TRIO-PS-2G/3AC/24DC/20 - Power supply unit
2903155

Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 3-phase, output: 24 V DC/20 A


Product Details


TRIO POWER power supplies with standard functionality
The TRIO POWER power supply range with push-in connection has been perfected for use in machine building. All functions and the space-saving design of the single and three-phase modules are optimally tailored to the stringent requirements. Under challenging ambient conditions, the power supply units, which feature an extremely robust electrical and mechanical design, ensure the reliable supply of all loads.



AC operation
Network type Star network
Nominal input voltage range 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC 3x 320 V AC ... 575 V AC
Typical national grid voltage 3x 400 V AC
3x 480 V AC
Voltage type of supply voltage AC
Inrush current ≤ 22 A (typical)
Inrush current integral (I2t) ≤ 0.5 A2s
AC frequency range 50 Hz ... 60 Hz
Mains buffering time typ. 10 ms (400 V AC)
typ. 20 ms (500 V AC)
Current consumption 3x 1.2 A (400 V AC)
3x 1 A (500 V AC)
2x 2.3 A (400 V AC)
2x 1.9 A (500 V AC)
Nominal power consumption 822.2 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.63
Typical response time < 1 s
Input fuse 3.15 A (internal (device protection), slow-blow)
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
< (550 V AC, 60 Hz)

Efficiency > 93 % (400 V AC)
500 V AC
Output characteristic U/I with dynamic load reserve
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 20 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple ≤ 20 mVPP
Short-circuit-proof yes
No-load proof yes
Output power 480 W
720 W
Maximum no-load power dissipation < 1.2 W (400 V AC)
Power loss nominal load max. < 38 W (480 V AC)
Rise time ≤ 120 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK
Continuous load current 100 mA
Signal relay 13/14
Default closed
Digital 30 V AC 30 V DC 100 mA

Input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Output
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 6 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 6 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 8
Stripping length 15 mm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Types of signaling LED
Floating signal contact
Signal output: LED status indicator
Signalization designation DC OK
Status display LED
Color green
DC OK UOUT > 0.9 x UN (UN = 24 V DC)
UOUT > 0.9 x UN (UN = 24 V DC)

Number of phases 3.00
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)

Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 1800000 h (25 °C)
> 1100000 h (40 °C)
> 510000 h (60 °C)
Insulation characteristics
Protection class I (in closed control cabinet)
Degree of pollution 2

Width 65 mm
Height 130 mm
Depth 160 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Polycarbonate

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.

Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety IEC 62368-1 (SELV)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)

Shipbuilding approval GL applied for
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
Conformity/Approvals
SIL in accordance with IEC 61508 0

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Interference emission in accordance with EN 61000-6-2 (industrial)
Noise emission EN 55011 (EN 55022)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity in accordance with EN 61000-6-2 (industrial)
Harmonic currents
Frequency range Class A, B
Flicker
Frequency range 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal 1 kV (Test Level 1 - asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Input/Output asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 25 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 10 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 1 period
Additional text Test Level 2
Comments Criterion A
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Item number 2903155
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C14
Product Key CMPO33
Catalog Page Page 259 (C-4-2019)
GTIN 4046356960861
Weight per Piece (including packing) 1,686 g
Weight per Piece (excluding packing) 1,686 g
Customs tariff number 85044083
Country of origin CN


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

IECEE CB Scheme

Approval ID: DK-44808-A1-UL

EAC

Approval ID: RU S-DE.BL08.W.00764

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

EAC

Approval ID: RU S-DE.BL08.W.00764

DNV

Approval ID: TAA00000BM

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cULus Recognized

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Save time and costs, thanks to the Push-in connection and narrow design
Increase system availability, thanks to dynamic boost with 150% of the nominal current for five seconds
Maximum flexibility due to the wide temperature range from -25°C to +70°C and device startup at -40°C
Rugged design