Double-level terminal block - UKK 3-MSTB-5,08-PE
1876615

Double-level terminal block, nom. voltage: 1000 V, nominal current: 250 A, number of connections: 4, number of positions: 1, connection method: Screw/plug-in connection, 2nd level connection left, cross section: 0.2 mm2 - 4 mm2, mounting type: NS 35/7,5, NS 35/15, NS 32, color: green-yellow


Detalhes dos produtos




Product type Ground terminal block
Number of positions 1
Pitch 5.08 mm
Number of connections 4
Number of rows 2
Insulation characteristics
Overvoltage category III
Degree of pollution 3

Rated surge voltage 4 kV
Maximum power dissipation for nominal condition 0 W

Grounding foot Yes
2nd level connection left
Screw thread M3
Note Please observe the current carrying capacity of the DIN rails.
Tightening torque 0.5 ... 0.6 Nm
Stripping length 8 mm
Internal cylindrical gage A3
Conductor cross section solid 0.2 mm² ... 4 mm²
Cross section AWG 24 ... 12
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG] 24 ... 14
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.25 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.25 mm² ... 1.5 mm²
Nominal current 250 A
Nominal voltage 1000 V

Desenho cotado
Width 5.08 mm
End cover width 2.5 mm
Height NS 35/7,5 53.5 mm
Length 50 mm
Pitch 5.08 mm

Color green-yellow
Flammability rating according to UL 94 V2
Insulating material group I
Insulating material PA
Contact surface Tin Sn
Static insulating material application in cold -60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed

Mechanical data
Open side panel Yes

Oscillation/broadband noise
Specification DIN EN 50155 (VDE 0115-200):2018-05
Spectrum Service life test category 1, class B, body mounted
Frequency f1 = 5 Hz to f2 = 150 Hz
ASD level 0.964 (m/s²)²/Hz
Acceleration 0.58g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Result Test passed
Shocks
Specification DIN EN 50155 (VDE 0115-200):2018-05
Pulse shape Half-sine
Acceleration 5g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Result Test passed
Ambient conditions
Ambient temperature (operation) -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C
Permissible humidity (storage/transport) 30 % ... 70 %

Mounting type NS 35/7,5
NS 35/15
NS 32

N.º de artigo 1876615
Pcs./Emb 50 Unidade
Quantidade mínima de pedido 1 Unidade
Chave comercial BE1
Chave de produto BE1241
Página de catálogo Página 325 (CL-2005)
GTIN 4017918134082
Peso por unidade (inclusive embalagem) 11,5 g
Peso por unidade (excluindo embalagem) 11,5 g
Número do imposto alfandegário 85369010
País de origem PL


ECLASS

ECLASS-9.0 27141120
ECLASS-10.0.1 27141120
ECLASS-11.0 27141120

ETIM

ETIM 8.0 EC000897

UNSPSC

UNSPSC 21.0 39121400

EAC

Approval ID: RU C-DE.BL08.B.00534

cULus Recognized

Approval ID: E60425
Approval Specification Data
Tensão nominal UN Corrente nominal IN Secção transversal American Wire Gauge Secção transversal mm2
Use group B
30 - 12
Use group F
30 - 12
Use group D
30 - 12

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Produtos compatíveis