MACX PL-EX-T-UIREL-UP
   - 
  Temperature measuring transducer
    
      2904910
      
      
    
  
      Programmable temperature transducer with analog output and 3 limit value relays, intrinsically safe signal inputs, resistance thermometer in 2-, 3-, or 4-conductor technology, thermocouples, screw connection, PLd. Replacement part: 2865751 MACX MCR-EX-T-UIREL-UP.
      Transferência gratuita disponível.
      Downloads
    
  Detalhes dos produtos
| Product type | Temperature transmitter | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation | 4-way, between input/output/power supply/switching output | 
| Step response (0–99%) | 1000 ms (With SIL) | 
| 700 ms (Without SIL) | |
| Maximum temperature coefficient | 0.01 %/K | 
| Maximum transmission error | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) | 
| Electrical isolation Input/output/power supply | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Electrical isolation Input/output | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) | 
| Electrical isolation Input/power supply | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) | 
| Electrical isolation Input/switching output | |
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) | 
| Electrical isolation Output/supply | |
| Rated insulation voltage | 300 Vrms | 
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 | 
| Supply | |
| Supply voltage range | 24 V ... 230 V AC/DC (-20 % ... +10 %, 50 Hz ... 60 Hz) | 
| Typical current consumption | < 100 mA (24 V DC) | 
| Power consumption | < 2.4 W | 
| Signal | |
| Input signal | Temperature | 
| Resistor | |
| Voltage | |
| Measurement | |
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire | 
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG | 
| Temperature measuring range | -200 °C ... 850 °C | 
| Linear resistance measuring range | 0 Ω ... 50 kΩ | 
| Potentiometer resistance range | 0 Ω ... 50 kΩ | 
| Linear mV signal range | -1000 mV ... 1000 mV | 
| Switching: Relay | |
| Output description | 1 SIL/PL | 
| Configurable/programmable | Yes | 
| Contact switching type | 2 changeover contacts | 
| Contact material | AgSnO2, hard gold-plated | 
| Maximum switching voltage | 250 V AC (250 V DC) | 
| Maximum inrush current | 2 A (250 V AC) | 
| 2 A (28 V DC) | |
| 0.2 A (120 V DC) | |
| Signal | |
| Configurable/programmable | Yes | 
| Current output signal | 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) | 
| Max. current output signal | 22 mA | 
| Load/output load current output | ≤ 600 Ω (20 mA) | 
| Behavior in the event of a sensor error | according to NE 43 or freely configurable | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Safety data | |
| Max. internal inductance Li | negligible | 
| Max. internal capacitance Ci | 44 nF | 
| Max. output voltage Uo | 6 V | 
| Max. output current Io | 7.4 mA | 
| Max. output power Po | 11 mW | 
| Safety-related maximum voltage Um | 253 V AC/DC | 
| IIC: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1.3 µF | 
| 10 mH / 1.7 µF | |
| 1 mH / 2.6 µF | |
| 0 mH / 10 µF | |
| IIB: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 6.8 µF | 
| 10 mH / 9.2 µF | |
| 1 mH / 15 µF | |
| Status display | LED supply voltage, PWR (green) | 
| Red LED, flashing (line, sensor error, ERR) | |
| Red LED (module error, ERR) | |
| Yellow LED (switching output) | 
| Width | 35 mm | 
| Height | 112.5 mm | 
| Depth | 114.5 mm | 
| Color | yellow (RAL 1018) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) | 
| Ambient temperature (operation) | -20 °C ... 65 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) | 
| Shock (operation) | 15g (IEC 60068-2-27) | 
| Vibration (operation) | 5g (IEC 60068-2-6) | 
| CE | |
| Certificate | CE-compliant | 
| ATEX | |
| Identification |  II (1) G [Ex ia Ga] IIC | 
|  II (1) D [Ex ia Da] IIIC | |
|  II 3 G Ex nA nC ic IIC T4 Gc X | |
| Certificate | IBExU 10 ATEX 1044 | 
| IECEx | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex nA nC ic IIC T4 Gc X | |
| Certificate | IECEx IBE 10.0004 X | 
| UL, USA/Canada | |
| Identification | UL 508 Listed | 
| Certificate | , C.D.-No 83104549 | 
| Shipbuilding approval | |
| Identification | C, EMC2 | 
| Certificate | DNV GL 11 564-14HH | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Performance Level (ISO 13849) | |
| Identification | d | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 2 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 2 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 2 % | 
| Electrical isolation | 4-way, between input/output/power supply/switching output | 
| Mounting type | DIN rail mounting | 
| N.º de artigo | 2904910 | 
| Pcs./Emb | 1 Unidade | 
| Quantidade mínima de pedido | 1 Unidade | 
| Observação | Produção ligada a pedido (sem devolução) | 
| Chave comercial | CK3 | 
| Chave de produto | DK1215 | 
| GTIN | 4046356899789 | 
| Peso por unidade (inclusive embalagem) | 321,8 g | 
| Peso por unidade (excluindo embalagem) | 180 g | 
| Número do imposto alfandegário | 85437090 | 
| País de origem | DE | 
UNSPSC
| UNSPSC 21.0 | 41112105 | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China. | 
| EU REACH SVHC | |
| Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Nenhuma substância numa proporção superior a 0,1 % em massa | 
Produtos compatíveis
- 
    
      
- 
    
      MACX MCR-EX-I20 - Plug 2905679
- 
    
      MACX MCR-EX-CJC - Plug 2925002
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      MPS-MT - Test plug 0201744
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH WH - Insulating sleeve 0201663
Phoenix Contact S.A.
        
        Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA