CAPAROC CR EXT4 - Barra colectora
1110991

Barra colectora de extensión con 4 ranuras para sistema CAPAROC. Para instalar sobre el carril DIN.

Detalles de producto









Sus ventajas

El estándar personalizable gracias a la longitud adaptable de forma personalizada a los requisitos
Manejo especialmente sencillo para cualquier persona gracias al fácil diseño Plug & Play
Diseño extremadamente sencillo gracias a las barras colectoras de uso universal hasta 45 A

Preguntas frecuentes


How many conductor rails can be connected together?

You can connect as many busbars as you like, but a maximum of 45 A can flow continuously.


¿Hay un tutorial de hardware en el que se expliquen las funciones de CAPAROC?

video thumbnail of faq answer

Sí, hay un tutorial de hardware que ayuda a iniciarse en el uso de CAPAROC.... Ver más

Sí, hay un tutorial de hardware que ayuda a iniciarse en el uso de CAPAROC.

Ver menos

How many circuit breaker modules can I connect downstream of an infeed module?

CAPAROC PM S-R: 20 circuit breaker modules
CAPAROC PM IOL: 20 channels
CAPAROC PM PN: 16 circuit breaker modules
CAPAROC PM EIP: 16 circuit breaker modules
CAPAROC PM MB: 16 circuit breaker modules
CAPAROC PM EC: 16 circuit breaker modules


The channel LED flashes yellow twice every 4 seconds. What does this mean?

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the... Ver más

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the first module (left) that is flashing, if they are bent, either too far into the module, not centered in the housing opening or otherwise damaged, replace the module.

Ver menos

Can I block the setting of the set currents?

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to fla... Ver más

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to flash green 3 times and unlocks it again.
2. The lock can also be set and released via the communication interface; the operating lock can also be set here, which prevents operation and settings on the device. The lock can then only be released via the interface.

Ver menos