The module is designed for use within an Axioline F station. Two channels that operate independently of one another offer the option of pulse width modulation (PWM) for the output signals. The module supports PWM, pulse generator, and push-pull output operating modes.
AXL F PWM2 1H
-
Function module
1007352
Axioline F, Function module, Pulse width modulation, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
Transferência gratuita disponível.
Downloads
Detalhes dos produtos
Dimensional drawing |
|
Width | 35 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Note on application | |
Note on application | Only for industrial use |
Axioline F local bus | |
Number of interfaces | 2 |
Connection method | Bus base module |
Transmission speed | 100 Mbps |
Module | |
Input address area | 0 Byte |
Output address area | 8 Byte |
Required parameter data | 1 Byte |
Required configuration data | 6 Byte |
Signal | |
Output name | PWM outputs |
Operating mode | PWM, pulse generator, push-pull output |
Connection method | Push-in connection |
Connection technology | 2-conductor |
Number of outputs | 2 |
Frequency range | 0 Hz ... 65535 Hz |
Pulse duty factor | 0 % ... 100 % |
Nominal output voltage | 24 V (UO - 1.1 V) |
5 V DC | |
Nominal current IN | max. 500 mA (at 24 V DC) |
max. 10 mA (at 5 V DC) | |
Nominal load, ohmic | max. 12 W (at 24 V DC nominal voltage) |
max. 50 mW (at 5 V DC nominal voltage) | |
Nominal load, inductive | max. 12 VA (at 24 V DC nominal voltage) |
max. 50 mVA (at 5 V DC nominal voltage) | |
Nominal load, lamp | max. 6 W (at nominal voltage) |
Short-circuit-proof | yes |
Short-circuit current | typ. 2.2 A (for approx. 1.2 µs, auto-retry after approx. 40 µs, 24 V output) |
typ. 24 mA (5 V output) | |
Transient surge protection | yes |
Product type | I/O component |
Product family | Axioline F |
Type | block modular |
Mounting position | any (no temperature derating) |
Scope of supply | including bus base module and Axioline F connectors |
Special properties | Pulse width modulation |
Insulation characteristics | |
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 2.05 W |
Potentials: Axioline F local bus supply (UBus) | |
Supply voltage | 5 V DC (via bus base module) |
Current draw | max. 150 mA |
Potentials: Supply voltage input UO | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC including all tolerances, including ripple |
Current draw | max. 1.1 A |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Reverse polarity protection; parallel diode; with external 1 A fuse (for start-up only) | |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min |
Connection technology | |
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector | |
Connection method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Mounting position | any (no temperature derating) |
N.º de artigo | 1007352 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Chave comercial | DRI |
Chave de produto | DRI264 |
GTIN | 4055626478869 |
Peso por unidade (inclusive embalagem) | 171,06 g |
Peso por unidade (excluindo embalagem) | 171,06 g |
Número do imposto alfandegário | 85389091 |
País de origem | DE |
ECLASS
ECLASS-13.0 | 27242605 |
ECLASS-15.0 | 27242605 |
ETIM
ETIM 9.0 | EC001601 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim |
isenções tanto quanto conhecido | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Lead (n.º CAS: 7439-92-1) |
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol (n.º CAS: 79-94-7) | |
SCIP | c74a2822-23bf-4b46-9ea0-426df5a39fa5 |
Produtos compatíveis
Vantagens
2 independent channels
Output of 5 V or 24 V signals
Push-pull output
Nominal current per output: 500 mA (at 24 V DC), 10 mA (at 5 V DC)
Frequency output (0 Hz ... 65535 Hz)
Frequency resolution can be configured using the divider (1 Hz, 0.1 Hz, 0.01 Hz)
Pulse width resolution can be configured using the divider (1 ms, 0.1 ms, 0.01 ms)
Configurable pulse duty factor (0 % ... 100 %)
Device rating plate stored
Pesquisado com frequência
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA