VAL-US-SPP-240D/65/2+0-R
   - 
  Surge protection device
    
      1790786
      
      
    
  
      Surge protective device, UL Listed type 1 and IEC type 2, for power supply systems with corner-grounded Delta configuration for 240 V AC, replaceable surge protection plugs with local status indicator (green/red), with plug-in remote signaling.
Product details
| General | |
| Note | Only for use in IT systems between L-PE if the common earthing of the HV transformer station and conductive parts of the LV consumer system are interconnected (RE = RA & RE = Z according to IEC 60364-4-44:2024, Figure 1 and Table 1). | 
| Product type | Surge protection for NEMA power supply units | 
| Product family | VAL-SPP | 
| IEC test classification | II | 
| T2 | |
| EN type | T2 | 
| IEC power supply system | IT | 
| Type | DIN rail module, two-section, divisible | 
| Number of positions | 2 | 
| Surge protection fault message | Optical, remote indicator contact | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Pollution degree | 3 | 
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Indicator/remote signaling | |
| Connection name | Remote fault indicator contact | 
| Switching function | Changeover contact | 
| Max. required back-up fuse | 1 A (gG) | 
| AC operating voltage | 5 V AC ... 250 V AC | 
| AC operating current | 5 mA AC ... 1 A AC | 
| DC operating voltage | 30 V DC | 
| DC operating current | 1 A DC | 
| DC operating voltage | 125 V DC | 
| DC operating current | 200 mA DC | 
| Insulation type | The product has double/reinforced insulation between the main and auxiliary circuit. | 
| Connection method | Screw connection | 
| Screw thread | M5 | 
| Tightening torque | 3 Nm ... 3.5 Nm | 
| Stripping length | 18 mm | 
| Conductor cross-section flexible | 1.5 mm² ... 35 mm² (without ferrule) | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section rigid | 1.5 mm² ... 50 mm² | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section AWG | 15 ... 2 | 
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 1.5 mm² ... 16 mm² | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 1.5 mm² ... 35 mm² | 
| 2x 1.5 mm² ... 10 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section flexible, with ferrule without plastic sleeve | 1.5 mm² ... 25 mm² | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Connection method | Fork-type cable lug | 
| Conductor cross-section flexible | 1.5 mm² ... 25 mm² | 
| Remote fault indicator contact | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 0.75 mm² | 
| Dimensional drawing |  | 
| Width | 35.6 mm | 
| Height | 109.1 mm | 
| Depth | 71.5 mm (incl. DIN rail 7.5 mm) | 
| Horizontal pitch | 2 Div. | 
| Color | gray (RAL 7042) | 
| light gray (RAL 7035) | |
| Flammability rating according to UL 94 | V-0 | 
| CTI value of material | 600 | 
| Insulating material | PA 6.6-FR 20 % GF | 
| PBT | |
| Material group | I | 
| Housing material | PA 6.6-FR 20 % GF | 
| PBT | 
| Mechanical data | |
| Open side panel | No | 
| Mode of protection | L-PE | 
| Nominal voltage UN | 240 V AC ±10 % (IT) | 
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Maximum continuous operating voltage UC | 275 V AC | 
| Rated load current IL | 80 A (25 mm²) | 
| Standby power consumption PC | ≤ 248 mVA | 
| Nominal discharge current In (8/20) µs | 20 kA | 
| Short-circuit current rating ISCCR | 50 kA | 
| Voltage protection level Up | ≤ 1.35 kV | 
| Residual voltage Ures | ≤ 1.35 kV (at In) | 
| TOV behavior at UT | 350 V AC (5 s / withstand mode) | 
| 460 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns | 
| Max. backup fuse with V-type through wiring | 80 A (gG) | 
| Max. backup fuse with branch wiring | 315 A (gG) | 
| Ambient conditions | |
| Degree of protection | IP20C (Installed) | 
| Ambient temperature (operation) | -40 °C ... 85 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Ambient temperature (assembly) | -5 °C ... 50 °C | 
| Altitude | ≤ 2000 m (amsl) | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) | 
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) | 
| UL specifications | |
| Maximum continuous operating voltage MCOV (L-L) | 550 V AC | 
| Maximum continuous operating voltage MCOV (L-G) | 275 V AC | 
| Short-circuit current rating (SCCR) | 200 kA | 
| Voltage protection rating VPR (L-L) | 1800 V | 
| Voltage protection rating VPR (L-G) | 1000 V | 
| Nominal discharge current In | 20 kA | 
| Maximum Surge Current per Phase | 1x 65 kA (IEEE C62.73) | 
| Mode of protection | L-L | 
| L-G | |
| Nominal voltage | 240 V AC | 
| Power distribution system | Delta | 
| Nominal frequency | 50/60 Hz | 
| SPD Type | 1 | 
| UL indicator/remote signaling | |
| Operating voltage | 250 V AC | 
| DC operating voltage | 30 V DC | 
| AC operating current | 5 mA AC ... 1 A AC | 
| DC operating current | 1 A DC | 
| UL connection data | |
| Tightening torque | 30 lbf-in. | 
| Conductor cross-section AWG | 14 ... 2 | 
| Standards/specifications | IEC 61643-11 | 
| Note | 2011 | 
| Standards/specifications | EN 61643-11 | 
| Note | 2012 + A11:2018 | 
| Mounting type | DIN rail: 35 mm | 
| Item number | 1790786 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | CL138U | 
| GTIN | 4067923410374 | 
| Weight per piece (including packing) | 264.3 g | 
| Weight per piece (excluding packing) | 239.7 g | 
ECLASS
| ECLASS-13.0 | 27171202 | 
| ECLASS-15.0 | 27171202 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-E No hazardous substances above the limits | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Benzene-1,2,4-tricarboxylic acid 1,2 anhydride (CAS: 552-30-7) | 
Compatible products
Your advantages
Universal surge protective device (SPD) with UL Listed type 1 and IEC type 2: suitable for all common supply system configurations and supply voltages in North America
        Minimal maintenance with replaceable surge protection plugs
        Clear status indication with local optical green/red display and plug-in remote signaling for quick and easy installation
        Simple planning with comprehensive digital data
        Miswiring and touch protection for safe installation