PTCB E1 24DC/8A NO
-
Electronic circuit breaker
2909910
1-channel, electronic circuit breaker for protecting loads at 24 V DC against overload and short circuit. Easy potential distribution with components from the CLIPLINE complete terminal block system. With fixed nominal current. For installation on DIN rails.
Product details
General | |
Note | EN 50121-3-2: Railway applications - Electromagnetic compatibility - Part 3-2: Rolling stock – Apparatus |
Connection for signal line tested in accordance with EN 61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures | |
Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. |
Product type | Device circuit breakers |
Product family | PTCB |
Type | DIN rail module, one-piece |
Number of positions | 1 |
No. of channels | 1 |
Insulation characteristics | |
Protection class | III |
Pollution degree | 2 |
General | |
Operating voltage | 18 V DC ... 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | 24 A DC (Total current input) |
8 A DC (Rated current output) | |
Rated current (pre-adjusted) | 8 A |
Rated surge voltage | 0.5 kV |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. |
Short-circuit switching capacity | 300 A |
Dielectric strength | max. 35 V DC (Load circuit) |
Fuse | electronic |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 12 mA |
Power dissipation | typ. 0.3 W (No-load operation) |
< 1.6 W (Nominal operation) | |
Module initialization time | < 0.55 s |
Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
Measuring tolerance I | ± 15 % |
Temperature derating | 21 A (Total current at 60°C) |
24 A (Total current at 50°C) | |
7 A (Channel current at 60°C) | |
8 A (Channel current at 50°C) | |
MTBF (IEC 61709, SN 29500) | 25641025 h (at 25 °C with 21 % load) |
10989010 h (at 40°C with 34.25% load) | |
1149425 h (at 55°C with 100% load) | |
Voltage drop | 0.13 V (at 8 A) |
Fail-safe element | 15 A DC |
Contact switching type | without electrical isolation |
Load circuit | |
Shutdown time | ≤ 10 ms (for short circuit > 2.0 x IN) |
1 s (1.2 ... 2.0 x IN) | |
Undervoltage switch-off | ≤ 17.8 V DC (active) |
≥ 18.8 V DC (inactive) | |
Overvoltage switch-off | ≥ 30.5 V DC (active) |
≤ 29.5 V DC (inactive) | |
Max. capacitive load | 25000 µF (Depending on the available short-circuit current) |
Indicator/remote signaling | |
Connection name | Remote indication circuit |
Switching function | N/O contact |
Operating voltage | 0 V DC ... 30 V DC |
Operating current | 100 mA DC |
Main circuit IN+ | |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Main circuit IN- | |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Main circuit OUT | |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Remote indication circuit | |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 14 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Channel LED off | off (Channel switched off) |
Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
flashing (Programming mode active) | |
Channel LED green | lit (Channel switched on) |
Channel LED red | lit (Channel switched off, over- or undervoltage active) |
ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release) | |
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) | |
flashing quickly (Channel switched off, external voltage at the output, possible installation error) |
Dimensional drawing | |
Width | 6.2 mm |
Height | 105.8 mm |
Depth | 55.6 mm (incl. DIN rail 7.5 mm) |
Color | gray (RAL 7042) |
Material | PBT |
PBT | |
Flammability rating according to UL 94 | V-0 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -30 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Altitude | ≤ 3000 m up to 52 °C (amsl) |
≤ 4000 m up to 46 °C (amsl) | |
Humidity test | 96 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
59.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc) | |
5 Hz … 100 Hz (Resonance search 4g; resonance frequency 4g; 90 min in accordance with DNV GL Class B) |
UL approval | |
Identification | UL/C-UL Listed UL 508 |
UL Recognized UL 2367 | |
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D; T4 (Hazardous Location) | |
Shipbuilding approval | |
Identification | DNV GL |
Corrosive gas test | |
Identification | ISA S71.04.2013 G3 Harsh Group A |
Shipbuilding data | |
Temperature | D |
Humidity | B |
Vibration | B |
EMC | B |
Enclosure | A |
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Standards/specifications | EN 50178 |
Note | Equipping power installations with electronic equipment |
Standards/specifications | EN 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-27 |
Note | Environmental influences – Shocks |
Standards/specifications | EN 60068-2-30 |
Note | Environmental influences – Part 2–30: Tests – Test Db: Damp heat, cyclical |
Standards/specifications | EN 61373 |
Note | Railway applications - Rolling stock equipment - Shock and vibration tests |
Standards/specifications | EN 45545-2 |
Note | Railway applications - Fire protection on railway vehicles - Part 2: Requirements for fire behavior of materials and components |
Mounting type | DIN rail: 35 mm |
Item number | 2909910 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CL10 |
Product key | CLA135 |
Catalog page | Page 379 (C-4-2019) |
GTIN | 4055626408774 |
Weight per piece (including packing) | 34.3 g |
Weight per piece (excluding packing) | 27.64 g |
Customs tariff number | 85363010 |
Country of origin | US |
ECLASS
ECLASS-11.0 | 27140401 |
ECLASS-12.0 | 27140401 |
ECLASS-13.0 | 27140401 |
ETIM
ETIM 9.0 | EC003538 |
UNSPSC
UNSPSC 21.0 | 39121400 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 00849b8f-7867-45c9-a937-b5e628099ace |
EF3.0 Climate Change | |
CO2e kg | 1.04 kg CO2e |
Compatible products
Note: Applying some accessories below might limit this product.
-
FBS 2-6 - Plug-in bridge 3030336
-
FBS 3-6 - Plug-in bridge 3030242
-
FBS 4-6 - Plug-in bridge 3030255
-
FBS 5-6 - Plug-in bridge 3030349
-
FBS 10-6 - Plug-in bridge 3030271
-
FBS 20-6 - Plug-in bridge 3030365
-
FBS 50-6 - Plug-in bridge 3032224
-
FBS 2-6 BU - Plug-in bridge 3036932
-
FBS 3-6 BU - Plug-in bridge 3036945
-
FBS 4-6 BU - Plug-in bridge 3036958
-
FBS 5-6 BU - Plug-in bridge 3036961
-
FBS 10-6 BU - Plug-in bridge 3032198
-
FBS 20-6 BU - Plug-in bridge 3032208
-
FBS 50-6 BU - Plug-in bridge 3032211
-
FBS 2-6 GY - Plug-in bridge 3032237
-
FBS 3-6 GY - Plug-in bridge 3032240
-
FBS 4-6 GY - Plug-in bridge 3032279
-
FBS 5-6 GY - Plug-in bridge 3032266
-
FBS 2-5 - Plug-in bridge 3030161
-
FBS 3-5 - Plug-in bridge 3030174
-
FBS 4-5 - Plug-in bridge 3030187
-
FBS 5-5 - Plug-in bridge 3030190
-
FBS 10-5 - Plug-in bridge 3030213
-
FBS 20-5 - Plug-in bridge 3030226
-
FBS 50-5 - Plug-in bridge 3038930
-
FBS 2-5 BU - Plug-in bridge 3036877
-
FBS 3-5 BU - Plug-in bridge 3036880
-
FBS 4-5 BU - Plug-in bridge 3036893
-
FBS 5-5 BU - Plug-in bridge 3036903
-
FBS 10-5 BU - Plug-in bridge 3036916
-
FBS 20-5 BU - Plug-in bridge 3036929
-
FBS 50-5 BU - Plug-in bridge 3032114
-
FBS 2-5 GY - Plug-in bridge 3038969
-
FBS 3-5 GY - Plug-in bridge 3038972
-
FBS 4-5 GY - Plug-in bridge 3038985
-
FBS 5-5 GY - Plug-in bridge 3038998
-
RB ST 10-(2,5/4) - Reducing bridge 3030873
-
PT 4 - Feed-through terminal block 3211757
-
PT 4-TWIN - Feed-through terminal block 3211771
-
PT 4-QUATTRO - Feed-through terminal block 3211797
-
ST 4 - Feed-through terminal block 3031364
-
ST 4-TWIN - Feed-through terminal block 3031393
-
ST 4-QUATTRO - Feed-through terminal block 3031445
-
QTC 2,5 - Feed-through terminal block 3206416
-
QTC 2,5-TWIN - Feed-through terminal block 3206445
-
QTC 2,5-QUATTRO - Feed-through terminal block 3206446
-
PT 2,5 - Feed-through terminal block 3209510
-
PT 2,5-TWIN - Feed-through terminal block 3209549
-
PT 2,5-QUATTRO - Feed-through terminal block 3209578
-
ST 2,5 - Feed-through terminal block 3031212
-
ST 2,5-TWIN - Feed-through terminal block 3031241
-
ST 2,5-QUATTRO - Feed-through terminal block 3031306
-
QTC 1,5 - Feed-through terminal block 3205019
-
QTC 1,5-TWIN - Feed-through terminal block 3205048
-
QTC 1,5-QUATTRO - Feed-through terminal block 3205077
-
PT 10 - Feed-through terminal block 3212120
-
ST 10 - Feed-through terminal block 3036110
-
ZB 6:UNBEDRUCKT - Zack marker strip 1051003
-
ZBF 6:UNBEDRUCKT - Zack Marker strip, flat 0808710
-
UCT-TM 6 - Marker for terminal blocks 0828736
-
UCT-TM 6 CUS - Marker for terminal blocks 0829602
-
US-TML (104X3,8) - Marker for terminal blocks 0830768
-
TTC-6P-T3-24DC-PT-I - Type 3 surge protection device 1027586
-
DB 50- 90 BK - Wire bridge 2820916
-
DB 50- 90 BU - Wire bridge 2821180
-
DB 50- 90 GY - Wire bridge 2820929
-
DB 50- 90 RD - Wire bridge 2864639
Your advantages
Simple application setup due to bridging option to CLIPLINE complete terminal block system
More space in the control cabinet: narrowest protection on just 6 mm width
Individual setup for suitable protection, exactly according to your requirements
PHOENIX CONTACT
586 Fulling Mill Road, Middletown, PA 17057