In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and exceptional power reserves are available for applications in the low-power range.
Primary-switched power supply unit, QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 15 V / 2 A
In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and exceptional power reserves are available for applications in the low-power range.
AC operation | |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Electric strength, max. | 300 V AC 30 s |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC/DC |
Inrush current | < 15 A (at 25 °C) |
Inrush current integral (I2t) | < 0.03 A2s |
Inrush current limitation | < 10 A |
Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 % |
Mains buffering time | typ. 32 ms (120 V AC) |
typ. 32 ms (230 V AC) | |
Current consumption | 0.69 A (100 V AC) |
0.59 A (120 V AC) | |
0.31 A (230 V AC) | |
0.31 A (240 V AC) | |
Nominal power consumption | 96.3 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | 300 ms |
Input fuse | 3.15 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C or comparable) |
Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
< 0.17 mA | |
DC operation | |
Input voltage range | 110 V DC ... 250 V DC -20 % ... +10 % |
Voltage type of supply voltage | AC/DC |
Inrush current integral (I2t) | < 0.03 A2s |
Inrush current limitation | < 10 A |
Current consumption | 0.61 A (110 V DC) |
0.27 A (250 V DC) |
Efficiency | typ. 88.8 % (120 V AC) |
typ. 89.4 % (230 V AC) | |
Nominal output voltage | ± 15 V |
Nominal output current (IN) | 2 A (+) |
1.4 A (-) | |
Static Boost (IStat.Boost) | 2.5 A ((+) ≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 4 A ((+) ≤ 60 °C, 5 s) |
Feedback voltage resistance | ≤ 25 V DC |
Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 60 mVPP (with nominal values) |
Short-circuit-proof | yes |
No-load proof | yes |
Output power | 51 W |
58.5 W | |
81 W | |
Maximum no-load power dissipation | < 1.4 W (120 V AC) |
< 2 W (230 V AC) | |
Power loss nominal load max. | < 6.6 W (120 V AC) |
< 6.1 W (230 V AC) | |
Crest factor | typ. 1.8 (120 V AC) |
typ. (230 V AC) | |
Rise time | 50 ms (UOut = 10 % ... 90 %) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal (configurable) | |
Digital | 0 V DC 15 V DC 24 mA |
Default | 15 V DC 24 mA |
Input | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Output | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Signal | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Types of signaling | LED |
Floating signal contact | |
Active signal output Out1 (digital, configurable) | |
Active signal output Out2 (analog, configurable) | |
Remote contact | |
Signal ground SGnd | |
Signal output | |
POut | > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) |
UOut | > 0.9 x USet (LED lights up green) |
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) | |
Switching frequency | 4 kHz ... 70 kHz (Auxiliary converter stage) |
80 kHz ... 190 kHz (Main converter stage) | |
30 kHz ... 150 kHz (PFC stage) |
Product type | Power supply |
MTBF (IEC 61709, SN 29500) | > 1284000 h (25 °C) |
> 644000 h (40 °C) | |
> 231000 h (60 °C) | |
Insulation characteristics | |
Protection class | II |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 40 °C |
Time | 56000 h |
Additional text | 120 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 40 °C |
Time | 65000 h |
Additional text | 230 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 25 °C |
Time | 168000 h |
Additional text | 120 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 25 °C |
Time | 195000 h |
Additional text | 230 V AC |
Width | 45 mm |
Height | 106 mm |
Depth | 90 mm |
Installation dimensions | |
Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
Mounting type | DIN rail mounting |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Housing material | Plastic |
Type of housing | Polycarbonate |
Hood version | Polycarbonate |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard - Safe isolation | IEC 61558-2-16 |
IEC 61010-2-201 | |
Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
IEC 61010-2-201 (SELV) | |
Standard - Safety of transformers | EN 61558-2-16 |
Overvoltage category | |
EN 61010-1 | II (≤ 5000 m) |
EN 62477-1 | III (≤ 2000 m) |
SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
UL approvals | UL Listed UL 61010-1 |
UL Listed UL 61010-2-201 | |
UL 1310 Class 2 Power Units | |
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | |
Conformity/Approvals | |
SIL in accordance with IEC 61508 | 0 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
EMC requirements, power plant | IEC 61850-3 |
EN 61000-6-5 | |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Interference emission | Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise immunity | Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply) |
Harmonic currents | |
Standards/regulations | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Frequency range | 0 kHz ... 2 kHz |
Flicker | |
Standards/regulations | EN 61000-3-3 |
Frequency range | 0 kHz ... 2 kHz |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 4 kV (Test Level 4 - asymmetrical) |
Signal | 4 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Input | 2 kV (Test Level 4 - symmetrical) |
4 kV (Test Level 4 - asymmetrical) | |
Output | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Signal | 0.5 kV (Test Level 2 - symmetrical) |
1 kV (Test Level 2 - asymmetrical) | |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Power frequency magnetic field | |
Standards/regulations | EN 61000-4-8 |
Frequency | 16.67 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Frequency range | 50 Hz ... 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips | |
Standards/regulations | EN 61000-4-11 |
Voltage | 100 V AC |
Frequency | 60 Hz |
Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 30 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Voltage dip | 0 % |
Number of periods | 0.5 / 1 / 5 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Pulse-shape magnetic field | |
Standards/regulations | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | |
Standards/regulations | EN 61000-4-12 |
Input | 2 kV (symmetrical) |
4 kV (asymmetrical) | |
Comments | Criterion A |
Asymmetrical conducted disturbance variables | |
Standards/regulations | EN 61000-4-16 |
Test level 1 | 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) |
Voltage | 30 V (10 s) |
Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 2) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave | |
Standards/regulations | EN 61000-4-18 |
Voltage | 1 kV (symmetrical) |
2.5 kV (asymmetrical) | |
1 kV (symmetrical) | |
Comments | Criterion A |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
N.º de artigo | 2904596 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Observação | Produção ligada a pedido (sem devolução) |
Chave de produto | CMPI12 |
GTIN | 4055626255743 |
Peso por unidade (inclusive embalagem) | 375 g |
Peso por unidade (excluindo embalagem) | 370 g |
País de origem | VN |
ECLASS-9.0 | 27040701 |
ECLASS-10.0.1 | 27040701 |
ECLASS-11.0 | 27040701 |
ETIM 8.0 | EC002540 |
UNSPSC 21.0 | 39121000 |