Controller - ILC 191 ME/AN
2700074

Inline controller with integrated pulse/direction/PWM interface, RS-485/RS-422, analog inputs (0 ... 10 V), and analog outputs (0 ... 10 V), with programming options according to IEC 61131-3

Downloads

Product Details


The ILC 191 ME/AN is a reliable compact controller for the Inline I/O system. The controller uses directly alignable Inline I/O modules and also is notable for supporting a number of Ethernet-based protocols such as Modbus/TCP or PROFINET.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Type modular
Product type Controller
Display
Diagnostics display No

Transmission medium Copper
Real-time clock
Realtime clock Yes
Description realtime clock Integrated (rechargeable battery buffered)
Potentials: 24 V supply UILC
Supply voltage 24 V DC -15 % / +20 % (according to EN 61131-2)
Supply voltage range 19.2 V DC ... 30 V DC
Potentials: 7.5 V communications power UL (potential jumper)
Supply voltage 7.5 V DC ±5 %
max. 0.8 A DC (observe derating)
Potentials: 24 V analog supply UANA (potential jumper)
Supply voltage 24 V DC -15 % / +20 %
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
0.5 A DC (observe derating)
Potentials: 24 V main supply UM
Supply voltage 24 V DC -15 % / +20 % (according to EN 61131-2)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 8 A DC (sum of UM + US)
Current draw max. 8 A DC
6 mA (without sensors)
Potentials: 24 V segment supply US
Supply voltage 24 V DC -15 % / +20 % (according to EN 61131-2)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 8 A (sum of UM + US)
Current draw max. 8 A DC
10 mA (without actuators)

Analog
Input name Analog inputs
Number of inputs 2
A/D converter resolution 11 bit
Connection method Inline potential distributor
Connection technology 2-conductor
Note regarding the connection technology Inline potential distributor
Voltage input signal 0 V DC ... 10 V DC (Resolution: 11 bits)
Input resistance of voltage input typ. 324 kΩ
Limit frequency (3 dB) 100 Hz
Common mode voltage range signal - ground 0 V ... 10 V
Digital
Input name Digital inputs
Description of the input EN 61131-2 type 1 NPN/PNP
Number of inputs 8
Cable length max. 30 m
Connection method Inline potential distributor
Connection technology 2-, 3-, 4-conductor
Input voltage range -0.5 V ... 30 V
Input voltage range "0" signal -0.5 V ... 5 V
Input voltage range "1" signal 15 V ... 30 V
Nominal input current at UIN typ. 7 mA
max. 15 mA
Input filter time typ. 5 ms ()
typ. 5 ms ()
Typical response time min. 3 ms

Analog
Output name Analog outputs
Connection method Inline potential distributor
Connection technology 2-conductor
Number of outputs 2
D/A conversion time 10 ms
D/A converter resolution 11 bit
Voltage output signal 0 V DC ... 10 V DC
Load/output load voltage output > 1 kΩ
Digital
Output name Digital outputs
Connection method Spring-cage connection
Connection technology 2-, 3-, 4-conductor
Number of outputs 4
Output voltage 24 V DC
Maximum output current per channel 500 mA
Maximum output current per module / terminal block 2 A
Nominal load, lamp 12 W
Nominal load, ohmic 12 W
Pulse direction
Output name Pulse directional output for 5 V signals
Number of pulse direction outputs 2 (can be used as an alternative to pulse width modulation)
Output voltage 5 V ±5 %
Limit frequency 150 kHz

Inline connector
Connection method Spring-cage connection
Conductor cross section, rigid 0.08 mm² ... 1.5 mm²

Web server yes
Ethernet 10Base-T/100Base-TX
Bus system RJ45
Number of interfaces 2
Connection method RJ45 jack
Transmission speed 10/100 Mbps
No. of channels 2
INTERBUS local bus (master)
Number of interfaces 1
Connection method Inline data jumper
Transmission speed 500 kBaud / 2 MBaud (can be switched)
Parameterization/operation/diagnostics
Bus system RS-232
Number of interfaces 1
Connection method 6-pos. MINI DIN socket (PS/2)
Transmission speed max. 115.2 kbps
Transmission physics Copper
No. of channels 1
RS-422/-485
Bus system RS-485/-422
Number of interfaces 1
Connection method 4-pos. for full duplex
2-pos. for half duplex

Processor Altera Nios II 64 MHz
Retentive data storage 48 kByte (NVRAM)
IEC 61131 runtime system
Program memory 1 Mbyte
Data storage 1 Mbyte
Number of control tasks 8
INTERBUS-Master
Amount of process data max. 4096 Bit (INTERBUS)
Number of supported devices max. 128
Number of local bus devices that can be connected max. 63 (observe current consumption)
Number of devices with parameter channel max. 24
Number of supported branch terminals with remote bus branch max. 3
Modbus/TCP-Client
Amount of process data max. 32768 Bit (internal Modbus /TCP client)
Number of Modbus/TCP clients max. 16 later than FW 4.42
PROFINET
Device function PROFINET device
Specification 2.2
Function
Diagnostics display No
Controller redundancy No
Safety function No

Functionality
Programming languages supported Instruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
System requirements
Engineering tool PC Worx
PC Worx Express
Configuration tool Config+ Version 1.01 or later
Diagnostics tool DIAG+
Runtime system eCLR
Application interface OPC

Width 164 mm
Height 136.8 mm
Depth 71.5 mm

Color green

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Shock 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation) 5g
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity

Conformance with EMC directives Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 EN 55011 Class A
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU

Mounting type DIN rail mounting

Item number 2700074
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key DRAAAA
Product Key DRAAAA
Catalog Page Page 50 (C-6-2019)
GTIN 4046356479097
Weight per Piece (including packing) 624.3 g
Weight per Piece (excluding packing) 450 g
Customs tariff number 85371091
Country of origin DE


ECLASS

ECLASS-9.0 27242207
ECLASS-10.0.1 27242207
ECLASS-11.0 27242207

ETIM

ETIM 8.0 EC000236

UNSPSC

UNSPSC 21.0 32151700

EAC

Approval ID: RU *-DE.A*30.B.00238

UL Listed

Approval ID: FILE E 140324

cUL Listed

Approval ID: FILE E 140324

ATEX

Approval ID: PxCIF12ATEX2700074X

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Memory extendable by up to 2 GB via plug-in SD card
Free engineering with PC Worx Express (IEC 61131-3)
Complete INTERBUS master (4096 I/O points)
PROFINET-Device
Modbus/TCP-Client
Integrated FTP and HTML5 web server
Numerous protocols supported such as: HTTP, FTP, SNTP, SNMP, SMTP, SQL, MySQL, etc.
Integrated analog I/Os
Integrated RS-485/RS-422 interface