission error | 0.5 % (of nominal range value under nominal conditions) |
| Rated insulation voltage | 300 V AC (to earth) |
| Electrical isolation IEC 61010-2-030 | |
| Standards/regulations | IEC 61010-2-030 |
| Measuring category | III (300 V) |
| Electrical isolation Input/output | |
| Test voltage | 4 kV AC (50 Hz, 60 s) |
| Electrical isolation Input/power supply | |
| Test voltage | 4 kV AC (50 Hz, 60 s) |
| Electrical isolation Output/supply | |
| Test voltage | 2 kV AC (50 Hz, 60 s) |
| Supply | |
| Nominal supply voltage range | 12 V DC ... 24 V DC -20 % ... +25 % |
| Supply voltage range | 9.6 V DC ... 30 V DC |
| Power consumption | ≤ 2.3 W (30 V DC) |
| Signal: digital | |
| Voltage input signal | 0 V DC ... 30 V DC |
| Current input signal | 2 mA ... 15 mA |
| Measurement | |
| Input current range | 0 A AC ... 10 A AC |
| -10 A DC ... 10 A DC | |
| Measuring range | 0 A AC/DC ... 0.1 A AC/DC |
| 0 A AC/DC ... 1 A AC/DC | |
| 0 A AC/DC ... 5 A AC/DC | |
| 0 A AC/DC ... 10 A AC/DC | |
| Setting range for min. input current | 0 A AC/DC ... 100 mA AC/DC |
| Setting range for max. input current | 0 A AC/DC ... 12.5 A AC/DC (DIN/EN 61010-1) |
| 0 A AC/DC ... 10 A AC/DC (UL 61010-1) | |
| -12.5 A DC ... 12.5 A DC (DIN/EN 61010-1) | |
| -10 A DC ... 10 A DC (UL 61010-1) | |
| Overload capacity | 2 x IN |
| Surge strength | 10 x IN |
| Frequency measuring range | 0 Hz ... 100 Hz |
| 0 Hz ... 200 Hz | |
| 0 Hz ... 500 Hz | |
| 0 Hz ... 1000 Hz | |
| Curve type | AC, DC or distorted currents |
| Switching: Relay | |
| Contact switching type | 1 changeover contact |
| Contact material | AgNi |
| Minimum switching voltage | 12 V (10 mA) |
| Maximum switching voltage | 250 V AC |
| 48 V DC | |
| Limiting continuous current | 6 A AC (250 V AC, 50/60 Hz) |
| 1 A DC (48 V DC) | |
| Signal: Voltage/current | |
| Voltage output signal | 0 V ... 10 V |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| 2 V ... 10 V | |
| -10 V ... 10 V | |
| -5 V ... 5 V | |
| 10 V ... -10 V | |
| 5 V ... -5 V | |
| 10 V ... 0 V | |
| 5 V ... 0 V | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Load/output load voltage output | > 10 kΩ |
| Load/output load current output | < 500 Ω |
| Signal: digital | |
| Max. voltage output signal | 24 V DC |
| Max. current output signal | ≤ 100 mA |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 13 |
| WBM | |
| Designation | WBM: Default address, USB-C interface |
| IP address | 192.168.128.1 |
| Item dimensions | |
| Width | 22.6 mm |
| Height | 106.7 mm |
| Depth | 113.8 mm |
| Depth (Device depth (DIN rail mounting)) | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing material | PA 6.6-FR |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| -40 °F ... 140 °F | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| UL, USA/Canada | |
| Identification | Ind. Cont. Eq. E238705-E196811 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Noise immunity | EN 61000-6-2 |
| Noise emission | |
| Standards/regulations | EN 61000-6-4 |
| Standards/regulations | IEC 61010-1 |
| Standards/regulations | IEC/EN 61131-2 (type 3) |
| Standards/regulations | IEC/EN 61131-2 (type 3) |
| Mounting position | vertical or horizontal |
| Număr articol | 1698164 |
| Unitate de ambalare | 1 Bucată |
| Cantitate minimă pentru comandă | 1 Bucată |
| Cod produs | CMMA33 |
| GTIN | 4067923262850 |
| Greutate pe bucată (inclusiv ambalajul) | 170 g |
| Greutate pe bucată (fără ambalaj) | 113,5 g |
| Cod tarifar vamal | 85043129 |
| Țara de origine | DE |
ECLASS
| ECLASS-13.0 | 27210123 |
| ECLASS-15.0 | 27210123 |
ETIM
| ETIM 10.0 | EC002475 |
UNSPSC
| UNSPSC 21.0 | 39121000 |
| EU RoHS | |
| Îndeplineşte cerinţele conform directivei RoHS | Da |
| reglementări excepţionale, dacă sunt cunoscute | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
Un tabel de declarații China RoHS legat de articol poate fi găsit în zona de descărcare a articolului respectiv la „Declarația producătorului”. Nu se emite și nu este necesar niciun tabel de declarații China RoHS pentru toate articolele EFUP-E.
|
| EU REACH SVHC | |
| Trimitere la substanţa candidată REACH (nr. CAS) | Lead (nr. CAS: 7439-92-1) |
| 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol (nr. CAS: 79-94-7) | |