Energy meters for billing purposes enable cost-center-specific energy data billing. EMpro AC energy meters with MID approval record all important electrical parameters such as currents, voltages, power factors, power ratings, and energy values in all four quadrants. EMpro DC energy meters enable the direct measurement of currents and voltages up to 650 A/1000 V DC. The measurement data is provided via standard communication interfaces.
EEM-XM357
-
Measuring device
1674511
3-phase energy meter with direct measurement up to 100 A AC, Modbus/RTU interface, 2 pulse outputs, 4 tariffs (via Modbus), operating temperature up to +70°C, certified in accordance with Measuring Instruments Directive (MID)
Transferência gratuita disponível.
Downloads
Detalhes dos produtos
| Product family | EMpro |
| Number | 4 (Tariffs) |
| Calibration validity period | 8 Years |
| Meter type | Bidirectional meter (delivery and consumption) incl. 4-quadrant measurement |
| Insulation characteristics | |
| Protection class | II |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Display | |
| Display type | LCD with white backlighting and maximum display range of 999999.99 kWh/kVArh |
| Rated surge voltage | 6 kV |
| Accuracy class | C (EN 50470-3) |
| 0.5 (IEC 62053-21) | |
| Mains type | 1-phase (2-conductor) |
| 3-phase (3-conductor) | |
| 3-phase (4-conductor) | |
| Supply | |
| Supply voltage range | Supply from the measuring circuit |
| Electrical isolation | |
| Measuring category | CAT III 300 V |
| Utilization category | UC 2 (EN 62052-31) |
| Measurement | |
| Nominal voltage | 3x 230 V AC (400 V AC) |
| Input voltage range | 100 V AC ... 277 V AC (Phase/neutral conductor) |
| 173 V AC ... 480 V AC (Phase/Phase) | |
| Input current range | 100 A AC (Direct measurement) |
| Power consumption | 10 VA (2 W) |
| Frequency range | ±2 % (50/60 Hz reference frequency fN) |
| Power factor (cos phi) | 0.5 (inductive) |
| 0.8 (capacitive) | |
| Startup current Ist | 0.04 A |
| Minimum current Imin | 0.3 A |
| Limiting current Imax | 100 A |
| Transient current Itr | 1 A |
| Reference current Iref | 10 A |
| Current carrying capacity | ≤ 100 A (Neutral conductor) |
| Overload capacity | 30 x Imax for 0.01 s |
| Active energy (EN 50470-3) | Class C |
| Real energy (IEC 62053-21) | Class 0.5 |
| Reactive power (IEC 62053-23) | Class 2 |
| Scanning rate | 4096 Hz |
| Pulse output | |
| Output description | Passive opto-isolated |
| Maximum switching voltage | 27 V DC |
| Max. switching current | 27 mA |
| Pulse width Pulse output 1 | configurable |
| Pulse width Pulse output 2 | 100 ms |
| Pulse LED | 400 imp/kWh (Metrological LED) |
| Meter constant Pulse output 1 | configurable |
| Meter constant Pulse output 2 | 400 imp/kWh |
| Measurement connection | |
| Designation | Measurement connection |
| Conductor connection | |
| Connection method | Screw connection |
| rigid | 0.5 mm² ... 2.5 mm² |
| flexible | 0.5 mm² ... 2.5 mm² |
| AWG | 14 ... 4 (rigid/flexible) |
| Stripping length | 15 mm |
| Tightening torque | 2.5 Nm |
| other connections | |
| Designation | other connections |
| Conductor connection | |
| Connection method | Screw connection |
| rigid | 0.5 mm² ... 1.5 mm² |
| flexible | 0.5 mm² ... 1.5 mm² |
| AWG | 26 ... 14 (rigid/flexible) |
| Stripping length | 7 mm |
| Tightening torque | 0.2 Nm |
| Communication: | |
| Communication protocol | Modbus/RTU |
| Communication standard | RS-485 |
| Connection method | Screw connection |
| Transmission speed range | 2400 bps |
| 4800 bps | |
| 9600 bps (preset) | |
| 19200 bps | |
| 38400 bps | |
| Address area | 1 ... 247 (adjustable) |
| Parity | odd, even, none |
| Stop bit | 1 or 2 |
| Data update rate | 100 ms (Real power) |
| 1 s (Energy values) | |
| Item dimensions | |
| Width | 72 mm |
| Height | 100 mm |
| Depth | 71 mm |
| Depth (NS 35/7,5) | 65 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Horizontal pitch | 4 Div. |
| Color (Upper housing part) | light gray (RAL 7035) |
| Color (Lower housing part) | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 |
| Ambient conditions | |
| Degree of protection (Front) | IP51 (Front) |
| Degree of protection (Connections) | IP20 (Connections) |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| -40 °F ... 158 °F (MID) | |
| 0 °C ... 55 °C (Display) | |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 0 % ... 90 % (non-condensing) |
| Shock (storage/transport) | 30gn (300 m/s2), 18 ms (IEC 60068-2-27) |
| Vibration (storage/transport) | 10 Hz … 150 Hz, 1g (EN 60068-2-6) |
| Mechanical environment | M1 |
| EMC environment | E2 |
| CE | |
| Certificate | CE-compliant |
| MID | |
| Certificate | MID-compliant |
| Noise immunity | EN 62052-11 |
| Impulse withstand voltage | 4 kV |
| Standards/regulations | EN 50470-1 |
| EN 50470-3 |
| Mounting type | DIN rail mounting |
| Mounting position | Horizontal DIN rail |
| N.º de artigo | 1674511 |
| Pcs./Emb | 1 Unidade |
| Quantidade mínima de pedido | 1 Unidade |
| Chave comercial | CMM |
| Chave de produto | CMMC11 |
| GTIN | 4067923225138 |
| Peso por unidade (inclusive embalagem) | 385 g |
| Peso por unidade (excluindo embalagem) | 335 g |
| Número do imposto alfandegário | 90283019 |
| País de origem | A informação sobre o país de origem é fornecida com a entrega. |
ECLASS
| ECLASS-13.0 | 27142330 |
| ECLASS-15.0 | 27142330 |
ETIM
| ETIM 10.0 | EC002301 |
UNSPSC
| UNSPSC 21.0 | 26111500 |
| EU RoHS | |
| Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim (Sem regras de exceção) |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-E
Nenhuma substância perigosa acima dos valores-limite
|
| EU REACH SVHC | |
| Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Nenhuma substância numa proporção superior a 0,1 % em massa |
Produtos compatíveis
Vantagens
Direct current measurement up to 100 A AC over the full temperature range of -40°C to +70°C
Compliance with accuracy class C in accordance with EN 50470-3 and 0.5 in accordance with IEC 62053-21
Easy, intuitive operation and reading via the backlit LCD display
Simple bus and network connection via Modbus/RTU or Modbus/TCP interface
Modbus registers based on EMpro multifunctional energy measuring devices
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA