DC/DC converters - QUINT4-PS/24DC/24DC/20/SC/+
1046881

Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking),- 24 V DC, output: 24 V DC / 20 A

Free Download available. Downloads

Product Details




Nominal input voltage range 24 V DC
Input voltage range 24 V DC -25 % ... +40 %
Wide-range input no
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 2.7 A
Inrush current integral (I2t) < 0.2 A2s
Inrush current limitation 2.7 A (after 1 ms)
Mains buffering time typ. 16 ms (24 V DC)
Current consumption 27 A (24 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Recommended breaker for input protection 50 A (Characteristic B, C or comparable)
Signal Remote (configurable)
Connection labeling 3.3 +
Function Output power ON/OFF (remote)
Default Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)

Efficiency typ. 94.7 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 20 A
Static Boost (IStat.Boost) 25 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
Selective Fuse Breaking (ISFB) 120 A (15 ms)
Magnetic circuit breaker tripping A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Short-circuit-proof yes
No-load proof yes
Output power (PN) 480 W
Output power (PStat. Boost) 600 W
Output power (PDyn. Boost) 720 W (5 s)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Residual ripple < 50 mVPP
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Rise time < 100 ms (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 4 W
Power loss nominal load max. < 26.6 W
Power dissipation SLEEP MODE < 2 W
Connection in parallel yes, for redundancy and increased capacity
Signal Out 1 (configurable)
Connection labeling 3.5 +
Digital 0 V DC
24 V DC
20 mA
Signal option Output voltage
Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Default UIN input voltage OK
Signal Out 2 (configurable)
Connection labeling 3.6 +
Digital 0 V DC
24 V DC
20 mA
Default Output power
Signal option Output voltage
Output current
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Analog 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Signal option Output voltage
Output current
Output power
Signal relay 13/14 (configurable)
Connection labeling 3.1, 3.2
Switch contact (floating) floating
Maximum contact load 24 V DC
1 A
30 V AC
0.5 A
Default Output voltage
Signal option Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
UIN input voltage OK
Signal ground SGnd
Connection labeling 3.4 +
Function Signal ground
Reference potential to OUT1, OUT2, REM

Input
Position 1.x
Conductor connection
Connection method Screw connection
rigid 0.75 mm² ... 16 mm²
flexible 0.75 mm² ... 16 mm²
flexible with ferrule without plastic sleeve 0.75 mm² ... 16 mm²
flexible with ferrule with plastic sleeve 0.75 mm² ... 16 mm²
rigid (AWG) 20 ... 6
Stripping length 18 mm
Tightening torque 1.4 Nm ... 1.7 Nm
Drive form screw head Slotted L
Output
Position 2.x
Conductor connection
Connection method Screw connection
rigid 0.2 mm² ... 6 mm²
flexible 0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 4 mm²
rigid (AWG) 24 ... 10
Stripping length 10 mm
Tightening torque 0.6 Nm ... 0.8 Nm
Drive form screw head Slotted L
Signal
Position 3.x
Conductor connection
Connection method Push-in connection
rigid 0.2 mm² ... 1 mm²
flexible 0.2 mm² ... 1.5 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 0.75 mm²
rigid (AWG) 24 ... 16
Stripping length 8 mm

Types of signaling LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal threshold > 100 % (LED lights up yellow, output power > 480 W)
> 75 % (LED lights up green, output power > 360 W)
> 50 % (LED lights up green, output power > 240 W)
> 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
> 0.8 x UInNom (LED off)
< 0.8 x UInNom (LED lights up yellow)

Number of phases 1.00
Insulation voltage input/output 4 kV DC (type test)
2 kV DC (routine test)
Switching frequency 190 kHz ... 220 kHz (Auxiliary converter stage)
67 kHz ... 135 kHz (Main converter stage)

Product type DC/DC converters
MTBF (IEC 61709, SN 29500) > 1034000 h (25 °C)
> 577000 h (40 °C)
> 229000 h (60 °C)
Insulation characteristics
Protection class Special with SELV input and output
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 10 A
Temperature 40 °C
Time 413707 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 20 A
Temperature 40 °C
Time 139340 h
Additional text 24 V DC
Life expectancy (electrolytic capacitors)
Current 20 A
Temperature 30 °C
Time 278680 h
Additional text 24 V DC

Width 70 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left (active) 15 mm / 15 mm
Installation distance right/left (passive) 5 mm / 5 mm
Installation distance top/bottom (active) 50 mm / 50 mm
Installation distance top/bottom (passive) 50 mm / 50 mm
Alternative assembly
Width 122 mm
Height 130 mm
Depth 73 mm

Mounting type DIN rail mounting
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
With protective coating yes

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Hood version Stainless steel X6Cr17
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5 Hz ... 100 Hz resonance search 2.3g, 90 min, resonance frequency 2.3g, 90 min

Overvoltage category
EN 61010-1 II (≤ 5000 m)
EN 62477-1 III (≤ 5000 m)
Safety for measurement, control, and laboratory equipment
Standards/specifications IEC 61010-1
Protective extra-low voltage
Standards/specifications EN 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Explosive atmospheres
Standards/specifications IEC 60079-0
IEC 60079-7
IEC 60079-11
IEC 60079-15
Mains voltage dips
Standards/specifications EN 61000-4-29
Railway applications
Standards/specifications EN 50121-3-2
EN 50121-4
IEC 62236-3-2
IEC 62236-4

UL
Identification UL Listed UL 61010-1
UL
Identification UL Listed UL 61010-2-201
UL
Identification UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification CAN/CSA-C22.2 No. 61010-1-12
CSA
Identification CAN/CSA-IEC 61010-2-201:14
SIQ
Identification Type tested (type approved)
SIQ
Identification CB scheme (IEC 61010-1, IEC 61010-2-201)
ATEX
Identification SIQ 21 ATEX 287 X
 II 3 G Ex ec ic nC IIC T4 Gc
IECEx
Identification IECEx SIQ 20.0002X
Ex ec ic nC IIC T4 Gc
Identification SIL 2
UKEX
Identification EXV21UKEX1073X
Shipbuilding
Identification DNV
Shipbuilding
Identification ABS
Shipbuilding
Identification LR
Shipbuilding
Identification NK

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant IEC 61850-3
EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
DNV GL conducted interference Class B
Additional text Bridge and deck area
DNV GL noise radiation Class B
Additional text Bridge and deck area
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.7 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Comments Criterion A
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Comments Criterion A
Voltage dips
Standards/regulations EN 61000-4-29
Voltage 24 V DC
Voltage dip 70 %
Time 100 ms
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Time 100 ms
Additional text Test Level 2
Comments Criterion B
Voltage dip 0 %
Time 50 ms
Additional text Test Level 2
Comments Criterion B
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 3)
Voltage 10 V 1 V
Test level 2 150 Hz 1.5 kHz (Test Level 3)
Voltage 1 V
Test level 3 1.5 kHz 15 kHz (Test Level 3)
Voltage 1 V 10 V
Test level 4 15 kHz 150 kHz (Test Level 3)
Voltage 10 V
Test level 5 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage 10 V (Permanent)
Test level 6 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Voltage 100 V (1 s)
Comments Criterion A
Alternating component of direct voltage
Standards/regulations EN 61000-4-17
Alternating component 10 % (UN)
Frequency 50 Hz
100 Hz
150 Hz
Comments Criterion A
Alternating component 10 % (UN)
Frequency 300 Hz
Comments Criterion A
Attenuated oscillating wave
Standards/regulations EN 61000-4-18
Input, output (test level 1) 1 MHz (Test Level 2 - symmetrical)
Voltage 0.5 kV
Input, output (test level 2) 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Input, output (test level 3) 10 MHz (Test Level 2 - asymmetrical)
Voltage 0.5 kV
Signals (test level 1) 1 MHz (Test Level 2 - symmetrical)
Voltage 0.5 kV
Signals (test level 2) 1 MHz (Test Level 2 - asymmetrical)
Voltage 1 kV
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Item number 1046881
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C13
Product Key CMDI43
GTIN 4055626645629
Weight per Piece (including packing) 1,569.2 g
Weight per Piece (excluding packing) 1,200 g
Customs tariff number 85044030
Country of origin TH


ECLASS

ECLASS-9.0 27210901
ECLASS-10.0.1 27210901
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

IECEE CB Scheme

Approval ID: SI-7748

BV

Approval ID: 57060/A1 BV

CSA

Approval ID: 80031630

ABS

Approval ID: 21-2073195-PDA

NK

Approval ID: TA21182M

LR

Approval ID: 17-20107-03

Type approved

Approval ID: SI-SIQ BG 005/076

cULus Listed

Approval ID: FILE E 123528

CSA

Approval ID: 80031630

IECEE CB Scheme

Approval ID: SI-7748

LR

Approval ID: 17-20107-03

NK

Approval ID: TA21182M

ABS

Approval ID: 21-2073195-PDA

cULus Listed

Approval ID: FILE E 123528

Type approved

Approval ID: SI-SIQ BG 005/076

DNV

Approval ID: TAA00000BV

DNV

Approval ID: TAA00000BV

cULus Listed

Approval ID: FILE E 199827

ATEX

Approval ID: BVS 20 ATEX E 028 X

NEPSI

Approval ID: GYJ21.1001X

IECEx

Approval ID: SIQ 20.0002X

ATEX

Approval ID: SIQ 21 ATEX 287 X

IECEx

Approval ID: SIQ 20.0002X

NEPSI

Approval ID: GYJ21.1001X

ATEX

Approval ID: BVS 20 ATEX E 028 X

cULus Listed

Approval ID: FILE E 199827

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Most powerful output side: easy system expansion, reliable heavy load startup and miniature circuit breaker tripping
Most comprehensive signaling: preventive function monitoring reports critical operating states before errors occur
Integrated decoupling MOSFET for 1+1 and n+1 redundancy