PT 1X2-12AC-ST
-
Surge protection plug
2856045
PT protective connector with protective circuit for a 2-wire floating signal circuit. HART-compatible.
This product needs further products for operation.
Mandatory accessories
Product details
| General | |
| Note | Technical data is valid in association with the following specified base elements: |
| PT 1X2+F-BE 2856126 | |
| PT 1X2-BE 2856113 | |
| Product type | Surge protection for MCR technology |
| Product family | PLUGTRAB PT |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | Male |
| Number of positions | 2 |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
| Wire pairs per module | 1 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 12 V AC |
| Connection method | Screw connection (in connection with the base element) |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross-section AWG | 24 ... 12 |
| Dimensional drawing |
|
| Width | 17.7 mm |
| Height | 45 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module width | 17.7 mm |
| Complete module height | 90 mm |
| Complete module depth | 65.5 mm |
| Flammability rating according to UL 94 | V-0 |
| Housing material | PA 6.6 |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Nominal voltage UN | 12 V AC |
| Maximum continuous operating voltage UC | 18 V DC |
| 13 V AC | |
| Rated current | 450 mA (45 °C) |
| Operating effective current IC at UC | ≤ 5 A |
| Protective conductor current IPE | ≤ 1 µA (with PT 1X2+F-BE) |
| ≤ 2 µA (with PT 1X2-BE) | |
| Nominal discharge current In (8/20) µs (line-line) | 10 kA |
| Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp (10/350) µs | 2.5 kA |
| Total discharge current ITotal (8/20) µs | 20 kA |
| Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 49 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 25 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (with PT 1X2-BE) |
| ≤ 1 kV (with PT 1X2+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 25 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V (with PT 1X2-BE) |
| ≤ 50 V (with PT 1X2+F-BE) | |
| Residual voltage at In (conductor-conductor) | ≤ 25 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 31 V |
| Voltage protection level Up (line-line) | ≤ 55 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (line-earth) | ≤ 450 V (C1 - 1 kV / 500 A with PT 1X2-BE) |
| ≤ 1000 V (C2 - 10 kV / 5 kA with PT 1X2+F-BE) | |
| Voltage protection level Up static (line-line) | ≤ 25 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up static (line-earth) | ≤ 50 V (C2 - 10 kV / 5 kA with PT 1X2-BE) |
| ≤ 100 V (C2 - 10 kV / 5 kA with PT 1X2+F-BE) | |
| Response time tA (line-line) | ≤ 1 ns |
| Response time tA (line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 700 kHz/50 Ω) |
| typ. 0.2 dB (≤ 250 kHz / 150 Ω) | |
| typ. 0.1 dB (≤ 60 kHz/600 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 4 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 1.5 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ω system | typ. 400 kHz |
| Capacity (Core-Core) | typ. 2.5 nF |
| Capacity (Core-Earth) | typ. 4 pF (with PT 1X2-BE) |
| typ. 2 pF (with PT 1X2+F-BE) | |
| Resistance per path | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV / 5 kA |
| C3 - 49 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| D1 - 2.5 kA |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl) |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 + A2:2013 |
| Mounting type | on base element |
| Item number | 2856045 |
| Packing unit | 10 pc |
| Minimum order quantity | 1 pc |
| Product key | CL2111 |
| GTIN | 4017918599195 |
| Weight per piece (including packing) | 19.99 g |
| Weight per piece (excluding packing) | 15.763 g |
| Country of origin | DE |
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
X-PEN 0,35 - Marker pen 0811228
-
ZBF 5:UNBEDRUCKT - Zack Marker strip, flat 0808642
-
ZBF 5/WH-100:UNBEDRUCKT - Zack Marker strip, flat 0808668
-
ZBF 5,LGS:FORTL.ZAHLEN - Zack Marker strip, flat 0808671
-
ZBF 5,LGS:GERADE ZAHLEN - Zack Marker strip, flat 0810821
-
ZBF 5,LGS:UNGERADE ZAHLEN - Zack Marker strip, flat 0810863
-
ZBF 5,QR:FORTL.ZAHLEN - Zack Marker strip, flat 0808697
-
ZBN 18:UNBEDRUCKT - Zack marker strip 2809128
-
SSA 3-6 - Shield connection 2839295
-
SSA 5-10 - Shield connection 2839512