When using the power module with status output and reset input (CAPAROC PM S-R), max. 20 circuit breaker modules can be set. Any number of extra potential distribution modules can be added.
Max. permissible current in relation to the ambient temperature
Power module - CAPAROC PM S-R
1115661
Power module with status output and reset input for supplying the CAPAROC circuit breaker system with 12 or 24 V DC. For DIN rail installation via the CAPAROC current rails.
LABS release – in accordance with test specification VW PV 3.10.7:2005-0
When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.
Product type
Device circuit breakers
Insulation characteristics
Protection class
III
Pollution degree
2
Operating voltage
10 V DC ... 30 V DC
Rated voltage
12 V DC
24 V DC
Rated current IN
45 A DC (Total current input)
Rated surge voltage
0.5 kV
Tripping method
E (electronic)
Dielectric strength
35 V DC (Load circuit)
Efficiency
> 99 %
Closed circuit current I0
typ. 9 mA (no load at 24 V)
Power dissipation
typ. 0.22 W (no load at 24 V)
< 1.5 W (in nominal operation at 24 V and 45 A)
Temperature derating
45 A (Total current at 40°C)
30 A (Total current at 65 °C)
MTBF (IEC 61709, SN 29500)
18886912.65 h (at 25 °C with 21 % load)
5907048.64 h (at 40°C with 34.25% load)
933563.97 h (at 40°C with 100% load)
Voltage drop
0.03 V (at 45 A)
Reset
Input voltage range
7 V DC ... 30 V DC (Reset with falling edge)
Current consumption
typ. 0.5 mA (at 24 V DC)
Pulse length
≥ 50 ms
Stripping length
8 mm
Conductor cross section solid
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.2 mm² ... 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
Status output
Output voltage
max. 30 V DC (Input voltage ±5% in the event of no error)
0 V DC (Error)
Output current
max. 20 mA
Stripping length
8 mm
Conductor cross section solid
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.2 mm² ... 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
Status output
Output voltage
max. 30 V DC (Input voltage ±5% when I >80% at at least one channel)
Output current
max. 20 mA
Stripping length
8 mm
Conductor cross section solid
0.2 mm² ... 1.5 mm²
Conductor cross section AWG
24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.2 mm² ... 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
Main circuit IN+
Connection method
Push-in connection
Stripping length
18 mm
Conductor cross section solid
0.5 mm² ... 16 mm²
Conductor cross section AWG
20 ... 8
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.5 mm² ... 16 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.5 mm² ... 16 mm²
Main circuit IN-
Connection method
Push-in connection
Stripping length
18 mm
Conductor cross section solid
0.5 mm² ... 16 mm²
Conductor cross section AWG
20 ... 8
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.5 mm² ... 16 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.5 mm² ... 16 mm²
PROFINET
Maximum system extension
≤ 20 (Modules)
Power (PWR) LED green
lit (with no channel errors)
lit (Supply voltage in the nominal range)
flashing (3 x on deactivation of programming lock)
Power (PWR) LED red
lit (Supply voltage outside the nominal range)
Dimensional drawing
Width
12.4 mm
Height
132.4 mm
Depth
111.3 mm (incl. DIN rail 7.5 mm)
Color
light grey RAL 7035
Material
PA 6 (Housing)
PA 6 (Pusher)
PA 6 (Release lever)
PC (Fiber optics)
Flammability rating according to UL 94
V-0
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-30 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Altitude
≤ 4000 m (amsl (above mean sea level))
Humidity test
96 h, 95 % RH, 40 °C
Shock (operation)
30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
25g (6 ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock)