CBM E8 24DC/0.5-10A NO-R
-
Electronic circuit breaker
2905744
Multi-channel, electronic circuit breaker with active current limitation for protecting eight loads at 24 V DC in the event of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For installation on DIN rails.
Detalhes dos produtos
Product type | Device circuit breakers |
Product family | CBM |
Type | DIN rail module, one-piece |
Number of positions | 1 |
No. of channels | 8 |
Data management status | |
Article revision | 27 |
Insulation characteristics | |
Protection class | III |
Pollution degree | 2 |
General | |
Operating voltage | 18 V DC ... 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | max. 80 A DC (for double supply IN+ with at least 2 x 6 mm²) |
max. 70 A DC (for UL 2367) | |
Rated current IN | 0.5 / 1 / 2 / 4 / 6 / 10 A DC (adjustable per output channel) |
Rated current (pre-adjusted) | 0.5 A |
Rated surge voltage | 0.5 kV |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. |
Short-circuit switching capacity | 300 A |
Dielectric strength | max. 30 V DC (Load circuit) |
Active current limitation | typ. 1.5 x IN (2 - 10 A) |
Fuse | electronic |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 50 mA |
Power dissipation | 1.2 W (No-load operation) |
17.2 W (Nominal operation) | |
Module initialization time | 3.3 s |
Waiting time after switch off of a channel | 10 s (at overload / short circuit) |
Measuring tolerance I | typ. 40 % (0.5 A ... 1 A) |
typ. 10 % (2 A ... 10 A) | |
Temperature derating | 40 A DC (at 70°C (65°C for UL 2367)) |
50 A DC (at 60 °C) | |
60 A DC (at 50 °C) | |
70 A DC (at 40 °C) | |
80 A DC (at 40 °C) | |
70 A DC (at 40°C for UL 2367) | |
MTBF (IEC 61709, SN 29500) | 1304293 h (at 25 °C) |
858501 h (at 40 °C) | |
440048 h (at 60 °C) | |
Fail-safe element | 15 A DC (per output channel) |
Load circuit | |
Shutdown time | 0.02 s (> 1.3 x IN) |
30 s (1.1 ... 1.3 x IN) | |
Undervoltage switch-off | ≤ 17.8 V DC (active) |
≥ 19 V DC (inactive) | |
Overvoltage switch-off | ≥ 30.5 V DC (active) |
≤ 29.5 V DC (inactive) | |
Max. capacitive load | 75000 µF |
Switch-on delay | 0.1 s (per output channel) |
Reset | |
Input voltage range | 7 V DC ... 30 V DC (Reset with falling edge) |
Current consumption | typ. 0.4 mA (at 24 V DC) |
Pulse length | ≥ 50 ms (High signal) |
≥ 50 ms (Low signal) | |
Voltage | < 5 V DC (Low signal) |
> 8 V DC (High signal) | |
Status output | |
Output voltage | 24 V DC |
Output current | max. 20 mA (when I > 80% at at least one channel) |
Indicator/remote signaling | |
Connection name | Remote indication circuit |
Switching function | N/O contact |
Operating voltage | 0 V DC ... 30 V DC |
Operating current | 1 mA DC ... 100 mA DC |
Main circuit IN+ | |
Connection method | Push-in connection |
Stripping length | 18 mm |
Conductor cross section rigid | 0.75 mm² ... 16 mm² |
Conductor cross section AWG | 20 ... 4 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.75 mm² ... 10 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.75 mm² ... 16 mm² |
Main circuit IN- | |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Main circuit OUT | |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Remote indication circuit | |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
DC OK LED off | off (No supply voltage) |
DC OK LED yellow | lit (Undervoltage active, voltage ≤ 17.8 V, active channels switched off and channel LEDs are lit red) |
flashing (Undervoltage switch-off inactive, device was in undervoltage switch-off) | |
DC OK LED green | lit (Operating voltage in nominal range 18 ... 30 V) |
DC OK LED red | lit (Overvoltage switch-off active, voltage ≥ 30.5 V, channels switched off and channel LEDs are lit red) |
flashing (Overvoltage switch-off inactive, device was in overvoltage shutdown) | |
Channel LED off | off (Channel switched off) |
Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
Channel LED yellow-green | flashing (Channel switched on, nominal current assistant active) |
Channel LED green | lit (Channel switched on) |
flashing (Channel switched on, programming mode active) | |
Channel LED red | lit (Channel switched off, over- or undervoltage active) |
ON temporarily (Channel switched off, 10 s cool-down phase, overload or short-circuit release) | |
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) | |
Channel LED red-yellow | flashing (Channel switched on, overload mode, capacity approximately 110 ... 130% , shutdown after 30 s) |
Channel LED red-green | flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release) |
Dimensional drawing | |
Width | 41 mm |
Height | 130 mm |
Depth | 121 mm (incl. DIN rail 7.5 mm) |
Color | light gray (RAL 7035) |
gray (RAL 7042) | |
Material | PC |
PA 6.6 | |
PC | |
PBT-FR17 | |
POM | |
Flammability rating according to UL 94 | V-0 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (Startup at -40 C type-tested) |
-25 °C ... 65 °C (for UL 2367) | |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 6000 m (amsl) |
Humidity test | 240 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 5 Hz ... 24.9 Hz (Amplitude ±1.6 mm; in accordance with IEC 60068-2-6, Test Fc) |
24.9 Hz … 150 Hz (Acceleration 4g; in accordance with IEC 60068-2-6, Test Fc with additional resonance frequency testing in accordance with DNV GL) |
UL approval | |
Identification | UL/C-UL Listed UL 508 |
UL Recognized UL 2367 | |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
Shipbuilding approval | |
Identification | DNV GL |
Corrosive gas test | |
Identification | ISA S71.04.2013 G3 Harsh Group A |
DNV GL data | |
Temperature | D |
Humidity | B |
Vibration | B |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-1 |
Note | Environmental influences – Part 2-1: Tests – Test A: Cold |
Standards/specifications | EN 60068-2-2 |
Note | Environmental influences – Part 2-2: Tests – Test B: Dry heat |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Mounting type | DIN rail: 35 mm |
N.º de artigo | 2905744 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Chave comercial | CLA |
Chave de produto | CLA151 |
Página de catálogo | Página 372 (C-4-2019) |
GTIN | 4046356992367 |
Peso por unidade (inclusive embalagem) | 306,05 g |
Peso por unidade (excluindo embalagem) | 303,8 g |
Número do imposto alfandegário | 85362010 |
País de origem | DE |
ECLASS
ECLASS-11.0 | 27140401 |
ECLASS-12.0 | 27140401 |
ECLASS-13.0 | 27140401 |
ETIM
ETIM 9.0 | EC003538 |
UNSPSC
UNSPSC 21.0 | 39121400 |
EU RoHS | |
Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim |
isenções tanto quanto conhecido | 34, 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Lead (n.º CAS: 7439-92-1) |
Perfluorobutane sulfonic acid (PFBS) and its salts (n.º CAS: Não aplicável) | |
SCIP | 3eb6a9fc-0de7-4d5f-af02-ec25c9a53840 |
EF3.0 Alterações climáticas | |
CO2e kg | 6,17 kg CO2e |
Produtos compatíveis
-
TRIO-PS-2G/1AC/24DC/3/C2LPS - Power supply unit 2903147
-
TRIO-PS-2G/1AC/24DC/5 - Power supply unit 2903148
-
TRIO-PS-2G/1AC/24DC/10 - Power supply unit 2903149
-
TRIO-PS-2G/1AC/24DC/20 - Power supply unit 2903151
-
TRIO-PS-2G/3AC/24DC/5 - Power supply unit 2903153
-
TRIO-PS-2G/3AC/24DC/10 - Power supply unit 2903154
-
TRIO-PS-2G/3AC/24DC/20 - Power supply unit 2903155
Vantagens
Easy to configure, thanks to the nominal current assistant
Active current limitation to improve the capacity of the upstream power supply
Adjustable in increments per channel:
from 0.5 A to 10 A
Easy system monitoring with early signaling and direct pickup of information at the product
Increased system availability with intelligent detection of under- and overvoltage
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA