Surge protection plug - CLT-10P/2-2-12V-I-P
1088569

Surge protection plug, directly pluggable on 2 terminal blocks, with integrated status indicator on the module for a 2-wire floating signal circuit. Nominal voltage: 12 V DC

Pentru operarea acestui produs, sunt necesare și alte produse. Accesoriu necesar

Detalii despre produs




IEC test classification C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Product type Surge protection for MCR technology
Insulation characteristics
Overvoltage category III
Pollution degree 3

Connection method pluggable

Desen dimensional
Width 10.3 mm
Height 53.25 mm
Depth 81.9 mm

Color light grey RAL 7035
Flammability rating according to UL 94 V-0
Insulating material PA 6.6+GV 20 %
Housing material PA 6.6+GV 20 %

Mechanical data
Open side panel No

Maximum continuous voltage UC 15 V DC
10 V AC
Rated current 600 mA (80 °C)
Operating effective current IC at UC ≤ 150 µA
Residual current IPE ≤ 1 µA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 40 V (C1 - 700 V/350 A)
≤ 35 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 900 V (C1 - 2 kV / 1 kA)
≤ 900 V (C2 - 10 kV / 5 kA)
≤ 1050 V (C3 - 100 A)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 8,5 MHz / 150 Ω)
Input attenuation aE, asym. typ. 0.3 dB (≤ 14,5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 60 MHz
Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system typ. 60 MHz
Capacity (Core-Core) typ. 45 pF
Capacity (line-signalground) typ. 30 pF
Surge protection fault message optical
Max. required back-up fuse 630 mA (T)
Impulse durability (line-line) C1 - 700 V / 350 A
C3 - 100 A
Impulse durability (line-earth) C1 - 2 kV / 1 kA
C2 – 10 kV / 5 kA
C3 - 100 A
D1 - 1,25 kA
Pulse reset time (line-earth) ≤ 30 ms

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 5g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
10g (Half-sine / 8 ms / 3x ±X, ±Y, ±Z)
5g (Half-sine / 30 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 0,58g (5 ... 150 Hz / 5 h / X, Y, Z)
1g (5 ... 2000 Hz / 5 h / X, Y, Z)

Standards/specifications IEC 61643-21
Standards/specifications EN 61643-21

Mounting type on base element

Număr articol 1088569
Unitate de ambalare 1 Bucată
Cantitate minimă pentru comandă 1 Bucată
Cod produs CL2171
GTIN 4055626889832
Greutate pe bucată (inclusiv ambalajul) 47,26 g
Greutate pe bucată (fără ambalaj) 27,3 g
Cod tarifar vamal 85363010
Țara de origine DE


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

REACh SVHC Lead 7439-92-1

Avantajele dumneavoastră

Easy installation due to Push-in terminal blocks with pluggable surge protection
Superior system availability thanks to high-performance protective circuit with integrated overload protection
Quick and easy diagnostics with optional remote signaling for integration into digital infrastructures
Three become two - use just two terminal blocks to protect two signal paths in an overall width of 10.3 mm
Future-proof - satisfies international standards and directives, such as the DB RIL 819.0808 railway directive