EEM-350-D-MCB
-
Measuring device
2905849
Three-phase energy meter for real power measurement in networks up to 460 V / 65 A, with 3 digital inputs and RS-485 interface, certified according to the MID directive
Detalhes dos produtos
Product type | Energy measuring device |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Rated insulation voltage | 300 V AC (EN 61010-1) |
Test voltage | 4 kV AC (50 Hz, 1 min.) |
Mains type | 3-phase (4-conductor) |
Supply | |
Supply voltage range | Measurement voltage supply |
Power consumption | ≤ 12 VA (2 W) |
General | |
Measuring principle | True r.m.s. value measurement |
Measured value | AC sine (50 Hz/60 Hz) |
Description of the input | Digital input |
Number | 3 |
Voltage input signal | 5 V DC ±5 % |
Maximum control current | > 10 mA |
Measurement: Voltage | |
Input name | Voltage measuring input V1, V2, V3 |
Input voltage range | 196 V AC ... 460 V AC (Phase/Phase) |
113 V AC ... 265 V AC (Phase/neutral conductor) | |
Surge voltage capacity | 460 V AC (Permanent) |
480 V AC (500 ms) | |
Precision | 0.5 % (Phase/neutral conductor) |
1 % (Phase/Phase) | |
Measurement: Current | |
Input name | Current measuring input I1, I2, I3 |
Input current | 10 A (scaled nominal current) |
65 A (Imax) | |
Overload capacity | 1920 A (10 ms) |
200 A (500 ms) | |
Precision | 0.5 % |
Measurement: Power | |
Precision | 1 % (Effective and apparent power) |
Active energy (EN 50470-3) | Class B |
Real energy (IEC 62053-21) | Class 1 |
Reactive power (IEC 62053-23) | Class 2 |
Connection method | Screw connection |
Note | other connections |
Conductor cross section rigid | 1.5 mm² |
Conductor cross section flexible | 1.5 mm² ... 1.5 mm² |
Note | Measurement connection |
Conductor cross section rigid | 2.5 mm² ... 16 mm² |
Conductor cross section flexible | 2.5 mm² ... 16 mm² |
Tightening torque | 1.7 Nm ... 3 Nm |
Data: Modbus RTU/JBUS | |
Interface | RS-485 |
Connection method | Screw terminal blocks |
Data: Network interface | |
Communication protocol | Modbus RTU/JBUS |
Communication standard | RS-485 |
Connection method | Screw terminal blocks |
Transmission speed range | 4.8 kbps ... 9.6 kbps |
Address area | 1 ... 247 |
Parity | none |
Stop bit | 1 |
Width | 72 mm |
Height | 90 mm |
Depth | 67 mm |
Color | black (RAL 9005) |
Ambient conditions | |
Degree of protection | IP50 (Front) |
IP20 (Back side) | |
Ambient temperature (operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -30 °C ... 70 °C |
Max. permissible relative humidity (operation) | < 90 % |
Permissible humidity (storage/transport) | 0 % ... 90 % |
CE | |
Certificate | CE-compliant |
MID | |
Identification | Annex V |
Mounting type | DIN rail mounting |
Mounting position | Horizontal DIN rail |
N.º de artigo | 2905849 |
Pcs./Emb | 1 Unidade |
Quantidade mínima de pedido | 1 Unidade |
Observação | Produção ligada a pedido (sem devolução) |
Chave comercial | CK4 |
Chave de produto | CMMC11 |
GTIN | 4055626000855 |
Peso por unidade (inclusive embalagem) | 411,9 g |
Peso por unidade (excluindo embalagem) | 398,4 g |
Número do imposto alfandegário | 90303370 |
País de origem | IT |
ETIM
ETIM 8.0 | EC002301 |
UNSPSC
UNSPSC 21.0 | 41113600 |
EU RoHS | |
Cumpre os requisitos de substância segundo a Diretiva RoHS | Sim (Sem regras de exceção) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
Nenhuma substância perigosa acima dos valores-limite
|
EU REACH SVHC | |
Nota sobre as substâncias candidatas ao REACH (n.º CAS) | Nenhuma substância numa proporção superior a 0,1 % em massa |
Phoenix Contact S.A.
Sintra Business Park, Edifício n°1 Zona Industrial da Abrunheira, sala 0M, 2710-089 SINTRA