CAPAROC PM MB - Feed-in module
1687559

Feed-in module with Modbus/TCP interface for supplying the CAPAROC circuit breaker system with 12 V DC or 24 V DC. Additional system interface for communication with the power supply. For DIN rail installation via the CAPAROC current rails.

Tämä tuote edellyttää muita tuotteita, jotta sitä voidaan käyttää. Pakolliset lisätarvikkeet

Tuotetiedot









Yhteensopivat tuotteet




Edut

The benchmark that you can customize by selecting single signals and resets all the way to Modbus/TCP communication
Particularly easy operation for everyone with tool-free assembly, direct feed-in to the busbar, and clear operating states
Exceptionally easy design-in with the comprehensive digital data packet for universal use in communication applications

Usein kysytyt kysymykset


Is there a hardware tutorial in which the CAPAROC functions are explained?

video thumbnail of faq answer

Yes, there is a hardware tutorial to make getting started with CAPAROC easier.... Näytä lisää

Yes, there is a hardware tutorial to make getting started with CAPAROC easier.

Näytä vähemmän

How many circuit breaker modules can I connect downstream of an infeed module?

CAPAROC PM S-R: 20 circuit breaker modules
CAPAROC PM IOL: 20 channels
CAPAROC PM PN: 16 circuit breaker modules
CAPAROC PM EIP: 16 circuit breaker modules
CAPAROC PM MB: 16 circuit breaker modules
CAPAROC PM EC: 16 circuit breaker modules


The channel LED flashes yellow twice every 4 seconds. What does this mean?

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the... Näytä lisää

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the first module (left) that is flashing, if they are bent, either too far into the module, not centered in the housing opening or otherwise damaged, replace the module.

Näytä vähemmän

Can I block the setting of the set currents?

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to fla... Näytä lisää

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to flash green 3 times and unlocks it again.
2. The lock can also be set and released via the communication interface; the operating lock can also be set here, which prevents operation and settings on the device. The lock can then only be released via the interface.

Näytä vähemmän