A safe redundant system is the result of the parallel connection of two power supply units which are decoupled from one another. To further increase system availability, QUINT DIODE provides the solution: decoupling with diode.
QUINT4-DIODE/48DC/2X20/1X40
-
Redundancy module
2907720
DIN rail diode module 48 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.
Tuotetiedot
UL Recognized
Hyväksyntätunnus: E211944EAC
Hyväksyntätunnus: RU S-DE.BL08.W.00764UL Listed
Hyväksyntätunnus: E123528cUL Listed
Hyväksyntätunnus: E123528DNV
Hyväksyntätunnus: TAA000011FNK
Hyväksyntätunnus: TA25015MNimellisjännite UN | Nimellisvirta IN | Poikkipinta AWG | Poikkipinta mm2 | |
---|---|---|---|---|
500 V | 63 A | - 10 |
ATEX
Hyväksyntätunnus: DEKRA 20ATEX0041 XEAC Ex
Hyväksyntätunnus: RU C-DE.HB49.B.00004IECEx
Hyväksyntätunnus: DEK 20.0022XcUL Listed
Hyväksyntätunnus: FILE E 199827UL Listed
Hyväksyntätunnus: E199827INMETRO
Hyväksyntätunnus: DNV 22.0238 XNEPSI-EX
Hyväksyntätunnus: GYJ20.1591XCCC
Hyväksyntätunnus: 2020322303003426Yhteensopivat tuotteet
Edut
Usein kysytyt kysymykset
Is this module also suitable for series connection of power supplies?
No, the item can also be used in a series connection of power supplies. Correct wiring can protect the power supplies from critical voltages at the time of switch-on and switch-off, especially with capacitive loads.
NOTE:
Since "-" is n...
Näytä lisää
No, the item can also be used in a series connection of power supplies. Correct wiring can protect the power supplies from critical voltages at the time of switch-on and switch-off, especially with capacitive loads.
NOTE:
Since "-" is not connected for the protection of a series circuit, this device is not operated in accordance with its specification.
Can the item also be used to decouple 110 V power supplies?
The integrated transient surge protection prevents use with 110 V voltages. However, the diodes are designed for up to 150 V. If "-" is not connected and is routed past the module, 110 V power supplies can also be decoupled from each other.
NOT...
Näytä lisää
The integrated transient surge protection prevents use with 110 V voltages. However, the diodes are designed for up to 150 V. If "-" is not connected and is routed past the module, 110 V power supplies can also be decoupled from each other.
NOTE:
Since "-" must not be connected for use with 110 V voltages, this device is not operated in accordance with its specification if used with that kind of wiring.