MACX MCR-VDC-PT
-
Voltage measuring transducers
2906243
MACX MCR voltage transducers for DC voltages of 0... (+/-) 20 V DC to 0.. .(+/-) 660 V DC, output signal (+/-) 10 V/ (+/-)20 mA
Detalhes dos produtos
Product type | Voltage transducer |
Alignment span | ± 20 % |
Alignment zero | ± 20 % |
Maximum power dissipation for nominal condition | 1.2 W |
Protective circuit | Surge protection; 33 V suppressor diode |
Step response (10-90%) | < 16 ms |
Maximum temperature coefficient | < 0.015 %/K |
Maximum transmission error | < 1 % (of measuring range end value) |
Electrical isolation | |
Pollution degree | 2 |
Electrical isolation Measuring circuit to supply circuit and output IEC 61010-2-030 | |
Standards/regulations | IEC 61010-2-030 |
Test voltage | 5.3 kV AC (50 Hz, 60 s) |
Measuring category | II (1000 V) |
III (600 V) | |
IV (300 V) | |
Insulation | Reinforced insulation |
Electrical isolation Supply circuit to output circuit IEC 61010-1 | |
Standards/regulations | IEC 61010-1 |
Test voltage | 2.2 kV AC (50 Hz, 60 s) |
Overvoltage category | III (300 V) |
IV (150 V) | |
Insulation | Basic insulation |
Supply | |
Nominal supply voltage | 24 V DC (-20 % ... +25 %) |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 60 mA |
Measurement | |
Configurable/programmable | Yes |
Input voltage range | -550 V DC ... 550 V DC |
Maximum input voltage | ± 660 V DC |
Input resistance of voltage input | 5500 kΩ |
Impulse form | DC voltage |
Measurement | |
Input voltage range | -370 V DC ... 370 V DC |
Input resistance of voltage input | 3700 kΩ |
Measurement | |
Input voltage range | -250 V DC ... 250 V DC |
Input resistance of voltage input | 2500 kΩ |
Measurement | |
Input voltage range | -170 V DC ... 170 V DC |
Input resistance of voltage input | 1700 kΩ |
Measurement | |
Input voltage range | -120 V DC ... 120 V DC |
Input resistance of voltage input | 1200 kΩ |
Measurement | |
Input voltage range | -80 V DC ... 80 V DC |
Input resistance of voltage input | 800 kΩ |
Measurement | |
Input voltage range | -54 V DC ... 54 V DC |
Input resistance of voltage input | 800 kΩ |
Measurement | |
Input voltage range | -36 V DC ... 36 V DC |
Input resistance of voltage input | 800 kΩ |
Measurement | |
Input voltage range | -24 V DC ... 24 V DC |
Input resistance of voltage input | 240 kΩ |
Signal: Voltage | |
Voltage output signal | -10 V ... 10 V |
2 V ... 10 V | |
Max. voltage output signal | ≤ 11 V |
Load/output load voltage output | > 10 kΩ |
Ripple | 50 mV |
Signal: Current | |
Current output signal | -20 mA ... 20 mA |
4 mA ... 20 mA | |
Max. current output signal | ≤ 22 mA |
Load/output load current output | < 500 Ω |
Max. capacitive load | < 1000 pF |
Max. inductive load | < 1 mH |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Width | 22.5 mm |
Height | 118 mm |
Depth | 114 mm |
Color | gray (RAL 7042) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C (non-condensing) |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
UKCA | |
Certificate | UKCA-compliant |
UL, USA/Canada | |
Identification | UL 61010 Listed |
Electromagnetic compatibility | Conformance with EMC directive |
Low Voltage Directive | Conformance with Low Voltage Directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Mounting type | DIN rail mounting |
Assembly note | can be aligned with spacing = 10 mm |
Mounting position | any |
N.º de artigo | 2906243 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Chave comercial | CMM |
Chave de produto | CMMB21 |
Página de catálogo | Página 238 (C-5-2019) |
GTIN | 4055626050935 |
Peso por unidade (inclusive embalagem) | 218,4 g |
Peso por unidade (excluindo embalagem) | 206,8 g |
Número do imposto alfandegário | 85437090 |
País de origem | DE |
ECLASS
ECLASS-13.0 | 27210125 |
ETIM
ETIM 9.0 | EC002477 |
UNSPSC
UNSPSC 21.0 | 39121000 |
EU RoHS | |
Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim |
isenções tanto quanto conhecido | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Lead (n.º CAS: 7439-92-1) |
SCIP | 34c3d415-8ee5-47a9-8ac7-1969ebee4ef5 |
Vantagens
Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20 %
Tool-free parameterization of measured values
Teach-in configuration of the measured value range
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA