Product type | Isolating switch amplifier |
Product family | MINI Analog |
No. of channels | 1 |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Rated insulation voltage | 150 V AC (Input/relay outputs (reinforced insulation)) |
150 V AC (Supply/relay outputs (reinforced insulation)) | |
150 V AC (Relay output 1/relay output 2 (reinforced insulation)) | |
30 V AC (Input/supply) | |
50 V DC (Input/supply) | |
Electrical isolation | Reinforced insulation in accordance with EN 61010-1 |
Electrical isolation between input and output | yes |
Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) |
Supply | |
Designation | Supply |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 25 mA |
Power consumption | < 600 mW |
Signal: NAMUR | |
Number of inputs | 1 |
Available input sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
floating switch contacts | |
Switch contacts with resistance circuit | |
Switching threshold "0" signal current | < 1.2 mA (blocking) |
Switching threshold "1" signal, current | > 2.1 mA (conductive) |
Line fault detection | > 6 mA (Short circuit) |
< 0.35 mA (Line break) | |
Activated /deactivated via DIP switch | |
Non-load voltage | 8.2 V DC ±10 % |
Switching: | |
Maximum switching voltage | 250 V AC |
125 V DC | |
150 V AC (UL) | |
125 V DC (UL) | |
Signal | |
Number of outputs | 2 |
Connection method | Spring-cage connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensional drawing |
|
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 102.5 mm |
Color | green (RAL 6021) |
Housing material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II 3 G Ex nA nC IIC T4 Gc X |
UL, USA/Canada | |
Identification | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 | |
Shipbuilding approval | |
Identification | BBBAA |
Certificate | DNV GL TAA00000N1 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Evaluation criterion | A |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Electrical isolation | Reinforced insulation in accordance with EN 61010-1 |
Mounting type | DIN rail mounting |
Mounting position | any |
N.º de artigo | 2810269 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Observação | Produção ligada a pedido (sem devolução) |
Chave comercial | CK1 |
Chave de produto | DK1133 |
Página de catálogo | Página 112 (C-7-2015) |
GTIN | 4017918996086 |
Peso por unidade (inclusive embalagem) | 93,8 g |
Peso por unidade (excluindo embalagem) | 63,9 g |
Número do imposto alfandegário | 85437090 |
País de origem | DE |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Nenhuma substância numa proporção superior a 0,1 % em massa |
Produtos compatíveis
-
-
TC-D37SUB-AIO16-M-PS-UNI - Module carrier 2902934
-
TC-D37SUB-ADIO16-M-P-UNI - Module carrier 2902933
-
MINI MCR DKL - Transparent cover 2308111
-
MINI MCR-DKL-LABEL - Marking label 2810272
-
MINI MCR-SL-PTB - Power terminal block 2864134
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
-
SZS 0,6X3,5 - Screwdriver 1205053
Vantagens
Floating contacts and contacts with resistance circuit can be connected
Power supply possible via the foot element (TBUS)
Highly compact isolation amplifier for electrical isolation, amplification, and duplication of proximity sensor signals
For proximity sensors according to IEC 60947-5-6 and EN 50227
Error indication via diagnostic LED and analog signal
Second output can be used as a duplicator or error signaling output
N/O contacts at output
Input and output signals can be configured via DIP switches
3-way isolation
Operating current/closed circuit current switch-over (inverted switching behavior)