The Auto Current Balancing ACB technology of the QUINT ORING modules doubles the service life of redundantly operated power supplies by evenly utilizing the power supply units. The load current is automatically distributed symmetrically.
QUINT-ORING/24DC/2X40/1X80
-
Redundancy module
2902879
Active QUINT redundancy module for DIN rail mounting with ACB (Auto Current Balancing) Technology and monitoring functions, input: 24 V DC/2x 40 A, output: 24 V DC/1 x 80 A, including mounted UTA 107/30 universal DIN rail adapter
Tuotetiedot
UL Recognized
Hyväksyntätunnus: E211944EAC
Hyväksyntätunnus: RU S-DE.BL08.W.00764NK
Hyväksyntätunnus: TA25015MNimellisjännite UN | Nimellisvirta IN | Poikkipinta AWG | Poikkipinta mm2 | |
---|---|---|---|---|
500 V | 63 A | - 10 |
UL Listed
Hyväksyntätunnus: E123528cUL Listed
Hyväksyntätunnus: E123528RINA
Hyväksyntätunnus: ELE362819XGABS
Hyväksyntätunnus: 20-2022537-PDADNV
Hyväksyntätunnus: TAA000011FIECEE CB Scheme
Hyväksyntätunnus: DE/PTZ/0044cUL Listed
Hyväksyntätunnus: E199827UL Listed
Hyväksyntätunnus: E199827Yhteensopivat tuotteet
Edut
Usein kysytyt kysymykset
Does the QUINT-ORING/24DC/2X40/2X40 have integrated surge protection?
Yes, the QUINT-ORING/24DC/2X40/2X40 has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the r... Näytä lisää
Yes, the QUINT-ORING/24DC/2X40/2X40 has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply. The fault is signaled via the "Red OK" relay (13/14) and the LED.
Näytä vähemmänWhat is "ACB"?
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3... Näytä lisää
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3 V. Thanks to the balanced utilization and the lower load on an individual power supply, the service life of the redundant system can be doubled.
Näytä vähemmän