CAPAROC PM S-R
-
Módulo de alimentación
1115661
Módulo de alimentación con salida de estado y entrada de reinicio para la alimentación del sistema de interruptores para protección de equipos CAPAROC con 12 o 24 V DC. Para instalar sobre el carril DIN mediante barras colectoras CAPAROC.
Detalles de producto
Productos compatibles
Sus ventajas
Preguntas frecuentes
What signals does the CAPAROC PM S-R power module provide?
The module has three different connection options for the signals:
S - Status output: Potential-bound collective signal, this indicates the status of the system. If there is at least one fault shutdown, this outputs a message.
High (24 V) ...
Ver más
The module has three different connection options for the signals:
S - Status output: Potential-bound collective signal, this indicates the status of the system. If there is at least one fault shutdown, this outputs a message.
High (24 V) = there is no fault
Low (0 V) = there is at least one fault shutdown
Maximum current 20 mA
RST - Reset input: Channels that have been switched off by an error are switched on again via a falling edge.
I > 80%-signal output: Potential-bound collective signal, if the current flowing on a channel is greater than 80% of the set nominal current, a HIGH signal (24 V) is out
¿Hay un tutorial de hardware en el que se expliquen las funciones de CAPAROC?
How many circuit breaker modules can I connect downstream of an infeed module?
CAPAROC PM S-R: 20 circuit breaker modules
CAPAROC PM IOL: 20 channels
CAPAROC PM PN: 16 circuit breaker modules
CAPAROC PM EIP: 16 circuit breaker modules
CAPAROC PM MB: 16 circuit breaker modules
CAPAROC PM EC: 16 circuit breaker modules
The channel LED flashes yellow twice every 4 seconds. What does this mean?
This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the...
Ver más
This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the first module (left) that is flashing, if they are bent, either too far into the module, not centered in the housing opening or otherwise damaged, replace the module.
Can I block the setting of the set currents?
The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to fla...
Ver más
The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to flash green 3 times and unlocks it again.
2. The lock can also be set and released via the communication interface; the operating lock can also be set here, which prevents operation and settings on the device. The lock can then only be released via the interface.