Pulse measuring device - IPCH-4X-PCL-TCP-24DC-UT
1045379

Evaluation unit for the recording of surge currents and transient overvoltages over external sensor cables. Communication of the measured data to PROFICLOUD via Ethernet. The data evaluated in the cloud can be accessed on the device via Modbus/TCP or RESTful web service.

This product needs further products for operation. Mandatory Accessories
Free Download available. Downloads

Product Details


ImpulseCheck is the first assistance system for surge protection in the field of mains protection. The system consists of an IPCH-4X-PCL-TCP-24DC-UT pulse measuring device, the sensors, and the ImpulseAnalytics application in PROFICLOUD. The current state of the surge protection can be accessed online at any time. In addition to monitoring the surge protective devices, ImpulseCheck and ImpulseAnalytics also provide a simple and comprehensive analysis of the system's EMC. The accurate recording of electromagnetic interference on the supply lines makes it possible to draw conclusions as to their cause. Possible disturbance variables are detected before they result in a system failure. This means that service and maintenance work can be scheduled in advance and implemented more efficiently. In addition to using ImpulseAnalytics, the data that is acquired and evaluated in the cloud can also be accessed directly on the device via Modbus/TCP or a RESTful web service. After initially registering the ImpulseCheck in PROFICLOUD, you will be granted free access to the ImpulseAnalytics cloud application for one year. When the free trial period expires, an annual fee of €39 will be charged per device.



General
Note The product was successfully tested in an extended temperature range of -35 °C … +85 °C. When using in the extended temperature range, note the information in the module-specific user manual.
The ImpulseCheck module is designed to be operated in a control cabinet in conjunction with surge protective devices (SPDs) that are used in power supply systems with nominal alternating or nominal DC voltages of no more than 600 V AC or 600 V DC between the conductor and neutral conductor. These maximum nominal voltage values refer to environments of overvoltage category IV and pollution degree 2 at a maximum installation altitude of 2,000 m above sea level.
NOTE: Electrical damage due to overload. Provide external protection for the 24 V area. To ensure reliable tripping in the event of an error, the power supply unit must be able to supply the tripping current of the external overcurrent protection.

Type DIN rail module, one-piece 
Product type Evaluation unit
Insulation characteristics
Pollution degree 2

Current consumption ≤ 2 W
Evaluation unit
Operating voltage 24 V DC (-15% ... +20% including all tolerances and ripple)
Operating current ≤ 70 mA
Detectable values (current strength) 100 A ... 40 kA
Maximum measuring period 1 s
Sampling rate 500 kHz
Evaluation unit Ethernet ports
Interface Ethernet
Number 1
Connection method RJ45
Note on the connection method pluggable
Transmission speed 10/100 Mbps
Evaluation unit Function
Basic functions Acquisition of sensor data
Operation via Proficloud application and web interface

24 V supply
Connection method Screw terminal block
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 14
Note The DIN rail connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715.
Sensors
Connection method Screw terminal block
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 14

Platform: PROFICLOUD
Supports cloud computing yes
Protocol / IP-Port MQTT / 8883
HTTPS / 443
Smart Services ImpulseAnalytics

Dimensional drawing
Width 22.5 mm
Height 104.7 mm
Depth 114.5 mm
Horizontal pitch 1.3 Div.

Color traffic grey A RAL 7042
Housing material Polyamide

Mechanical data
Open side panel No

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C (Imax = 4 A)
-35 °C ... 85 °C (Imax = 2 A)
Ambient temperature (storage/transport) -35 °C ... 85 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 30 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 30 % ... 95 % (non-condensing)
Shock (operation) 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
Vibration (operation) 5g (Bump endurance test in accordance with EN 60068-2-6)

UL approval
Identification UL 61010-1:2012, 3rd Ed., Revised Nov. 21 2018
CSA C22.2 No. 61010-1-12, 3rd Ed., Revised Nov. 21 2018
IEC 61010-2-030:2017

Conformance with EMC directives Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion A, 2.2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Noise emission EN 61000-6-3/IEC 61000-6-3 Class B
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU

Standards/specifications EN 61000-6-2
Standards/specifications EN 61000-6-3

Mounting type DIN rail: 35 mm

Item number 1045379
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CLB321
Catalog Page Page 213 (C-4-2019)
GTIN 4055626633879
Weight per Piece (including packing) 182.5 g
Weight per Piece (excluding packing) 127.9 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27200316
ECLASS-10.0.1 27200316
ECLASS-11.0 27200316

ETIM

ETIM 8.0 EC002300

UNSPSC

UNSPSC 21.0 39121000

UL Listed

Approval ID: FILE E 357804

cUL Listed

Approval ID: FILE E 357804

cULus Listed


REACh SVHC Lead 7439-92-1

Compatible Products




Your advantages

Keeping the pulse of your system: Measure the status of your system and determine the remaining life expectancy (state of health) of SPDs
Always on the safe side: status reports complying with standards, at any time at the push of a button
Benefit from digital added value and services: Cloud-based data acquisition and the ability to display and combine measured values support completely new automated processes