VAL-CP-RCD-3S/40/0.3/SEL
-
Type 2 surge arrester
2808001
Combination of pluggable type 2 arrester and selective residual current circuit breaker
(RCD switch) for 3-phase power supply networks (5-conductor system: L1, L2, L3, N, PE).
Detalhes dos produtos
Product type | Surge arrester |
IEC test classification | II |
T2 | |
EN type | T2 |
IEC power supply system | TN-S |
TT | |
Type | DIN rail module, two-section, divisible |
Number of positions | 4 |
Surge protection fault message | optical |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Nominal frequency fN | 50 Hz (60 Hz) |
Nominal voltage UN | 240 V AC (230/400 V AC ... 240/415 V AC) |
415 V AC (L-L) | |
RCD switch | |
Rated residual operating current IΔn | 300 mA |
Rated making and breaking capacity Im | 1.50 kA |
Rated residual making and breaking capacity IΔm | 2.50 kA |
Rated impulse withstand voltage Uimp | 6 kV (1.2/50 µs) |
Rated conditional short-circuit current Inc | 10 kA |
Tripping time for IΔn | ≤ 300 ms |
Tripping time for 5xIΔn | ≤ 40 ms |
Switching cycles, max. | 20000 |
Utilization category | AC 23A |
Insulation voltage Ui | 440 V |
Connection protective circuit | |
Connection method | Screw connection |
Tightening torque | 3.5 Nm |
Stripping length | 15 mm |
Conductor cross section flexible | 4 mm² ... 25 mm² |
Conductor cross section rigid | 4 mm² ... 25 mm² |
Conductor cross section AWG | 12 ... 4 |
Protective ground connection | |
Connection method | Screw connection |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible | 2.5 mm² ... 16 mm² |
Conductor cross section rigid | 2.5 mm² ... 25 mm² |
Conductor cross section AWG | 12 ... 4 |
Dimensional drawing |
|
Width | 121 mm |
Height | 90 mm |
Depth | 76 mm |
Horizontal pitch | 7 Div. |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PBT-FR |
Material group | I |
Housing material | PBT-FR |
Mode of protection | L-N |
L-PE | |
N-PE | |
Direction of action | 3L-N & N-PE |
Nominal voltage UN | 240/415 V AC (TN-S) |
240/415 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC (L-N) | 350 V AC |
Maximum continuous operating voltage UC (N-PE) | 264 V AC |
Rated load current IL | 40 A |
Protective conductor current IPE | ≤ 1 µA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 30 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A (264 V AC) |
Short-circuit current rating ISCCR | 10 kA |
Voltage protection level Up (L-N) | ≤ 2 kV |
Voltage protection level Up (N-PE) | ≤ 2 kV |
Residual voltage Ures (L-N) | ≤ 1.8 kV (at In) |
≤ 1.5 kV (at 10 kA) | |
≤ 1.2 kV (at 5 kA) | |
≤ 1 kV (at 3 kA) | |
Residual voltage Ures (L-PE) | ≤ 2.5 kV (at In) |
≤ 2 kV (at 10 kA) | |
≤ 1.4 kV (at 5 kA) | |
≤ 1.1 kV (at 3 kA) | |
Residual voltage Ures (N-PE) | ≤ 0.7 kV (at In) |
≤ 0.4 kV (at 10 kA) | |
≤ 0.3 kV (at 5 kA) | |
≤ 0.2 kV (at 3 kA) | |
TOV behavior at UT (L-N) | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / safe failure mode) | |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (N-PE) | ≤ 100 ns |
Max. backup fuse with branch wiring | 63 A AC (MCB) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 40 °C |
Ambient temperature (storage/transport) | -40 °C ... 60 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Standards | |
Standards/regulations | IEC 61643-1 |
EN 61643-11 | |
IEC 61008-1 | |
IEC 61008-2-1 | |
IEC 60947-3 | |
Standards/specifications | IEC 61643-11 |
Note | 2011 |
Standards/specifications | EN 61643-11 |
Note | 2012 |
Standards/specifications | EN 61008-1 |
Standards/specifications | IEC 60947-1 |
Standards/specifications | IEC 60947-3 |
Mounting type | DIN rail: 35 mm |
Mounting position | any |
N.º de artigo | 2808001 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Observação | Produção ligada a pedido (sem devolução) |
Chave comercial | CL1 |
Chave de produto | CL1315 |
Página de catálogo | Página 67 (C-4-2017) |
GTIN | 4046356337472 |
Peso por unidade (inclusive embalagem) | 812,7 g |
Peso por unidade (excluindo embalagem) | 648,79 g |
Número do imposto alfandegário | 85363010 |
País de origem | DE |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
Uma lista de declaração de acordo com a RoHS da China relativa a artigos encontra-se na área de transferências do respetivo artigo, em "Declaração do fabricante". Para todos os artigos com EFUP-E não é emitida nem necessária uma tabela de declaração de acordo com a RoHS da China.
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Nenhuma substância numa proporção superior a 0,1 % em massa |
Produtos compatíveis
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA