Evaluation unit - MINI MCR-2-FM-RC-PT 2904508

Fault monitoring module with plug-in connection technology for evaluating and reporting group errors from the FM system and for monitoring the supply voltages. Error message via N/C contact. Push-in connection technology, standard configuration

Detalii despre produs


The fault monitoring module with plug-in connection technology is used to evaluate and report group errors from the fault monitoring system of up to 115 connected MINI Analog Pro signal conditioners via the ME 6,2 TBUS-2 DIN rail connector (Order No.: 2869728). You can also monitor the supply voltages of MINI MCR-2-PTB(-PT) power terminals (Order No.: 2902066, 2902067). Drawing off the supply is also possible. The error is reported via an N/C contact. The error reporting module supports NFC communication.



Signal
Number of outputs 1
Voltage output signal 9.6 V DC ... 29.7 V DC
Max. current output signal 3.2 A
Switching
Output name Switching output
Maximum switching voltage 30 V DC
Max. switching current 50 mA

Signal
Description of the input Voltage input for redundancy monitoring
Number of inputs 1
Voltage input signal 9.9 V DC ... 30 V DC

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
China RoHS For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Rated insulation voltage 50 V AC/DC (effective)
Electrical isolation Basic insulation according to EN 61010
Electrical isolation Input, power supply and output to the switching output
Test voltage 1500 V AC (50 Hz, 1 min.)
Test voltage input/output 1.5 kV AC (50 Hz, 1 min.)
Maximum temperature coefficient < 0.01 %/K
Supply
Supply voltage range 12 V DC ... 24 V DC -20 % ... +25 % (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption < 16 mA (at 24 V DC)
Power consumption < 410 mW (at 24 V DC)

Width 6.2 mm
Height 109.81 mm
Depth 119.2 mm

Status display Yellow LED (switching output)
Operating voltage display Green LED
Indication Red LED

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Mounting type DIN rail mounting
Mounting position any

CE
Identification CE-compliant
CCC / China-Ex
Identification Ex nA IIC T4 Gc
Certificate NEPSI GYJ20.1320X
ATEX
Identification  II 3 G Ex ec IIC T4 Gc
Certificate BVS 20 ATEX E 014X
DNV GL data
Temperature B
Humidity B
Vibration A
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board
UL, USA/Canada
Identification UL 508 Listed
Identification Class I, Div. 2, Groups A, B, C, D T6
Identification Class I, Zone 2, Group IIC T6
Shipbuilding approval
Certificate DNV GL TAA00002UA
IECEx
Identification Ex ec IIC T4 Gc
Certificate IECEx BVS 20.0010X

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Surge current load (surge)
Standards/regulations EN 61000-4-5
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Electrostatic discharge
Standards/regulations EN 61000-4-2
Comments Safety measures must be taken to prevent electrostatic discharge.

Degree of protection IP20 (not assessed by UL)
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm2 ... 2.5 mm2 (with ferrule)
Conductor cross section solid 0.14 mm2 ... 2.5 mm2 (without ferrule)
Conductor cross section flexible 0.14 mm2 ... 2.5 mm2
Conductor cross section AWG 24 ... 12 (flexible)

Electrical isolation Basic insulation according to EN 61010
GB Standard
Standards/regulations GB 3836.1
Standards/regulations GB 3836.8

Insulation characteristics
Overvoltage category II
Degree of pollution 2


Cod comandă 2904508
Unitate de ambalare 1 pc
Cantitate minimă pentru comandă 1 pc
Pagina de catalog Pagina 110 (C-5-2019)
GTIN 4046356857390
Greutate pe bucată (inclusiv ambalajul) 121,2 GRM
Greutate pe bucată (fără ambalaj) 96,3 GRM
Cod tarifar vamal 85437090
Țara de origine DE



UL Listed

cUL Listed

cULus Listed

cULus Listed

ATEX

UL Listed

cUL Listed

EAC Ex