CBMC E4 24DC/1-4A+ IOL - Electronic circuit breaker
2910410

Multi-channel electronic circuit breaker with IO-Link interface for protecting four loads at 24 V DC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.

Free Download available. Downloads

Product Details




General
Note Repeated hard short circuits can reduce the melting integral of the integrated backup fuse.

Type DIN rail module, one-piece 
Product type Device circuit breakers
Product family CBMC
Number of positions 1
No. of channels 4
Insulation characteristics
Protection class III
Pollution degree 2

No. of channels 4
General
Operating voltage 18 V DC ... 30 V DC
Rated voltage 24 V DC
Rated current IN max. 16 A DC (IN+)
max. 40 A DC (per terminal position when bridging additional devices via IN+)
Rated current IN 1 / 2 / 3 / 4 A DC (adjustable per output channel)
Rated current (pre-adjusted) 4 A
Rated surge voltage 0.5 kV
Tripping method E (electronic)
Feedback resistance max. 35 V DC
Required backup fuse Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element.
Short-circuit switching capacity 300 A
Dielectric strength max. 35 V DC (Load circuit)
Fuse electronic
Efficiency > 99 %
Closed circuit current I0 typ. 25 mA
Power dissipation typ. 0.6 W (No-load operation)
< 4 W (Nominal operation)
Module initialization time 1.6 s
Waiting time after switch off of a channel 5 s (at overload / short circuit)
Measuring tolerance I ± 15 %
MTBF (IEC 61709, SN 29500) 6896552 h (at 25 °C with 21 % load)
2597403 h (at 40°C with 34.25% load)
443066 h (at 35 °C with 100 % load)
Fail-safe element 15 A DC (per output channel)
Load circuit
Shutdown time ≤ 10 ms (for short circuit > 2.0 x IN)
1 s (1.2 ... 2.0 x IN)
Undervoltage switch-off ≤ 17.8 V DC (active)
≥ 18.8 V DC (inactive)
Overvoltage switch-off ≥ 30.5 V DC (active)
≤ 29.5 V DC (inactive)
Max. capacitive load 30000 µF (Depending on the current setting and the short-circuit current available)

Main circuit IN+
Connection method Push-in connection
Stripping length 15 mm
Conductor cross section solid 0.2 mm² ... 10 mm²
Conductor cross section AWG 24 ... 8
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 6 mm²
Main circuit IN-
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
Main circuit OUT
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 2.5 mm²
IO-Link
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 1.5 mm²

IO-Link
Interface type IO-Link
Specification V1.1
Reverse polarity protection yes
Transmission speed 230.4 kbps (COM3)
Cycle Time min. 40 ms
Amount of process data 8 Byte (Input data)
3 Byte (Output data)
Nominal voltage for I/O supply 24 V DC
Current consumption max. 30 mA (IO-Link L+)
IO-Link Vendor ID 176dec, 00 B0hex
IO-Link Device ID 393520dec, 06 01 30hex

IO-Link LED off off (No communication)
IO-Link LED green flashing (IO-Link connection exists)
Channel LED off off (Channel switched off)
Channel LED yellow lit (Channel switched on, channel load > 80% )
flashing (Programming mode active)
Channel LED green lit (Channel switched on)
Channel LED red lit (Channel switched off, over- or undervoltage active)
ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release)
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release)
two flashes (Channel switched off, device total current limit 40 A exceeded)

Dimensional drawing
Width 36 mm
Height 90 mm
Depth 98 mm (incl. DIN rail 7.5 mm)

Color light grey RAL 7035
Material PC
PA 6.6
PA 6.3T
POM
Flammability rating according to UL 94 V-0

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 70 °C
Altitude ≤ 3000 m up to 52 °C (amsl (above mean sea level))
≤ 4000 m up to 46 °C (amsl (above mean sea level))
Humidity test 96 h, 95 % RH, 40 °C
Shock (operation) 30g (IEC 60068-2-27, Test Ea)
Vibration (operation) 10 Hz ... 57.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc)
57.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc)

UL approval
Identification UL/C-UL Listed UL 508
UL Recognized UL 2367
NEC Class 2 according to UL 1310

Standards/specifications EN 61000-6-2
Standards/specifications EN 61000-6-3
Standards/specifications EN 60068-2-6
Standards/specifications EN 60068-2-27
Standards/specifications EN 60068-2-78
Standards/specifications EN 50178

Mounting type DIN rail: 35 mm

Item number 2910410
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C09
Product Key CLA152
Catalog Page Page 376 (C-4-2019)
GTIN 4055626448558
Weight per Piece (including packing) 142.7 g
Weight per Piece (excluding packing) 139 g
Customs tariff number 85362010
Country of origin DE


ECLASS

ECLASS-9.0 27141116
ECLASS-10.0.1 27140401
ECLASS-11.0 27140401
ECLASS-12.0 27140401

ETIM

ETIM 8.0 EC003538

UNSPSC

UNSPSC 21.0 39121400

UL Recognized

Approval ID: FILE E 317172

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

System transparency, thanks to comprehensive diagnostics capabilities
Worldwide access to the device, thanks to integration into your IO-Link infrastructure
Secure locking, thanks to interlock
Plan service calls more efficiently since regular service interval calls can be performed conveniently via the interface.
Convenient error diagnostics, thanks to precise error categorization and recording
Autonomous operation since the device is fully functional even without the IO-Link interface connection