The Auto Current Balancing ACB technology of the QUINT ORING modules doubles the service life of redundantly operated power supplies by evenly utilizing the power supply units. The load current is automatically distributed symmetrically.
QUINT-ORING/24DC/2X20/1X40
-
Redundancy module, with protective coating
2320186
Active QUINT redundancy module for DIN rail mounting with ACB (Auto Current Balancing) Technology and monitoring functions, input: 24 V DC/2x 20 A, output: 24 V DC/1 x 40 A, including mounted UTA 107/30 universal DIN rail adapter
Detalii despre produs
UL Recognized
ID de înregistrare: E211944UL Listed
ID de înregistrare: E123528cUL Listed
ID de înregistrare: E123528DNV
ID de înregistrare: TAA000011FIECEE CB Scheme
ID de înregistrare: DE/PTZ/0044NK
ID de înregistrare: TA25015M| Tensiune nominală UN | Curent nominal IN | Secțiune transversală AWG | Secțiune transversală mm2 | |
|---|---|---|---|---|
| keine | ||||
| 500 V | 63 A | - 10 | ||
EAC
ID de înregistrare: RU S-DE.BL08.W.00764ATEX
ID de înregistrare: DEKRA_20ATEX0136_XIECEx
ID de înregistrare: IECEx DEK 20.0082XCCC
ID de înregistrare: 2024322303005876cUL Listed
ID de înregistrare: E199827UL Listed
ID de înregistrare: E199827INMETRO
ID de înregistrare: DNV 22.0237 XNEPSI-EX
ID de înregistrare: GYJ21.1003XEAC Ex
ID de înregistrare: KZ 7500525010102095Produse compatibile
Avantajele dumneavoastră
Întrebări frecvente
Is there a signal if there is a cable break on the output side or if a cable is not connected?
No. The QUINT4-ORING/12-24DC/2X20/2X20 is recommended as an alternative for signaling this.
Does the item have integrated surge protection?
Yes, the item has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply.... Vezi mai mult
Yes, the item has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply. The fault is signaled via the "Red OK" relay (13/14) and the LED.
Vezi mai puținWhat is "ACB"?
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3... Vezi mai mult
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3 V. Thanks to the balanced utilization and the lower load on an individual power supply, the service life of the redundant system can be doubled.
Vezi mai puțin