Ex i temperature measuring transducer: converts signals from resistance thermometers and remote resistance-type sensors in 2-, 3-, and 4-conductor connection technology installed in the Ex area to a linear 0/4 mA ... 20 mA signal and transmits this to a load in the safe area. The output can be operated either actively or passively via switches. The measuring transducer is installed on a corresponding VIP I/O marshalling base element by means of plug-in contact. Parameterization can be carried out via a free software solution. A USB interface under the housing cover establishes communication with the PC.
IOA MCR-EX-RTD-I
-
Temperature measuring transducer
1085764
Ex i temperature transducer for VIP I/O marshalling base elements: converts signals from resistance temperature detectors installed in the Ex area and transmits a 0/4 mA ... 20 mA signal to a load (active or passive) in the safe area. Freely configurable.
Este produto precisa de outros produtos para a operação.
Acessórios necessários
Detalhes dos produtos
Product type | Temperature transmitter |
Product family | VIP I/O-Marshalling |
Application | Temperature |
No. of channels | 1 |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Step response (0–99%) | ≤ 1.7 s |
Maximum temperature coefficient | 0.01 %/K |
Transmission error, typical | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
Electrical isolation | |
Overvoltage category | II (≤ 5000 m) |
Pollution degree | 2 (≤ 5000 m) |
Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 200 Vrms |
Test voltage | 2.3 kV AC (50 Hz, 60 s) |
Insulation | Double/reinforced insulation |
Electrical isolation Input/output, power supply IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 150 Vrms |
212 VP | |
Electrical isolation Input/output/power supply IEC/EN 60079-7 | |
Standards/regulations | IEC/EN 60079-7 |
Rated insulation voltage | 251 Vrms |
355 VP | |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 40 mA (24 V DC) |
Power dissipation | ≤ 0.7 W (Active output) |
≤ 1 W (Passive output) | |
Power consumption | ≤ 1 W (Active output) |
≤ 0.73 W (Passive output) |
Signal | |
Number of inputs | 1 |
Input signal | Temperature |
Resistor | |
Measurement | |
Description of the input | intrinsically safe |
Sensor types (RTD) that can be used | Pt, Ni, Cu, Si sensors: 2, 3, 4-conductor |
Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) |
Linear resistance measuring range | 0 Ω ... 50 kΩ |
Potentiometer resistance range | 0 Ω ... 50 kΩ |
Max. permissible overall conductor resistance | 25 Ω (Per cable) |
Sensor input current | 10 µA ... 210 µA (Up to 2x 210 µA with 3-conductor technology) |
Temperature measuring range | ≥ 20 K (R0: 100 Ω ... 10000 Ω) |
≥ 100 K (R0: 10 Ω ... 100 Ω) |
Signal: Current | |
Number of outputs | 1 |
Configurable/programmable | Yes |
Current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA (active) | |
4 mA ... 20 mA (Passive, external source voltage 19.2 V ... 26.4 V) | |
Max. current output signal | 21 mA |
Load/output load current output | ≤ 600 Ω |
Output ripple | < 20 mVPP |
< 14 mVrms | |
Output ripple (current) | < 15 µAPP |
< 10 µArms | |
Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection method | Plug-in connection |
Number of connections | 1 |
Number of positions | 11 |
Programming connection | |
Connection method | Micro USB type B |
Number of connections | 1 |
Note | Programming adapter |
Safety data | |
Max. internal capacitance Ci | 44 nF |
Max. output voltage Uo | 6 V |
Max. output current Io | 16.6 mA (RTD in 4-conductor technology) |
13 mA (RTD in 3-conductor technology) | |
7.1 mA (RTD in 2-conductor technology) | |
16.6 mA (2x RTD in 2-conductor technology) | |
13 mA (Potentiometer) | |
Max. output power Po | 25 mW (RTD in 4-conductor technology) |
20 mW (RTD in 3-conductor technology) | |
11 mW (RTD in 2-conductor technology) | |
25 mW (2x RTD in 2-conductor technology) | |
20 mW (Potentiometer) | |
Safety-related maximum voltage Um | 121 V AC |
110 V DC | |
30 V DC (Zone 2: CHn+, CHn-) | |
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 850 mH / 1000 µF |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 460 mH / 1000 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 40 µF |
IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 950 nF, 50 mH / 950 nF, 5 mH / 950 nF, 1 mH / 950 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 555 nF, 50 mH / 555 nF, 5 mH / 555 nF, 1 mH / 555 nF, 10 µH / 555 nF |
Status display | LED supply voltage, PWR (green) |
Red LED, flashing 2.8 Hz (cable error, sensor error on input or output, ERR) | |
Red LED, flashing 1.2 Hz (simulation mode, ERR) | |
LED, red, lights up: module error (exception: connected programming adapter and no supply voltage) |
Width | 10.3 mm |
Height | 80.1 mm |
Depth | 136 mm |
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -40 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (IEC/EN 61010-1) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Rated insulation voltage | 150 Vrms (Input/output/power supply) |
Insulation | Double/reinforced insulation |
Altitude range (IEC/EN 61010-1) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Rated insulation voltage | 150 Vrms (Input/output/power supply) |
Insulation | Double/reinforced insulation |
Altitude range (IEC/EN 61010-1) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 49 °C |
Rated insulation voltage | 150 Vrms (Input/output/power supply) |
Insulation | Double/reinforced insulation |
Altitude range (IEC/EN 60079-11) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Safety-related maximum voltage Um | 121 V AC/DC |
Rated insulation voltage | 150 Vrms (Input/output, power supply) |
212 VP (Input/output, power supply) | |
Altitude range (IEC/EN 60079-11) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Safety-related maximum voltage Um | 60 V AC/DC |
Rated insulation voltage | 60 Vrms (Input/output, power supply) |
84 VP (Input/output, power supply) | |
Altitude range (IEC/EN 60079-11) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 49 °C |
Safety-related maximum voltage Um | 33 V AC/DC |
Rated insulation voltage | 60 Vrms (Input/output, power supply) |
84 VP (Input/output, power supply) | |
Altitude range (IEC/EN 60079-7) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Rated insulation voltage | 162 Vrms (Input/output/power supply) |
230 VP (Input/output/power supply) | |
Altitude range (IEC/EN 60079-7) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Rated insulation voltage | 60 Vrms (Input/output/power supply) |
84 VP (Input/output/power supply) | |
Altitude range (IEC/EN 60079-7) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 49 °C |
Rated insulation voltage | 60 Vrms (Input/output/power supply) |
84 VP (Input/output/power supply) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX | |
Identification | I (M1) [Ex ia Ma] I |
II (1) G [Ex ia Ga] IIC | |
II (1) D [Ex ia Da] IIIC | |
II 3 (1) G Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | IBExU 19 ATEX 1006 X |
IECEx | |
Identification | [Ex ia Ma] I |
[Ex ia Ga] IIC | |
[Ex ia Da] IIIC | |
Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | IECEx IBE 19.0001 X |
UL, USA/Canada | |
Identification | UL 61010-1 |
UL 61010-2-201 | |
UL 61010-2-030 | |
CAN/CSA No. 61010-1-12 | |
CAN/CSA C22.2 No. 61010-2-201 | |
CSA C22.2 No. 61010-2-030 | |
[Ex ia Ga] IIC X | |
[Ex ia Da] IIIC X | |
Ex ec [ia Ga] IIC T4 Gc X | |
Ex ec [ia IIIC Da] IIC T4 Gc X | |
[AEx ia Ga] IIC | |
[AEx ia Da] IIIC | |
AEx ec [ia Ga] IIC T4 Gc | |
AEx ec [ia IIIC Da] IIC T4 Gc | |
Certificate | E330267 |
E199827 | |
Corrosive gas test | |
Identification | ISA S71.04.2013 G3 Harsh Group A |
UL data | |
Operating mode | Indoor use |
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 1 % |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 1 % |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 1 % |
Electrical isolation | 3-way isolation |
Mounting type | Plug-in mounting |
Mounting position | any |
N.º de artigo | 1085764 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Chave comercial | DK1 |
Chave de produto | DK1255 |
GTIN | 4055626875606 |
Peso por unidade (inclusive embalagem) | 127 g |
Peso por unidade (excluindo embalagem) | 127 g |
Número do imposto alfandegário | 85437090 |
País de origem | DE |
ECLASS
ECLASS-13.0 | 27210129 |
ECLASS-15.0 | 27210129 |
ETIM
ETIM 9.0 | EC002919 |
UNSPSC
UNSPSC 21.0 | 41112105 |
EU RoHS | |
Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim |
isenções tanto quanto conhecido | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Lead (n.º CAS: 7439-92-1) |
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol (n.º CAS: 79-94-7) |
Produtos compatíveis
Vantagens
Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Input for resistance thermometers and resistance-type sensors
Installation in zone 2, protection type "ec" (EN 60079-7) permitted
3-way electrical isolation
Status indicator for supply voltage, cable, sensor, and module errors
Output: 0 mA ... 20 mA or 4 mA ... 20 mA
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA