PS-EE-2G-DIODE/12-48DC/2X10/SC
   - 
  Redundancy module
    
      1584245
      
      
    
  
      Redundancy module ESSENTIAL DIODE, DIN rail mounting, 12 V DC ... 48 V DC, 2x 10 A DC
Tuotetiedot
| Nominal input voltage range | 12 V DC ... 48 V DC | 
| Input voltage range | 10 V DC ... 60 V DC | 
| Nominal input current (IN) | 2x 10 A DC (-20 °C ... 45 °C) | 
| 1x 20 A DC (-20 °C ... 45 °C) | |
| Reverse polarity protection | yes, < 60 V | 
| Voltage drop, input/output | typ. 0.75 V | 
| Transient surge protection | Varistor | 
| Efficiency | ≥ 94 % (≥ 12 V DC) | 
| ≥ 96 % (≥ 24 V DC) | |
| ≥ 98 % (≥ 48 V DC) | |
| Nominal output voltage | UIn - 0,8 V | 
| Nominal output current (IN) | 20 A | 
| Derating | 60 °C ... 70 °C (2 % / K) | 
| Conductor connection | |
| Connection method | Screw connection | 
| rigid | 0.2 mm² ... 6 mm² | 
| flexible | 0.2 mm² ... 4 mm² | 
| flexible with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² | 
| 1.5 mm² (recommended) | |
| flexible with ferrule with plastic sleeve | 0.25 mm² ... 4 mm² | 
| 1.5 mm² (recommended) | |
| rigid (AWG) | 24 ... 10 (Cu) | 
| Stripping length | 8 mm (rigid/flexible/ferrule without plastic sleeve) | 
| 11 mm (Ferrule with plastic sleeve) | |
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Drive form screw head | Slotted L | 
| Conductor connection | |
| Connection method | Screw connection | 
| rigid | 0.5 mm² ... 16 mm² | 
| flexible | 0.5 mm² ... 16 mm² | 
| flexible with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² | 
| 4 mm² (recommended) | |
| flexible with ferrule with plastic sleeve | 0.5 mm² ... 16 mm² | 
| 4 mm² (recommended) | |
| rigid (AWG) | 20 ... 6 (Cu) | 
| Stripping length | 10 mm (rigid/flexible/ferrule without plastic sleeve) | 
| 13 mm (Ferrule with plastic sleeve) | |
| Tightening torque | 1.2 Nm ... 1.5 Nm | 
| Drive form screw head | Slotted L | 
| Conductor connection | |
| Connection method | Push-in connection | 
| rigid | 0.2 mm² ... 1.5 mm² | 
| flexible | 0.2 mm² ... 1.5 mm² | 
| flexible with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| flexible with ferrule with plastic sleeve | 0.25 mm² ... 0.75 mm² | 
| rigid (AWG) | 24 ... 16 (Cu) | 
| Stripping length | 10 mm (rigid/flexible/ferrule without plastic sleeve) | 
| 99 mm (Ferrule with plastic sleeve) | |
| LED signaling | |
| Types of signaling | DC OK (green) | 
| Signal threshold | Input1 OK (LED lights up green) | 
| Input2 OK (LED lights up green) | |
| Signal output Relay 13/14 | |
| Connection labeling | 3.1, 3.2 | 
| Switch contact (floating) | N/O contact | 
| Digital | 30 V DC | 
| 1 A | |
| Signal option | Redundancy OK | 
| Signal output Relay 23/24 | |
| Connection labeling | 3.3, 3.4 | 
| Switch contact (floating) | N/O contact | 
| Digital | 30 V DC | 
| 1 A | |
| Signal option | Redundancy OK | 
| Insulation voltage input/output | 500 V AC | 
| Insulation voltage input, output / housing | 500 V AC | 
| Product type | Redundancy module | 
| Product family | ESSENTIAL DIODE | 
| MTBF (IEC 61709, SN 29500) | > 2992278 h (25 °C) | 
| > 1874605 h (40 °C) | |
| > 1594343 h (45 °C) | |
| LED | yes | 
| Insulation characteristics | |
| Protection class | III | 
| Degree of pollution | 2 | 
| Item dimensions | |
| Width | 40 mm | 
| Height | 124 mm | 
| Depth | 126 mm | 
| Installation dimensions | |
| Installation distance right/left | 10 mm / 10 mm | 
| Installation distance top/bottom | 30 mm / 30 mm | 
| Mounting type | DIN rail mounting | 
| Mounting position | horizontal DIN rail NS 35, EN 60715 | 
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 | 
| Housing material | Metal | 
| Housing material | Aluminum (AlMg3) / sheet steel, zinc-plated | 
| Foot latch material | Sheet steel, zinc-plated | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 70 °C (Derating: > 45°C; 2.5%/K ) | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Maximum altitude | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) | 
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) | 
| Dry heat (IEC 60068-2-2) | 70 °C (16 h) | 
| Humid heat cyclic (IEC 60068-2-30) | 55 °C (95 %, 2 x 23 h) | 
| Cold (IEC 60068-2-1) | - 25 °C (16 h) | 
| Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) | 
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6) | 
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Electrical safety | |
| Standard designation | Electrical safety | 
| Standards/specifications | IEC 61010-1 (SELV) | 
| Protective extra-low voltage | |
| Standard designation | Protective extra-low voltage | 
| Standards/specifications | IEC 61010-1 (SELV) | 
| UL | |
| Identification | UL/C-UL Listed UL 61010-1 | 
| UL | |
| Identification | UL/C-UL Listed UL 61010-2-201 | 
| CB scheme | |
| Identification | CB scheme (IEC 61010-1, IEC 61010-2-201, IEC 62368-1) | 
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | 
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC | 
| Noise immunity | EN 61000-6-2:2019 | 
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 | 
| Fast transients (burst) | |
| Input | 1 kV (Test Level 2 - asymmetrical) | 
| Output | 1 kV (Test Level 2 - asymmetrical) | 
| Signal | 1 kV (Test Level 3 - asymmetrical) | 
| Comments | Criterion A | 
| Surge voltage load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge voltage load (surge) | |
| Input | 0.5 kV (Test Level 2 - symmetrical) | 
| 1 kV (Test Level 2 - asymmetrical) | |
| Output | 0.5 kV (Test Level 2 - symmetrical) | 
| 1 kV (Test Level 2 - asymmetrical) | |
| Signal | 1 kV (Test Level 2 - asymmetrical) | 
| Comments | Criterion A | 
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 | 
| Conducted interference | |
| Input/output/signal | asymmetrical | 
| Frequency range | 150 kHz ... 80 MHz | 
| Comments | Criterion A | 
| Voltage | 10 V (Test Level 3) | 
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. | 
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. | 
| Tuotenumero | 1584245 | 
| Pakkausyksikkö | 1 Kappaletta | 
| Vähimmäistilausmäärä | 1 Kappaletta | 
| Tuoteavain | CMRG4 | 
| Tuotekoodi | CMB543 | 
| GTIN | 4067923078031 | 
| Paino kappaletta kohti (sis. pakkauksen) | 421 g | 
| Paino kappaletta kohti (ilman pakkausta) | 345 g | 
| Tullitariffinumero | 85363030 | 
| Alkuperämaa | CN | 
ECLASS
| ECLASS-13.0 | 27371010 | 
| ECLASS-15.0 | 27371010 | 
ETIM
| ETIM 9.0 | EC000683 | 
| EU RoHS | |
| Täyttää RoHS-direktiivin vaatimukset | Kyllä | 
| poikkeussäännökset siltä osin kuin ne ovat tiedossa | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-25 Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia. | 
| EU REACH SVHC | |
| Huomautus REACH-kandidaattiaineesta (CAS-nro) | Lead (CAS-nro: 7439-92-1) | 
| EF3.0 Ilmastonmuutos | |
| CO2e kg | 15,67 kg CO2e | 
Yhteensopivat tuotteet