PTCB BE PT 6 - 基本元件
1567576

基本元件, 安装方式: DIN导轨: TH 35 - 7.5 mm, 额定电流: 31 A

此產品需要其他產品才能運作。 必要的附件

產品細節









相容的產品




您的優勢

总宽度仅8 mm,为控制柜节省更多空间
可与CLIPLINE complete端子桥接,应用方便
借助集成的单体或集体信号连接,实现系统利用率和状态的透明化
采用可预安装接线,更换连接器时无需改动线路,从而实现便捷调试和维护

經常問的問題


How does the feed-in work and how is the bridging carried out?

Currents of up to 40 A can be fed in at the upper terminal point. Conductors with up to 6 mm2 flexible or 10 mm2 rigid can be connected. The current fed in can be distributed via the bridge shafts arranged at the top with FBS ..... 查看更多

Currents of up to 40 A can be fed in at the upper terminal point. Conductors with up to 6 mm2 flexible or 10 mm2 rigid can be connected. The current fed in can be distributed via the bridge shafts arranged at the top with FBS ...-8 bridges. The following applies: currents greater than 31 A must be distributed via two bridges; currents up to and including 31 A can be distributed via one bridge.

少看

Which characteristic curves do I select and when?

Two different characteristic curves are available:
- The faster F2 characteristic curve is suitable for more sensitive loads, such as sensors or resistive loads. It triggers at DC voltages in the 4 ... 8 x In range.
- The medium-lag M1 characte... 查看更多

Two different characteristic curves are available:
- The faster F2 characteristic curve is suitable for more sensitive loads, such as sensors or resistive loads. It triggers at DC voltages in the 4 ... 8 x In range.
- The medium-lag M1 characteristic curve is recommended for more current-intensive (e.g. capacitive) loads or motors. It triggers at DC voltages 8 ... 15 times In.

少看

Are there requirements for the PS? What needs to be considered for correct dimensioning?

For selective protection, the power supply should be able to supply the necessary increased tripping current. Line impedances must also be taken into account.


What is meant by short-circuit breaking capacity and what is the difference between the terms Icn and Inc?

Short-circuit breaking capacity: Maximum short-circuit current that the circuit breaker can safely switch off. What must be observed if the source current is higher than the short circuit breaking capacity? In this case, the protective circuit breake... 查看更多

Short-circuit breaking capacity: Maximum short-circuit current that the circuit breaker can safely switch off. What must be observed if the source current is higher than the short circuit breaking capacity? In this case, the protective circuit breaker may be used with a backup fuse up to the Inc. Certain fuses have been tested and approved for this purpose (see certificate).
- Icn (rated short-circuit breaking capacity): Value that the circuit breaker alone can switch off without backup fuse.
- Inc (Conditional rated short-circuit current): Value that the switch can handle with an upstream fuse.

少看

Can the PTCB TM be used for AC and DC?

Yes, for AC the prospective short-circuit current at the intended installation location must be taken into account. This must not exceed the breaking capacity of the PTCB TM. The magnetic tripping for AC and DC differs by the factor DC/AC = 1.3.