CTM 1X2- 60DC
-
Surge protection plug
2838568
LSA-PLUS plug (COMTRAB CTM) with protection for conductor pairs in floating signal circuits. Nominal voltage: 60 V DC
Tämä tuote edellyttää muita tuotteita, jotta sitä voidaan käyttää.
Pakolliset lisätarvikkeet
Tuotetiedot
Product type | Surge protection for MCR technology |
Product family | COMTRAB |
IEC test classification | B2 |
C1 | |
C2 | |
C3 | |
D1 | |
Type | LSA-PLUS module |
Surge protection fault message | none |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Wire pairs per module | 1 |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Nominal voltage UN | 60 V DC |
Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
Dimensional drawing |
|
Width | 9.4 mm |
Height | 21 mm |
Depth | 52.4 mm |
Color | black (RAL 9005) |
copper color | |
Flammability rating according to UL 94 | V-0 |
Housing material | PA 6.6 |
Mechanical data | |
Open side panel | No |
Direction of action | Line-Line & Line-Earth Ground |
Maximum continuous voltage UC | 60 V DC |
50 V AC | |
Rated current | 380 mA AC (25 °C) |
150 mA DC (25 °C) | |
Operating effective current IC at UC | ≤ 70 µA |
Protective conductor current IPE | ≤ 2 µA |
Nominal discharge current In (8/20) µs (line-line) | 5 kA |
Nominal discharge current In (8/20) µs (line-ground) | 5 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 1 kA |
Total discharge current ITotal (8/20) µs | 10 kA |
Total discharge current ITotal (10/350) µs | 2.5 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 100 A |
Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 160 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
Residual voltage at In (conductor-conductor) | ≤ 95 V |
Residual voltage at In (conductor-ground) | ≤ 60 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 35 V |
Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 12 V |
Voltage protection level Up (line-line) | ≤ 200 V (C2 - 10 kV / 5 kA) |
≤ 160 V (C3 - 100 A) | |
Voltage protection level Up (line-earth) | ≤ 700 V (C2 - 10 kV / 5 kA) |
≤ 700 V (C3 - 100 A) | |
Voltage protection level Up static (line-line) | ≤ 95 V (C2 - 10 kV / 5 kA) |
≤ 35 V (C3 - 100 A) | |
Voltage protection level Up static (line-earth) | ≤ 90 V (C2 - 10 kV / 5 kA) |
≤ 12 V (C3 - 100 A) | |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 500 kHz / 100 Ω) |
Cut-off frequency fg (3 dB), sym. in 100 Ω system | typ. 2 MHz |
Capacity (Core-Core) | typ. 1.2 nF |
Resistance per path | 3.3 Ω 20 % |
Surge protection fault message | none |
Impulse durability (line-line) | B2 - 4 kV / 100 A |
C2 - 10 kV / 5 kA | |
C3 - 100 A | |
Impulse durability (line-earth) | B2 - 4 kV / 100 A |
C2 - 10 kV / 5 kA | |
C3 - 100 A | |
D1 - 1 kA | |
Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 75 °C |
Altitude | ≤ 2000 m (amsl) |
Standards/specifications | IEC 61643-21 |
Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
Standards/specifications | EN 61643-21 |
Note | 2001 + A1:2009 + A2:2013 |
Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
Tuotenumero | 2838568 |
Pakkausyksikkö | 10 Kappaletta |
Vähimmäistilausmäärä | 1 Kappaletta |
Tuoteavain | CL3211 |
Tuotekoodi | CL3211 |
GTIN | 4017918819736 |
Paino kappaletta kohti (sis. pakkauksen) | 8,9 g |
Paino kappaletta kohti (ilman pakkausta) | 8,9 g |
Tullitariffinumero | 85363010 |
Alkuperämaa | DE |
ECLASS
ECLASS-13.0 | 27171501 |
ETIM
ETIM 9.0 | EC000943 |
UNSPSC
UNSPSC 21.0 | 39121600 |
EU RoHS | |
Täyttää RoHS-direktiivin vaatimukset | Kyllä |
poikkeussäännökset siltä osin kuin ne ovat tiedossa | 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia.
|
EU REACH SVHC | |
Huomautus REACH-kandidaattiaineesta (CAS-nro) | Aineen pitoisuus ei ole yli 0,1 %. |
Yhteensopivat tuotteet
Edut
Space-saving due to compact design
Flexible fields of application with modular protective plug
Can be used in LSA-PLUS disconnect and control strips or CT-TERMIBLOCK via adapted connection technology
PHOENIX CONTACT OY
Niittytie 11, 01300 Vantaa