Power supply unit - QUINT4-SYS-PS/1AC/24DC/2.5/SC
2904614

Primary-switched power supply unit, QUINT POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 2.5 A


Detalhes dos produtos




AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max. 300 V AC 30 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 10 A (at 25 °C)
Inrush current integral (I2t) typ. 0.1 A2s
Inrush current limitation 10 A
Frequency range (fN) 50 Hz ... 60 Hz ±10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 31 ms (120 V AC)
typ. 31 ms (230 V AC)
Current consumption 0.85 A (100 V AC)
0.7 A (120 V AC)
0.39 A (230 V AC)
0.37 A (240 V AC)
Protective circuit Transient surge protection; Varistor
Typical response time 500 ms
Input fuse 4 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 0.25 mA (264 V AC, 60 Hz)
< 0.22 mA
DC operation
Input voltage range 110 V DC ... 250 V DC -20 % ... +40 %
Voltage type of supply voltage AC/DC
Current consumption 0.75 A (110 V DC)
0.33 A (250 V DC)

Efficiency typ. 93 % (120 V AC)
typ. 94 % (230 V AC)
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 27 V DC (constant capacity)
Nominal output current (IN) 2.5 A
Static Boost (IStat.Boost) 3.125 A (≤ 40°C)
Dynamic Boost (IDyn.Boost) 4 A (≤ 60 °C (on ≤ 5 s/off ≥ 5 s))
Feedback voltage resistance ≤ 32 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC ±2 %
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 60 W
75 W
96 W
Maximum no-load power dissipation < 1 W (120 V AC)
< 1 W (230 V AC)
Power loss nominal load max. < 5 W (120 V AC)
< 4 W (230 V AC)
Crest factor typ. 1.8 (120 V AC)
typ. 1.84 (230 V AC)
Rise time 50 ms (UOut = 10 % ... 90 %)
Signal (configurable)
Digital 0 V DC 24 V DC 30 mA
Default 24 V DC 30 mA 24 V DC for UOut > 0.9 x USet

Input
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 14
Stripping length 8 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 14
Stripping length 8 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 14
Stripping length 8 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Signal output
POut > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
UOut > 0.9 x USet (LED lights up green)

Number of phases 1.00
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
Switching frequency 90 kHz ... 110 kHz (Auxiliary converter stage)
50 kHz ... 195 kHz (Main converter stage)
60 kHz ... 360 kHz (PFC stage)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 2000000 h (25 °C)
> 1161000 h (40 °C)
> 514000 h (60 °C)
Environmental protection directive RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class II
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 2.5 A
Temperature 40 °C
Time 323000 h
Additional text 120 V AC
Life expectancy (electrolytic capacitors)
Current 2.5 A
Temperature 40 °C
Time 346000 h
Additional text 230 V AC
Life expectancy (electrolytic capacitors)
Current 2.5 A
Temperature 25 °C
Time 915000 h
Additional text 120 V AC
Life expectancy (electrolytic capacitors)
Current 2.5 A
Temperature 25 °C
Time 980000 h
Additional text 230 V AC

Width 40 mm
Height 99 mm
Depth 114 mm
Installation dimensions
Installation distance right/left (active) 15 mm / 15 mm (POut ≥50% )
Installation distance right/left (passive) 5 mm / 5 mm (POut ≥50% )
Installation distance right/left (active, passive) 0 mm / 0 mm (POut ≤50 %)
Installation distance top/bottom (active) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (passive) 30 mm / 30 mm (POut ≥50% )
Installation distance top/bottom (active, passive) 30 mm / 30 mm (POut ≤50 %)

Mounting type DIN rail mounting

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Type of housing Polycarbonate
Hood version Polycarbonate

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)

Rail applications EN 50121-3-2
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
IEC 61010-2-201 (SELV)
Standard - Safety of transformers EN 61558-2-16
Overvoltage category
EN 61010-1 II (≤ 5000 m)
EN 62477-1 III (≤ 2000 m)

ATEX
Identification UL 21 ATEX 2597 X
 II 3 G   Ex ec nC IIC T4 Gc
IECEx
Identification IECEx ULD 21.0023X
Ex ec nC IIC T4 Gc
UKEX
Identification UL21UKEX2208X
UL
Identification UL Listed UL 61010-1
UL
Identification UL Listed UL 61010-2-201
UL
Identification UL 1310 Class 2 Power Units
UL
Identification ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
SIQ
Identification CB scheme (IEC 61010-1, IEC 61010-2-201)

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant IEC 61850-3
EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
Harmonic currents
Standards/regulations EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range 0 kHz ... 2 kHz
Flicker
Standards/regulations EN 61000-3-3
Frequency range 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level X)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level X - asymmetrical)
Signal 4 kV (Test Level X - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.67 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 100 V AC
Frequency 60 Hz
Voltage dip 70 %
Number of periods 0.5 / 1 / 30 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Additional text Test Level 2
Comments Criterion B
Voltage dip 0 %
Number of periods 0.5 / 1 / 5 / 50 periods
Additional text Test Level 2
Comments Criterion B
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations EN 61000-4-12
Input 2 kV (symmetrical)
4 kV (asymmetrical)
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage 30 V (10 s)
Test level 2 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Voltage 300 V (1 s)
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Voltage 1 kV (symmetrical)
2.5 kV (asymmetrical)
1 kV (symmetrical)
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

N.º de artigo 2904614
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Chave comercial CMP
Chave de produto CMPI13
GTIN 4055626255651
Peso por unidade (inclusive embalagem) 360 g
Peso por unidade (excluindo embalagem) 360 g
Número do imposto alfandegário 85044030
País de origem VN


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0

IECEE CB Scheme

Approval ID: DK-116799-A1-UL

cULus Listed

Approval ID: FILE E 123528

IECEx

Approval ID: ULD 21.0023X

ATEX

Approval ID: UL 21 ATEX 2597X

cULus Listed

Approval ID: FILE E 199827
X

UKCA-EX

Approval ID: UL21UKEX2208X