The terminal is designed for use within an Inline station. The terminal is used for detecting positions, lengths, or angular positions with incremental encoders. Both symmetrical (RS-422) and asymmetrical (5 V DC to 24 V DC) encoders with rectangular signals can be connected to the terminal block. Rotary transducers or length measurement systems can be read in with or without a Z pulse. To increase operational safety, all encoder inputs are monitored for broken cables. Using a special operating mode, the terminal supports distance-coded incremental encoders, with which the reference run can be reduced to very short distances. In addition to the input for the encoder signals, the terminal also has three digital 24 V DC inputs, one input for the home position switch, and two inputs for limit position switches. Thus 2 or 3-conductor sensors can be connected. Input E3 can also be used as an "open collector" output. The terminal block records the position values using a counter, which counts up or down depending on the phase relationof the A and B signals.
IB IL INC-IN-PAC
-
Function module
2861755
Inline, Position detection terminal, Incremental encoder input: 1, symmetrical encoders according to EIA-422 and asymmetrical encoders, Digital inputs: 3, 24 V DC, Digital outputs: 1, 0.5 A, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
Доступно для безкоштовного завантаження.
Матеріали для завантаження
Докладно про виріб
cULus Listed
Ідентифікатор відповідності: E199827Сумісна продукція
Переваги
Supports incremental encoders with symmetrical signals in accordance with EIA standard RS-422 (line driver)
Supports incremental encoder with asymmetrical signals (push-pull)
Supplies encoder with 5 V or 24 V voltage
Three digital inputs for connecting two limit switches or a home position switch
Maximum input frequency: 300 kHz
25-bit actual position value
Precise evaluation via 1x, 2x, or 4x sampling
Direction of rotation indicator via LED