Module carrier - AXL F BP SE4
1088135

Axioline F, Backplane, 4 slots for Axioline Smart Elements, transmission speed in the local bus: 100 Mbps, degree of protection: IP20

Downloads

Detalhes dos produtos


The Axioline F backplane is intended for use in a station that is opened by an Axioline F bus coupler or an Axiocontrol. The backplane has four “Smart Element Interface” slots to accept Axioline Smart Elements.



Desenho cotado
Width 40 mm
Height 122.4 mm
Depth 36.9 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
Complete module width 40 mm
Complete module height 124.6 mm
Complete module depth 76.1 mm
Note The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Color traffic grey A RAL 7042

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps
Smart Element interface
Number of interfaces 4
Connection method Card edge connector
Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps
Smart Element interface
Number of interfaces 4
Connection method Card edge connector

Type block modular
Product type I/O component
Mounting position Wall mounting on horizontal or vertical DIN rail
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC
Potentials: Communications power supply of the Smart Elements (USE)
Supply voltage 3.3 V DC (using card edge connectors)
Potentials: I/O supply feed-in (UP)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 16 A (provide external protection)
max. 12 A (Applications with UL approval, external fusing)
Current consumption min. 1.5 mA (without connected Smart Elements, with nominal voltage)
Power consumption max. 480 W
max. 360 W (Applications with UL approval)
Protective circuit Surge protection; Suppressor diode

Connection technology
Connection name I/O supply feed-in (UP)
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.5 mm² ... 2.5 mm²
Conductor cross section flexible 0.5 mm² ... 2.5 mm²
Conductor cross section AWG 20 ... 14
Stripping length 8 mm
I/O supply feed-in (UP)
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.5 mm² ... 2.5 mm²
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail mounting
Mounting position Wall mounting on horizontal or vertical DIN rail

N.º de artigo 1088135
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Observação Produção ligada a pedido (sem devolução)
Chave comercial DRI
Chave de produto DRIBU1
GTIN 4055626887487
Peso por unidade (inclusive embalagem) 118,8 g
Peso por unidade (excluindo embalagem) 87 g
Número do imposto alfandegário 85389091
País de origem DE


ECLASS

ECLASS-9.0 27242610
ECLASS-10.0.1 27242610
ECLASS-11.0 27242610

ETIM

ETIM 8.0 EC001600

UNSPSC

UNSPSC 21.0 32151600

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Vantagens

Preparing the communications power supply for the plugged-in Axioline Smart Elements
Supply feed-in for the peripheral supply UP for the plugged in Axioline Smart Elements