Power supply unit - QUINT4-PS/1AC/110DC/4
2904613

Primary-switched power supply unit, QUINT POWER, Screw connection, input: 1-phase, output: 110 V DC / 4 A

Downloads

Detalhes dos produtos




AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -10 % ... +10 %
Derating < 100 V AC (1 %/V)
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current typ. 11 A (at 25 °C)
Inrush current integral (I2t) < 0.3 A2s
Inrush current limitation 11 A
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 37 ms (120 V AC)
typ. 38 ms (230 V AC)
Current consumption 6.3 A (100 V AC)
5 A (120 V AC)
2.6 A (230 V AC)
2.5 A (240 V AC)
Nominal power consumption 474 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.94
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Input fuse 12 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE < 3.5 mA
0.7 mA (264 V AC, 60 Hz)
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 110 V DC ... 250 V DC -18 % ... +40 %
Derating < 110 V DC (1 %/V)
Voltage type of supply voltage DC
Current consumption 5.6 A (110 V DC)
2.3 A (250 V DC)
Control input (configurable) Rem Output power ON/OFF (SLEEP MODE)
Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)

Efficiency typ. 93.5 % (120 V AC)
typ. 94.7 % (230 V AC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 110 V DC
Setting range of the output voltage (USet) 110 V DC ... 135 V DC (constant capacity)
Nominal output current (IN) 4 A
Static Boost (IStat.Boost) 5 A
Dynamic Boost (IDyn.Boost) 6 A (5 s)
Selective Fuse Breaking (ISFB) 24 A (15 ms)
Magnetic circuit breaker tripping A1 ... A4 / B2 ... B4 / C1 ... C2 / Z1 ... Z4
Derating > 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance ≤ 160 V DC
Protection against overvoltage at the output (OVP) < 150 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 600 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 440 W
550 W
660 W
Apparent power 336 VA (120 V, UOUT = 24 V, IOUT = stat. Boost)
345 VA (230 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation < 7 W (120 V AC)
< 7 W (230 V AC)
Power loss nominal load max. < 31 W (120 V AC)
< 25 W (230 V AC)
Power dissipation SLEEP MODE < 7 W (120 V AC)
< 7 W (230 V AC)
Crest factor typ. 1.54 (120 V AC)
typ. 1.57 (230 V AC)
Rise time < 1 s (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal
Signal ground SGnd Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital 24 V DC 20 mA
Default 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet
Signal Out 2 (configurable)
Digital 24 V DC 20 mA
Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default 24 V DC 20 mA 24 V DC for POut < PN
Signal relay 13/14 (configurable)
Default closed (Uout > 0.9 USet)
Digital 24 V DC 1 A
30 V AC/DC 0.5 A

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Types of signaling LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut > 100 % (LED lights up yellow, output power > 440 W)
UOut > 0.9 x USet (LED lights up green)

Number of phases 1.00
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency 90 kHz ... 110 kHz (Auxiliary converter stage)
80 kHz ... 340 kHz (Main converter stage)
50 kHz ... 70 kHz (PFC stage)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 1169000 h (25 °C)
> 688000 h (40 °C)
> 308000 h (60 °C)
Environmental protection directive RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class I
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 2 A
Temperature 40 °C
Time 218000 h
Additional text 120 V AC
Life expectancy (electrolytic capacitors)
Current 2 A
Temperature 40 °C
Time 322000 h
Additional text 230 V AC
Life expectancy (electrolytic capacitors)
Current 4 A
Temperature 25 °C
Time 528000 h
Additional text 120 V AC
Life expectancy (electrolytic capacitors)
Current 4 A
Temperature 25 °C
Time 817000 h
Additional text 230 V AC
Life expectancy (electrolytic capacitors)
Current 4 A
Temperature 40 °C
Time 176000 h
Additional text 120 V AC
Life expectancy (electrolytic capacitors)
Current 4 A
Temperature 40 °C
Time 272000 h
Additional text 230 V AC

Desenho cotado
Width 70 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

With protective coating No

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Housing material Metal

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 4000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)

Rail applications EN 50121-3-2
EN 50121-5
EN 50163
IEC 62236-3-2
IEC 62236-5
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety IEC 61010-2-201
Standard - Safe isolation IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
DIN 41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706, EN 61000-4-11
Overvoltage category
EN 61010-1 II (≤ 4000 m)
EN 62477-1 III (≤ 2000 m)

CSA CAN/CSA-C22.2 No. 61010-1-1
CAN/CSA-C22.2 No. 61010-1-12
Shipbuilding approval DNV GL applied for
SIQ BG (type approved)
CB-Scheme (IEC 61010-1, IEC 61010-2-201, IEC 60950-1)
UL approvals UL Listed UL 61010-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) applied for

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant IEC 61850-3
EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
DNV GL conducted interference Class A
Additional text Area power distribution
DNV GL noise radiation Class B
Additional text Bridge and deck area
Harmonic currents
Standards/regulations EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range 0 kHz ... 2 kHz
Flicker
Standards/regulations EN 61000-3-3
EN 61000-3-3
Frequency range 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level 4 - asymmetrical)
Signal 4 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input typ. 3 kV (Test Level 4 - symmetrical)
typ. 6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 4 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 10 kHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.7 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 0.5 / 1 / 25 / 30 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 / 25 / 30 periods
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 0,5 / 1 / 5 / 50 / 250 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations EN 61000-4-12
Input 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 4)
Voltage 30 V 3 V
Test level 2 150 Hz 1.5 kHz (Test Level 4)
Voltage 3 V
Test level 3 1.5 kHz 15 kHz (Test Level 4)
Voltage 3 V 30 V
Test level 4 15 kHz 150 kHz (Test Level 4)
Voltage 30 V
Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 4)
Voltage 30 V (10 s)
Test level 6 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage 300 V (1 s)
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Input, output (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage 1 kV
Input, output (test level 2) 10 MHz
Voltage 2 kV
Input, output (test level 3) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage 2.5 kV
Signals (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage 1 kV
Signals (test level 2) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage 2.5 kV
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

N.º de artigo 2904613
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Chave comercial CMP
Chave de produto CMPI14
GTIN 4063151023461
Peso por unidade (inclusive embalagem) 1 619 g
Peso por unidade (excluindo embalagem) 1 265 g
Número do imposto alfandegário 85044030
País de origem TH


ECLASS

ECLASS-9.0 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

NK

Approval ID: TA21182M

EAC

Approval ID: RU S-DE.BL08.W.00764

EAC

Approval ID: RU S-DE.BL08.W.00764

NK

Approval ID: TA21182M

REACh SVHC Lead 7439-92-1