Redundancy module - QUINT-DIODE/12-24DC/2X20/1X40
2320157

DIN rail diode module 12-24 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.


Detalhes dos produtos


A safe redundant system is the result of the parallel connection of two power supply units which are decoupled from one another. To further increase system availability, QUINT DIODE provides the solution: decoupling with diode.



DC operation
Nominal input voltage range 12 V DC ... 24 V DC
Input voltage range 10 V DC ... 30 V DC
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Maximum current Imax 2x 30 A (-25°C ... 40°C)
1x 60 A (-25°C ... 40°C)
Transient surge protection Varistor
Voltage drop, input/output typ. 0.5 V
Nominal input voltage range 12 V DC ... 24 V DC
Input voltage range 10 V DC ... 30 V DC
Input voltage range DC 10 V DC ... 30 V DC

Efficiency > 97 %
> 97 %
Output voltage UIn -
Nominal output current (IN) 40 A (Increasing power)
20 A (Redundancy)
Derating 60 °C ... 70 °C (2.5%/K)
Power loss nominal load max. 10 W (IOUT = 20 A)
Connection in series No
Derating 60 °C ... 70 °C 2.5 %/K

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 10
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 10
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Tightening torque, min 1.2 Nm
Tightening torque max 1.5 Nm

Insulation voltage input, output / housing 1000 V

Product type Redundancy module
MTBF (IEC 61709, SN 29500) 40000000 h
Insulation characteristics
Protection class III
Degree of pollution 2

Width 50 mm
Height 130 mm
Depth 125 mm
Horizontal pitch 2.8 Div.
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Housing material Metal
Housing material Steel sheet, zinc-plated

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 5000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Conformity/Approvals
ATEX  II 3 G Ex ec IIC T4 Gc
DEKRA 20ATEX0041 X
IECEx Ex ec IIC T4 Gc
IECEx DEK 20.0022X

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electrostatic discharge
Standards/regulations EN 61000-4-2
Housing Level 4
Electrostatic discharge
Contact discharge 8 kV (Contact discharge)
Discharge in air 15 kV (Air discharge)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m
Frequency range 1 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (level 3 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/Output Level 3
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

N.º de artigo 2320157
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Chave comercial CMR
Chave de produto CMRQ43
Página de catálogo Página 212 (C-6-2015)
GTIN 4046356524766
Peso por unidade (inclusive embalagem) 857,6 g
Peso por unidade (excluindo embalagem) 750 g
Número do imposto alfandegário 85049090
País de origem CN


ECLASS

ECLASS-9.0 27371010
ECLASS-10.0.1 27371010
ECLASS-11.0 27371010

ETIM

ETIM 8.0 EC000683

UNSPSC

UNSPSC 21.0 32151500

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

EAC

Approval ID: EAC-Zulassung

DNV GL

Approval ID: TAA000011F

LR

Approval ID: 14-20005
Approval Specification Data
Tensão nominal UN Corrente nominal IN Secção transversal American Wire Gauge Secção transversal mm2
500 V 41 A - 6

NK

Approval ID: TA19447M
Approval Specification Data
Tensão nominal UN Corrente nominal IN Secção transversal American Wire Gauge Secção transversal mm2
500 V 63 A - 10

BV

Approval ID: 36077/B0 BV

EAC

Approval ID: RU S-DE.BL08.W.00764

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

RINA

Approval ID: ELE362819XG

ABS

Approval ID: 20-2022537-PDA

ATEX

Approval ID: DEKRA 20ATEX0041X

EAC Ex

Approval ID: RU C-DE.HB49.B.00004

IECEx

Approval ID: IECEx DEK 20.0022X

CCC

Approval ID: 2020322303003441

NEPSI

Approval ID: GYJ20.1591X

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

INMETRO

Approval ID: DNV 19.0186X

cULus Recognized

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Vantagens

Flexible
Rugged design
Consistent redundancy up to the load