Potential distributor with Push-in connections for directly connecting the 0 V return conductor in the CAPAROC system. For DIN rail installation via the CAPAROC current rails.
LABS release – in accordance with test specification VW PV 3.10.7:2005-0
When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.
Product type
Device circuit breakers
Insulation characteristics
Protection class
III
Pollution degree
2
Operating voltage
0 V DC ... 30 V DC
Rated voltage
12 V DC
24 V DC
Rated current IN
10 A DC (per output)
40 A DC (Total)
Rated surge voltage
0.5 kV
Efficiency
> 99 %
Power dissipation
< 0.4 W (in nominal operation at 24 V and 4 x 10 A)
MTBF (IEC 61709, SN 29500)
269532625 h (at 25 °C with 21 % load)
269532334.5 h (at 40°C with 34.25% load)
269530881.5 h (at 60°C with 100% load)
Voltage drop
9.7 mV (at 10 A)
Load circuit
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section flexible
0.2 mm² ... 4 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve
0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic sleeve
0.25 mm² ... 4 mm²
Dimensional drawing
Width
6.2 mm
Height
132.4 mm
Depth
109.9 mm (incl. DIN rail 7.5 mm)
Color
light grey RAL 7035
Material
PA 6 (Housing)
PA 6 (Pusher)
PA 6 (Release lever)
Flammability rating according to UL 94
V-0
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-30 °C ... 65 °C (The temperature range of the power module must be taken into consideration)
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Altitude
≤ 4000 m (amsl (above mean sea level))
Humidity test
96 h, 95 % RH, 40 °C
Shock (operation)
30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
25g (6 ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock)