PLT-EE-T3-24DC-P
-
Type 3 surge protection plug
1249053
Replacement plug for type 3 surge protection from the PLT-EE product range. 24 V nominal voltage
Product details
Product type | Replacement plug |
IEC power supply system | TN-S |
Type | Male |
Number of positions | 2 |
Surge protection fault message | optical |
Data management status | |
Article revision | 03 |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
IEC test classification | III |
T3 | |
EN type | T3 |
Number of ports | One |
Connection method | pluggable |
Dimensional drawing | |
Width | 17.5 mm |
Height | 46.8 mm |
Depth | 62.7 mm |
Horizontal pitch | 1 Div. |
Color | traffic grey B (RAL 7043) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6-FR 20 % GF |
PA 6.6-FR | |
Housing material | PA 6.6-FR 20 % GF |
PA 6.6-FR |
Mode of protection | L-N |
L-PE | |
N-PE | |
Nominal voltage UN | 24 V AC (TN-S) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 34 V AC |
Residual current IPE | ≤ 5 µA |
Standby power consumption PC | ≤ 2.70 mVA (at UREF) |
≤ 4.80 mVA (at UC) | |
Reference test voltage UREF | 27 V AC |
Nominal discharge current In (8/20) µs | 1 kA |
Combination wave UOC | 2 kV |
Voltage protection level Up (L-N) | ≤ 0.2 kV |
Voltage protection level Up (L-PE) | ≤ 0.6 kV |
Voltage protection level Up (N-PE) | ≤ 0.6 kV |
TOV behavior at UT (L-N) | 50 V AC (120 min / withstand mode) |
TOV behavior at UT (L-PE) | 50 V AC (120 min / withstand mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Short-circuit current rating ISCCR | 6 kA AC |
Max. backup fuse with branch wiring | 16 A (gG / B / C) |
Additional technical data | |
Short-circuit current rating ISCCR | 3 kA DC (for 16 A gG / B backup fuse) |
Residual voltage Ures (L-N) | ≤ 0.16 kV (at 0.5 kA) |
≤ 0.2 kV (at 1 kA) | |
Residual voltage Ures (L-PE) | ≤ 0.35 kV (at 0.5 kA) |
≤ 0.4 kV (at 1 kA) | |
Residual voltage Ures (N-PE) | ≤ 0.35 kV (at 0.5 kA) |
≤ 0.4 kV (at 1 kA) | |
Maximum continuous voltage UC | 34 V DC |
Mode of protection | (DC+) - (DC-) |
(DC+/DC-) - PE |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (operating voltage remote contact ≤ 250 V) |
≤ 6000 m (operating voltage remote contact ≤ 150 V) | |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
Standards/specifications | IEC 61643-11 |
Note | 2011 |
EN 61643-11 | |
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting type | on base element |
Item number | 1249053 |
Packing unit | 10 pc |
Minimum order quantity | 1 pc |
Sales key | CL1 |
Product key | CLP312 |
GTIN | 4063151351854 |
Weight per piece (including packing) | 37.77 g |
Weight per piece (excluding packing) | 34 g |
Customs tariff number | 85363030 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27130890 |
ECLASS-13.0 | 27171292 |
ETIM
ETIM 9.0 | EC002496 |
UNSPSC
UNSPSC 21.0 | 39121600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
EF3.0 Climate Change | |
CO2e kg | 0.491 kg CO2e |