ESSENTIAL-PS/1AC/24DC/240W/EE
-
Power supply
2910587
Primary-switched ESSENTIAL edition power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/240 W
Product details
AC operation | |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
Derating | < 100 V (1 %/V) |
Input voltage range AC | 85 V AC ... 264 V AC |
Input voltage range DC | 120 V DC ... 375 V DC |
Inrush current | typ. 20 A (115 V AC) |
typ. 40 A (230 V AC) | |
AC frequency range | 47 Hz ... 63 Hz |
Mains buffering time | typ. 10 ms (115 V AC) |
typ. 20 ms (230 V AC) | |
Current consumption | 2.8 A (115 V AC) |
1.4 A (230 V AC) | |
Nominal power consumption | 273.22 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | 1000 ms |
Input fuse | 6.3 A (slow-blow, internal) |
Discharge current to PE | < 1 mA (264 V AC) |
Efficiency | 88 % (115 V AC) |
90 % (230 V AC) | |
Output characteristic | HICCUP |
Nominal output voltage | 24 V DC ±2 % |
Setting range of the output voltage (USet) | 22 V DC ... 28 V DC (max. power ≤ 240 W) |
Nominal output current (IN) | 10 A |
Derating | > 40 °C (1.67 % / °C, 115 V AC) |
> 50 °C (2.5 % / °C, 230 V AC) | |
Max. capacitive load | 8000 μF |
Active current limitation | 105% - 150% of the max. output power (in the event of short circuit) |
Control deviation | ≤ 1 % (change in load, static 10 % ... 90 %) |
typ. ± 2 % (change in load, dynamic 10 % ... 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 120 mVPP (-10 °C ... +70 °C) |
< 240 mVPP (-20 °C ... -10 °C) | |
Output power | 240 W |
Maximum no-load power dissipation | 4.62 W (115 V AC) |
2.14 W (230 V AC) | |
Power loss nominal load max. | 31.53 W (115 V AC) |
25.44 W (230 V AC) |
Input | |
Connection method | Screw connection |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Output | |
Connection method | Screw connection |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Types of signaling | LED |
Operating voltage display | Green LED |
Signal output | |
Status display | "DC OK" LED green |
Number of phases | 1 |
Insulation voltage input/output | 3 kV AC |
Insulation voltage output / PE | 0.5 kV AC |
Insulation voltage input / PE | 2 kV AC |
Product type | Power supply |
Product family | ESSENTIAL POWER |
MTBF (Telcordia SR-332) | > 700000 h |
Insulation characteristics | |
Protection class | I (with PE connection) |
Degree of pollution | 2 |
Dimensional drawing |
|
Width | 60 mm |
Height | 123.6 mm |
Depth | 117.6 mm |
Installation dimensions | |
Installation distance right/left | 10 mm / 10 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting type | DIN rail mounting |
Assembly note | alignable: horizontally 10 mm, vertically 50 mm |
With protective coating | no |
Housing material | Metal |
Housing material | Aluminum |
Type of housing | Steel sheet, zinc-plated |
Side element version | Aluminum |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | IEC 60068-2-27, 27, half sinusoidal wave: 50g for 11 ms; 3x per direction, 9x overall |
Vibration (operation) | IEC 60068-2-6, sinusoidal waves: 10 Hz ... 500 Hz, 19,6 m/s² (2g peak), 10 min. per cycle, 60 min. in the X direction |
Standard - Electrical safety | EN 60950-1 |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47 - 0706 (200 V AC) |
CSA | CSA-C22.2 Nr. 107.1-01 |
CSA-C22.2 Nr. 60950-01 | |
UL approvals | UL/C-UL listed UL 508 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements for noise immunity | EN 61000-6-1 |
EN 61000-6-2 | |
Noise emission | |
Standards/regulations | EN 55011 (EN 55022) Class B |
Emitted interference | |
Standards/regulations | EN 61000-6-3 |
Item number | 2910587 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CMP |
Product key | CMB313 |
GTIN | 4055626464404 |
Weight per piece (including packing) | 972.3 g |
Weight per piece (excluding packing) | 800 g |
Customs tariff number | 85044095 |
Country of origin | IN |
ECLASS
ECLASS-13.0 | 27040701 |
ETIM
ETIM 9.0 | EC002540 |
UNSPSC
UNSPSC 21.0 | 39121000 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-10
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Your advantages
Worldwide use thanks to the wide range input and international approval package
Fast installation, thanks to easy DIN rail mounting
Greater availability, thanks to fanless convention cooling