The Auto Current Balancing ACB technology of the QUINT ORING modules doubles the service life of redundantly operated power supplies by evenly utilizing the power supply units. The load current is automatically distributed symmetrically.
    
  
  QUINT-ORING/24DC/2X10/1X20
   - 
  Redundancy module, with protective coating
    
      2320173
      
      
    
  
      Active QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter
Detalhes dos produtos
UL Recognized
ID de certificação: E211944UL Listed
ID de certificação: E123528cUL Listed
ID de certificação: E123528DNV
ID de certificação: TAA000011FIECEE CB Scheme
ID de certificação: DE/PTZ/0044NK
ID de certificação: TA25015M| Tensão nominal UN | Corrente nominal IN | Secção transversal American Wire Gauge | Secção transversal mm2 | |
|---|---|---|---|---|
| keine | ||||
| 500 V | 63 A | - 10 | ||
EAC
ID de certificação: RU S-DE.BL08.W.00764ATEX
ID de certificação: DEKRA_20ATEX0136_XIECEx
ID de certificação: IECEx DEK 20.0082XCCC
ID de certificação: 2024322303005876cUL Listed
ID de certificação: E199827UL Listed
ID de certificação: E199827INMETRO
ID de certificação: DNV 22.0237 XNEPSI-EX
ID de certificação: GYJ21.1003XEAC Ex
ID de certificação: KZ 7500525010102095Produtos compatíveis
Vantagens
Perguntas mais frequentes
Is there a signal if there is a cable break on the output side or if a cable is not connected?
No. The QUINT4-ORING/12-24DC/2X10/2X10 is recommended as an alternative for signaling this.
https://www.phoenixcontact.com/en-us/products/power-supply-quint4-ps1ac24dc5-2904600
Does the item have integrated surge protection?
Yes, the item has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply.... Ver mais
Yes, the item has surge protection for voltages from 32 V. To protect the load from hazardous voltage, the respective input is switched off in the event of surge voltage. This means that the load can be supplied safely via the redundant power supply. The fault is signaled via the "Red OK" relay (13/14) and the LED.
Ver menosWhat is "ACB"?
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3... Ver mais
"ACB" stands for "Auto Current Balancing". Small differences in the output voltage of parallel power supplies have a large influence on the current supplied by a power supply. This technology balances out the current up to a voltage difference of 0.3 V. Thanks to the balanced utilization and the lower load on an individual power supply, the service life of the redundant system can be doubled.
Ver menos