Bus coupler - AXL F BK EIP XC
1167192

Axioline F, Bus coupler, EtherNet/IP™, RJ45 jack, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

Downloads

Detalhes dos produtos


The bus coupler is intended for use within an EtherNet/IP™ network. It is the link to the Axioline F I/O system. Up to 63 Axioline F devices can be connected to the bus coupler. A corresponding EDS file is available for integrating the Axioline F station into the programming system. This file can be downloaded at: phoenixcontact.net/product/1167192.



Desenho cotado
Width 45 mm
Height 126.1 mm
Depth 74 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Color traffic grey A RAL 7042

EtherNet/IP™
Number of interfaces 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually))
Transmission physics Ethernet in RJ45 twisted pair
Axioline F local bus
Number of interfaces 1
Connection method Bus base module
Transmission speed 100 Mbps
Service
Number of interfaces 1
Connection method USB type C
EtherNet/IP™
Number of interfaces 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually))
Transmission physics Ethernet in RJ45 twisted pair
Axioline F local bus
Number of interfaces 1
Connection method Bus base module
Transmission speed 100 Mbps
Service
Number of interfaces 1
Connection method USB type C
EtherNet/IP™
Number of interfaces 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually))
Transmission physics Ethernet in RJ45 twisted pair
Axioline F local bus
Number of interfaces 1
Connection method Bus base module
Transmission speed 100 Mbps
Service
Number of interfaces 1
Connection method USB type C

System limits
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63

Type modular
Product type I/O component
Mounting position any (observe temperature derating)
Scope of delivery including bus base module and Axioline F connector
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 670 mA (2.5 A on UBus, UL = 24 V)
max. 583 mA (2.0 A at UBus, UL = 24 V, applications with UL approval, use in zone 2 potentially explosive area)
Power consumption max. 16 W (2.5 A on UBus, UL = 24 V)
max. 14 W (2.0 A at UBus, UL = 24 V, applications with UL approval, use in zone 2 potentially explosive area)
Protective circuit Surge protection; electronic
Reverse polarity protection; electronic
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Power supply unit max. 2.5 A
max. 2 A (Applications with UL approval, use in zone 2 potentially explosive area)

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: wall mounting on horizontal DIN rail)
-25 °C ... 55 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: any)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

ATEX
Identification  II 3 G Ex ec IIC T4 Gc
Certificate UL 20 ATEX 2241X
IECEx
Identification Ex ec IIC T4 Gc
Certificate IECEx ULD 20.0026X
UL, USA / Canada
Identification cULus
Certificate E238705
UL Ex, USA / Canada
Identification Class I, Zone 2, AEx ec IIC T4, Ex ec IIC T4 Gc X
Class I, Div. 2, Groups A, B, C, D T4
Certificate E366272

Mounting type DIN rail mounting
Mounting position any (observe temperature derating)

N.º de artigo 1167192
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Observação Produção ligada a pedido (sem devolução)
Chave comercial DRI
Chave de produto DRI21D
GTIN 4063151184674
Peso por unidade (inclusive embalagem) 223 g
Peso por unidade (excluindo embalagem) 177 g
Número do imposto alfandegário 85176200
País de origem DE


ECLASS

ECLASS-9.0 27242608
ECLASS-10.0.1 27242608
ECLASS-11.0 27242608

ETIM

ETIM 8.0 EC001604

UNSPSC

UNSPSC 21.0

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

IECEx

Approval ID: IECEx ULD 20.0026X

ATEX

Approval ID: UL 20 ATEX 2441X

cULus Listed

Approval ID: FILE E 366272

cULus Listed


REACh SVHC Lead 7439-92-1

Vantagens

2 Ethernet ports (with integrated switch)
Transmission speed of 10 Mbps and 100 Mbps
Rotary coding switches for setting the IP address assignment and other functions
Firmware can be updated
Runtime in bus coupler is negligible (almost 0 µs)
Typical cycle time of the Axioline F local bus is around 10 μs
Web-based management
Supports the operation of Axioline Smart Elements
Supports IOL-CONF (firmware version 1.30 and later)
Supports Diag+
Can be used under extreme ambient conditions
Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Partially coated PCBs