MACX MCR-EX-AP-IDS-2I-2I-LP
   - 
  Output signal conditioner
    
      1291963
      
      
    
  
      Ex i-Output isolator isolates and transmits 0 mA / 4 mA ... 20 mA signals with intrinsic safety in potentially explosive areas. Suitable for fire and gas detectors. number of channels: 2, HART-transparent, open-circuit voltage: 25 V, Standard configuration, Loop-powered, 4-way isolation, Safety Integrity Level (SIL, IEC 61508): 3, Screw connection
Detalhes dos produtos
| Note on application | Accuracy, typically specified as a percentage of the measuring span (20 mA) at UN, 23°C | 
| Notes on operation | Installation conditions influence the ambient temperature. Please refer to the operating instructions. | 
| Product type | Output signal conditioner | 
| Product family | MACX Analog | 
| No. of channels | 2 | 
| Electrical isolation | 4-way isolation | 
| Electrical isolation between input and output | yes | 
| Linearity error | ≤ 0.25 % (at load = 0 Ω) | 
| Signal transmission behavior | In = Out | 
| Temperature coefficient, typical | ≤ 0.1 % (10 K) | 
| Reverse polarity protection | yes | 
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Electrical isolation Output 1/output 2 | |
| Test voltage | 350 V (50 Hz, 60 s) | 
| Electrical isolation Input 1 / input 2 | |
| Test voltage | 500 V (50 Hz, 60 s) | 
| Supply | |
| Supply voltage range | loop-powered, no external supply necessary | 
| Power dissipation | ≤ 0.2 W (at 20 mA, per channel) | 
| ≤ 0.6 W (at 40 mA, per channel) | |
| Signal: Current | |
| Number of inputs | 2 | 
| Current input signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 40 mA (Function area) | |
| Voltage drop | 1 V (constant) | 
| Signal: Current | |
| Output description | intrinsically safe | 
| Number of outputs | 2 | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA (with HART) | |
| 0 mA ... 40 mA (Function area) | |
| Load/output load current output | ≤ 800 Ω (20 mA) | 
| Open-circuit voltage | 25 V | 
| Line fault detection | 0 mA (Line break) | 
| ≤ 1 mA (Input current behavior) | |
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Ex installation (EPL) | Gc | 
| Ex i circuits (EPL) | Ga | 
| Da | |
| Ma | |
| Safety data | |
| Max. internal inductance Li | negligible | 
| Max. internal capacitance Ci | negligible | 
| Max. output voltage Uo | 25 V | 
| Max. output current Io | 99 mA | 
| Max. output power Po | 613 mW | 
| Safety-related maximum voltage Um | 253 V AC | 
| IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 28 mH / 2.97 µF | 
| IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 11 mH / 840 nF | 
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.5 mH / 110 nF | 
| I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 46 mH / 4.87 µF | 
| Data communication (bypass) | |
| Protocols supported | HART-transparent | 
| Dimensional drawing |  | 
| Width | 17.5 mm | 
| Height | 112.5 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Flammability rating according to UL 94 | V0 | 
| Housing material | PA 6.6 | 
| Ambient conditions | |
| Degree of protection | IP20 (Terminal blocks) | 
| IP30 (Housing) | |
| Ambient temperature (operation) | -20 °C ... 70 °C (Stand-alone device: any mounting position) | 
| -20 °C ... 70 °C (Group assembly: vertical DIN rail without circulating air) | |
| -20 °C ... 70 °C (Group assembly: vertical DIN rail with circulating air) | |
| -20 °C ... 70 °C (Group assembly: horizontal DIN rail without circulating air) | |
| -20 °C ... 70 °C (Group assembly: horizontal DIN rail with circulating air) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | ≤ 95 % (non-condensing) | 
| ATEX | |
| Identification |  II (1) G [Ex ia Ga] IIC | 
|  II (1) D [Ex ia Da] IIIC | |
|  II 3 (1) G Ex nA [ia Ga] IIC T4 Gc | |
|  I (M1) [Ex ia Ma] I | |
| IECEx | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 3 | 
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 | 
| Electrical isolation | 4-way isolation | 
| Mounting type | NS 35/15, NS 35/7,5 | 
| Mounting position | vertical, horizontal | 
| N.º de artigo | 1291963 | 
| Pcs./Emb | 1 Unidade | 
| Quantidade mínima de pedido | 1 Unidade | 
| Chave comercial | DK1 | 
| Chave de produto | DK121W | 
| GTIN | 4063151522995 | 
| Peso por unidade (inclusive embalagem) | 197,4 g | 
| Peso por unidade (excluindo embalagem) | 160 g | 
| Número do imposto alfandegário | 85437090 | 
| País de origem | DE | 
ECLASS
| ECLASS-13.0 | 27210120 | 
| ECLASS-15.0 | 27210120 | 
ETIM
| ETIM 9.0 | EC002653 | 
| EU RoHS | |
| Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim | 
| isenções tanto quanto conhecido | 6(c), 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China. | 
| EU REACH SVHC | |
| Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Lead (n.º CAS: 7439-92-1) | 
| SCIP | 51b6c522-60a7-4551-a805-93431c2cde3f | 
Produtos compatíveis
- 
    
      MCR-DP - Separating plate 1430594
- 
    
      ME-TBUS-A MC 1,5-2 - DIN rail bus connector 1351974
- 
    
      ME-TBUS-A IMC1,5-2 - DIN rail bus connector 1351982
- 
    
      MPS-IH WH - Insulating sleeve 0201663
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-MT - Test plug 0201744
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      SZS 0,6X3,5 - Screwdriver 1205053
Phoenix Contact S.A.
        
        Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA