FL SWITCH APL 2224-4A-213-PA
-
Industrial Ethernet Switch
1384244
24-port Ethernet-APL + PROFIBUS PA field switch, Zone 2 mountable, Ex ‘ia’ APL ports, four uplink ports
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 270 mm |
Height | 215 mm |
Depth | 127 mm |
Note on dimensions | Depth valid when a TH 35-15 DIN rail is used (according to EN 60715). |
Note on application | |
Note on application | Only for industrial use |
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Housing material | Die-cast aluminum |
PC |
Ethernet (RJ45) | |
Number of interfaces | 2 |
Connection method | RJ45 |
Note on the connection method | Auto negotiation and autocrossing |
Transmission speed | 10/100 Mbps |
Transmission physics | Copper |
Transmission length | 100 m (per segment) |
Signal LEDs | Data receive, link status |
No. of channels | 2 (RJ45 ports) |
Ethernet (SFP) | |
Number of interfaces | 2 |
Connection method | SFP |
Note on the connection method | Full duplex |
Transmission speed | 100/1000 Mbps (full duplex) |
Transmission physics | FO |
Transmission length | Depending on the SFP module used |
No. of channels | 2 (SFP ports) |
Ethernet (APL) | |
Connection method | Screw connection |
Note on the connection method | APL, full duplex |
Transmission speed | 10 Mbps |
Transmission physics | Copper |
No. of channels | 24 (APL ports) |
Power Source Equipment (PSE) Port: Class A | |
Power Class | SPAA |
Note | Each port configurable via software |
Output nominal voltage | ≥ 9.6 V DC |
Output current | ≥ 55.56 mA |
Output power | ≥ 0.54 W |
Power Source Equipment (PSE) Port: Class B, length 20 m | |
Power Class | SPBA |
Note | Each port configurable via software |
Output nominal voltage | ≥ 8.9 V DC |
Output current | ≤ 100 mA |
Output power | ≤ 0.89 W |
Power Source Equipment (PSE) Port: Class B, length 200 m | |
Power Class | SPBA |
Note | Each port configurable via software |
Output nominal voltage | ≥ 8.9 V DC |
Output current | ≥ 84 mA |
Output power | ≤ 0.739 W |
Power Source Equipment (PSE) Port: Class B, length 120 m | |
Power Class | SPBA |
Note | Each port configurable via software |
Output nominal voltage | ≥ 9.52 V DC |
Output current | ≥ 95 mA |
Output power | ≤ 0.845 W |
Product type | Switch |
Product family | Managed Switch 2000 |
MTTF | 37.59 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
19.62 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
11.6 Years (SN 29500 standard, temperature 70°C, operating cycle 100%) | |
Special properties | PROFIBUS PA field switch |
Zone 2 mountable | |
Ex ‘ia’ APL ports | |
four uplink ports | |
Insulation characteristics | |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Overvoltage category | II |
Degree of pollution | 2 |
Switch functions | |
Diagnostic functions | RMON History |
LLDP (Link Layer Discovery Protocol) | |
SNMP-Traps | |
N:1-Portmirroring | |
ACD (Address Conflict Detection) | |
SysLog | |
CRC-Surveillance | |
Filter functions | Quality of Service (8 priority classes) |
Class of Service | |
DiffServ/DSCP | |
Port prioritization | |
VLAN (up to 32 VLANs) | |
IGMP Snooping/Querier (v1/v2) | |
Auto-Query-Port | |
Extended Multicast Filtering | |
IP parameterization | DHCP client |
DHCP Option 82 (Relay Agent) | |
DHCP server (pool-based, port-based) | |
BootP | |
DCP (Discovery and Configuration Protocol) | |
MAC address table | 8k |
Management | Web-based management (HTTP/HTTPS) |
Role-based user management (LDAP, RADIUS) | |
SNMPv1/v2/v3 | |
Redundancy | MRP (Media Redundancy Protocol) |
RSTP (Rapid Spanning Tree Protocol) | |
Large Tree Support | |
LACP (Link Aggregation Control Protocol) | |
PROFINET S2 system redundancy | |
Time synchronization | SNTP (Simple Network Time Protocol) |
Current consumption | 5.75 A |
Power consumption | 25 W (No-load) |
max. 63 W (24 Class A ports at max. load (22 V DC supply voltage at 70°C)) | |
Maximum power dissipation for nominal condition | 50 W (24 Class A ports at max. load (22 V DC supply voltage at 70°C)) |
Test section | Supply Voltage/spurs 1500 V ACrms |
100BASE-T / Spurs 1500 V ACrms | |
SFP / Spurs 1500 V ACrms | |
Spurs / Earth Ground (Housing) 500 V ACrms | |
Block of Spurs / Block of Spurs 500 V ACrms | |
Supply / 100BASE-T 2000 V ACrms | |
100BASE-T / 100BASE-T 2000 V ACrms | |
Supply / SFP 1500 V ACrms | |
Supply | |
Supply voltage (DC) | 24 V DC (Redundancy) |
Supply voltage range | 22 V DC ... 30 V DC (Redundancy) |
Max. current consumption | 5.75 A |
Current consumption | 5.75 A |
Connection method | Pluggable screw connection |
Conductor cross section, rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Stripping length | 7 mm |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 70 °C (horizontal) |
-40 °C ... 60 °C (vertical) | |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | 2000 m (maximum) |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Shock (operation) | 15g (IEC 600868-2-27) |
Vibration (operation) | 1g, according to EN 60068-2-6 |
ATEX | |
Identification | II 3(1) G Ex ic ec [ia Ga] IIC T4 Gc |
II (1) D [Ex ia Da] IIIC | |
Certificate | UL 23 ATEX 2992X |
IECEx | |
Identification | Ex ic ec [ia Ga] IIC T4 Gc |
[Ex ia Da] IIIC | |
Certificate | IECEx UL 23.0028X |
UKEX | |
Identification | II 3(1) G Ex ic ec [ia Ga] IIC T4 Gc |
II (1) D [Ex ia Da] IIIC | |
Certificate | UL23UKEX2830X |
UL, USA/Canada | |
Identification | Ind. Cont. Eq. E238705 also Listed |
Ind. Cont. Eq. for haz. loc. E196811 | |
Install in: Class I, Div. 2, Groups A, B, C, D T4 | |
Intrinsically safe outputs for: Class I, Div. 2, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz. Loc. | |
Class I, Zone 2, AEx ic ec [ia Ga] IIC T4 Gc, [AEx ia Da] IIIC | |
Ex ic ec [ia Ga] IIC T4 Gc | |
[Ex ia Da] IIIC | |
CCC | |
Identification | Ex ic ec [ia Ga] IIC T4 Gc |
[Ex ia Da] IIIC |
Safety data | |
Max. output voltage Uo | 13.23 V |
Max. output current Io | 279.38 mA |
Max. output power Po | 1.66 W |
Safety-related maximum voltage Um | 60 V |
A, B / IIC: Max. external inductivity Lo / Max. external capacitance Co | / 0.5 µF |
C/IIB, IIIC: Max. external inductivity Lo / Max. external capacitance Co | / 1.3 µF |
D/IIA, E, F, G, Class III: Max. external inductivity Lo / Max. external capacitance Co | / 1.4 µF |
A, B / IIC: Max. external inductivity Lo / Max. external capacitance Co | 0.15 mH |
C/IIB, IIIC: Max. external inductivity Lo / Max. external capacitance Co | 1.5 mH |
D/IIA, E, F, G, Class III: Max. external inductivity Lo / Max. external capacitance Co | 2.6 mH |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU (Test requirements for NE 21, IEC 61326-7 also considered as per the APL EMC specifications) |
Conformance with EMC directives | EN 61000-6-2 EN 61000-4-2 (ESD) Criterion A, ±6 kV contact discharge, ±8 kV air discharge |
EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A, Field intensity: 10 V/m | |
EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A, supply lines: ±2 kV, signal/data lines: ±1 kV | |
EN 61000-6-2 EN 61000-4-5 (surge) Criterion A, ±1 kV supply line L-PE; ±1 kV supply line N-PE; ±1 kV shielded I/O signal lines for metallic enclosure devices | |
EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A, 10 Vrms | |
EN 61000-6-2 IEC 61000-4-16 (common mode disturbances) Criterion A: 10V (10 kHz to 150 kHz) | |
EN 61000-6-4 EN 55011 (emitted interference) Class A | |
Noise immunity | EN 61000-6-2 |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Item number | 1384244 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | ****** |
Product key | DNN128 |
GTIN | 4063151759506 |
Weight per piece (including packing) | 5,260 g |
Weight per piece (excluding packing) | 5,260 g |
Customs tariff number | 85176200 |
Country of origin | US |
ECLASS
ECLASS-13.0 | 19170401 |
ETIM
ETIM 9.0 | EC000734 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-10
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Compatible products
-
DT-LAN-CAT.6+ - Surge protection device 2881007
-
E/NS 35 N - End bracket 0800886
-
FL SFP LX40 - Media module 1113081
-
FL SFP LX - Media module 2891767
-
FL SFP SX - Media module 2891754
-
FL SFP SX2 - Media module 2702397
-
FL SFP FX SM - Media module 2891082
-
FL SFP FE WDM20-A - Media module 2702437
-
TTC-6P-3-APL-24DC-UT-I - Surge protection device 1635592
-
TTC-6P-3-APL-EX-24DC-UT-I - Surge protection device 1635587
Your advantages
Six isolation groups of four spurs
Redundant power connections
APL-managed switch
Top-down wiring terminations
PROFINET-managed switch
Dynamic reconfiguration
Proxy capability
Connects to Ex ia devices in Zone 1/0 hazardous locations using 2-WISE, FISCO, or intrinsically safe entity parameters
Global approvals
MRP and S2 PROFINET System Redundancy