Active redundancy module for superior system availability and maximum operational reliability. QUINT S-ORING enables the separate structuring of a redundant system. In combination with the new QUINT POWER power supply, the redundant system is monitored continuously.
QUINT4-S-ORING/12-24DC/1X40/VP
-
Redundancy module, with protective coating
1043418
Active QUINT single redundancy module for DIN rail mounting, protective coating, input: 12 V DC ... 24 V DC, output: 12 V DC ... 24 V DC / 1 x 40 A, integrated surge protection <30 V DC, incl. mounted UTA 107/30 universal DIN rail adapter
Detalhes dos produtos
UL Recognized
ID de certificação: E211944EAC
ID de certificação: RU S-DE.BL08.W.00764UL Listed
ID de certificação: E123528cUL Listed
ID de certificação: E123528IECEE CB Scheme
ID de certificação: DE/PTZ/0048EAC Ex
ID de certificação: RU C-DE.HB49.B.00004cUL Listed
ID de certificação: E199827UL Listed
ID de certificação: E199827IECEx
ID de certificação: IECEx SIQ 21.0001XATEX
ID de certificação: SIQ 21 ATEX 183 XNEPSI-EX
ID de certificação: GYJ21.1004XCCC
ID de certificação: 2021322303003918UKCA-EX
ID de certificação: EXV21UKEX1072X_00Produtos compatíveis
Vantagens
Perguntas mais frequentes
Do I only need one QUINT4-S-ORING/12-24DC/1X40/VP to decouple two power supplies from each other?
No, one QUINT4-S-ORING/12-24DC/1X40/VP is required for each power supply. The potentials must be brought together at the output of the S-ORING modules. With this module, n+1 redundancy can thus be set up in the simplest way.
Does the item have integrated surge protection?
Yes, the item has surge protection for voltages from 30 V. To protect the load from hazardous voltage, the input terminals are short-circuited in the event of surge voltage. This means that the load can be supplied safely via the redundant power supp... Ver mais
Yes, the item has surge protection for voltages from 30 V. To protect the load from hazardous voltage, the input terminals are short-circuited in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply. The fault is signaled via the contact relay and the LED.
Ver menos