QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.



Nominal input voltage range 24 V DC
Input voltage range 24 V DC -25 % ... +40 %
Wide-range input no
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 1 A
Inrush current integral (I2t) < 0.05 A2s
Inrush current limitation 1 A
Mains buffering time typ. 14 ms (24 V DC)
Current consumption 6.9 A (24 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 15 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Signal Remote (configurable)
Connection labeling 3.3 +
Function Output power ON/OFF (remote)
Default Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)

Efficiency typ. 92.2 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A
Dynamic Boost (IDyn.Boost) 10 A (5 s)
Selective Fuse Breaking (ISFB) 30 A (15 ms)
Magnetic circuit breaker tripping A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
Short-circuit-proof yes
No-load proof yes
Output power (PN) 120 W
Output power (PStat. Boost) 150 W
Output power (PDyn. Boost) 240 W (5 s)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Residual ripple < 10 mVPP
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Rise time < 1 s (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 2 W
Power loss nominal load max. < 10 W
Power dissipation SLEEP MODE < 1 W
Connection in parallel yes, for redundancy and increased capacity
Signal Out 1 (configurable)
Connection labeling 3.5 +
Digital 0 V DC
24 V DC
20 mA
Signal option Output voltage
Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Default UIN input voltage OK
Signal Out 2 (configurable)
Connection labeling 3.6 +
Digital 0 V DC
24 V DC
20 mA
Default Output power
Signal option Output voltage
Output current
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Signal option Output voltage
Output current
Output power
Signal relay 13/14 (configurable)
Connection labeling 3.1, 3.2
Switch contact (floating) floating
Maximum contact load 24 V DC
1 A
30 V AC
0.5 A
Default Output voltage
Signal option Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
UIN input voltage OK
Signal ground SGnd
Connection labeling 3.4 +
Function Signal ground
Reference potential to OUT1, OUT2, REM

Input
Position 1.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 6 mm²
flexible 0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 4 mm²
rigid (AWG) 24 ... 10
Stripping length 10 mm
Output
Position 2.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 6 mm²
flexible 0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 4 mm²
rigid (AWG) 24 ... 10
Stripping length 10 mm
Signal
Position 3.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 1 mm²
flexible 0.2 mm² ... 1.5 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 0.75 mm²
rigid (AWG) 24 ... 16
Stripping length 8 mm

Types of signaling LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal threshold > 100 % (LED lights up yellow, output power > 120 W)
> 75 % (LED lights up green, output power > 90 W)
> 50 % (LED lights up green, output power > 60 W)
> 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
> 0.8 x UInNom (LED off)
< 0.8 x UInNom (LED lights up yellow)

Number of phases 1.00
Insulation voltage input/output 4 kV DC (type test)
2 kV DC (routine test)
Switching frequency 190 kHz ... 220 kHz (Auxiliary converter stage)
50 kHz ... 420 kHz (Main converter stage)

Product type DC/DC converters
MTBF (IEC 61709, SN 29500) > 1600000 h (25 °C)
> 930000 h (40 °C)
> 380000 h (60 °C)
Insulation characteristics
Protection class Special with SELV input and output
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 2.5 A
Temperature 40 °C
Time 422000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 5 A
Temperature 40 °C
Time 260000 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 5 A
Temperature 30 °C
Time 520000 h
Additional text 24 V DC

Width 36 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
Installation distance right/left (passive) 0 mm / 0 mm (≤ 70 °C)
Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (passive) 50 mm / 50 mm (≤ 70 °C)
Alternative assembly
Width 122 mm
Height 130 mm
Depth 39 mm

Mounting type DIN rail mounting
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
With protective coating yes

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Hood version Stainless steel X6Cr17
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K3 (EN 60721)
Max. permissible relative humidity (operation) ≤ 100 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)

Overvoltage category
EN 61010-1 II
EN 62477-1 III
Safety for measurement, control, and laboratory equipment
Standards/specifications IEC 61010-1
Protective extra-low voltage
Standards/specifications EN 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Explosive atmospheres
Standards/specifications IEC 60079-0
IEC 60079-7
IEC 60079-11
IEC 60079-15
Mains voltage dips
Standards/specifications EN 61000-4-29

UL
Identification UL Listed UL 61010-1
 II 3 G Ex ec ic nC IIC T4 Gc
UL
Identification UL Listed UL 61010-2-201
Ex ec ic nC IIC T4 Gc
UL
Identification UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification CAN/CSA-C22.2 No. 61010-1-12
CSA
Identification CAN/CSA-IEC 61010-2-201:14
SIQ
Identification Type tested (type approved)
SIQ
Identification CB scheme (IEC 61010-1, IEC 61010-2-201)
Shipbuilding
Identification DNV GL
Shipbuilding
Identification ABS
ATEX
Identification SIQ 21 ATEX 024 X
 II 3 G Ex ec ic nC IIC T4 Gc
IECEx
Identification IECEx SIQ 19.0003X
Ex ec ic nC IIC T4 Gc

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant IEC 61850-3
EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
DNV GL conducted interference Class B
Additional text Bridge and deck area
DNV GL noise radiation Class B
Additional text Bridge and deck area
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.7 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Comments Criterion A
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Comments Criterion A
Voltage dips
Standards/regulations EN 61000-4-29
Voltage 24 V DC
Voltage dip 70 %
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Time 50 ms
Additional text Test Level 2
Comments Criterion B
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 3)
Voltage 10 V 1 V
Test level 2 150 Hz 1.5 kHz (Test Level 3)
Voltage 1 V
Test level 3 1.5 kHz 15 kHz (Test Level 3)
Voltage 1 V 10 V
Test level 4 15 kHz 150 kHz (Test Level 3)
Voltage 10 V
Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage 10 V (Permanent)
Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Voltage 100 V (1 s)
Comments Criterion A
Alternating component of direct voltage
Standards/regulations EN 61000-4-17
Alternating component 15 % (UN)
Frequency 50 Hz
100 Hz
150 Hz
Comments Criterion A
Alternating component 14 % (UN)
Frequency 300 Hz
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Input, output (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage 1 kV
Input, output (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Input, output (test level 3) 10 MHz (Test Level 2 - asymmetrical)
Voltage 0.5 kV
Signals (test level 1) 100 kHz 1 MHz (Test Level 2 - symmetrical)
Voltage 0.5 kV
Signals (test level 2) 100 kHz 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Item number 2910132
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C13
Product Key CMDI43
GTIN 4055626536699
Weight per Piece (including packing) 834.6 g
Weight per Piece (excluding packing) 834 g
Customs tariff number 85044030
Country of origin TH


ECLASS

ECLASS-9.0 27210901
ECLASS-10.0.1 27210901
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

EAC

Approval ID: RU S-DE.BL08.W.00764

LR

Approval ID: 17-20107-03

NK

Approval ID: TA21182M

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

BV

Approval ID: 57060/A1 BV

EAC

Approval ID: RU S-DE.BL08.W.00764

cUL Listed

Approval ID: FILE E 123528

UL Listed

Approval ID: FILE E 123528

NK

Approval ID: TA21182M

LR

Approval ID: 17-20107-03

DNV

Approval ID: TAA00000BV

DNV

Approval ID: TAA00000BV

IECEx

Approval ID: IECEx SIQ 19.0003X

ATEX

Approval ID: SIQ 21 ATEX 024 X

IECEx

Approval ID: IECEx SIQ 19.0003X

ATEX

Approval ID: SIQ 21 ATEX 024 X

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Most powerful output side: easy system expansion, reliable heavy load startup and miniature circuit breaker tripping
Most comprehensive signaling: preventive function monitoring reports critical operating states before errors occur
Protective coating and ATEX/IECEx approval