CAPAROC PM EIP - 电源模块
1393553

电源模块带EtherNet/IP™接口,用于为CAPAROC断路器系统供应12 V DC或24 V DC。额外的系统接口可用于与电源进行通信。适用于通过CAPAROC汇流条进行DIN导轨安装。

此產品需要其他產品才能運作。 必要的附件
可免費下載。 內容下載

產品細節









相容的產品

您的優勢

可通过选择单个信号自定义基准,并一直复位至EtherNet/IP™通信
无需工具即可组装、直接馈入汇流条,以及清晰的运行状态,任何人都可以轻松操作
Studio 5000采用全面的数字化数据包和EtherNet/IP™功能块,设计非常简单

經常問的問題


是否有介绍CAPAROC功能的硬件教程?

video thumbnail of faq answer

有,我们提供可帮助您轻松入门CAPAROC的硬件教程。... 查看更多

有,我们提供可帮助您轻松入门CAPAROC的硬件教程。

少看

How many circuit breaker modules can I connect downstream of an infeed module?

CAPAROC PM S-R: 20 circuit breaker modules
CAPAROC PM IOL: 20 channels
CAPAROC PM PN: 16 circuit breaker modules
CAPAROC PM EIP: 16 circuit breaker modules
CAPAROC PM MB: 16 circuit breaker modules
CAPAROC PM EC: 16 circuit breaker modules


The channel LED flashes yellow twice every 4 seconds. What does this mean?

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the... 查看更多

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the first module (left) that is flashing, if they are bent, either too far into the module, not centered in the housing opening or otherwise damaged, replace the module.

少看

Can I block the setting of the set currents?

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to fla... 查看更多

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to flash green 3 times and unlocks it again.
2. The lock can also be set and released via the communication interface; the operating lock can also be set here, which prevents operation and settings on the device. The lock can then only be released via the interface.

少看

CAPAROC断路器系统是否提供功能块?

是的,在产品的下载区域内,以及在PLCnext Engineer的PLCnext Store中,都可以提供适用于具有适合TIA Portal和CODESYS的PROFINET接口的电源模块功能块。